Инструкция на Внутренние блоки VRF-системы V4+ (сервис мануалы)
Внутренние блоки кассетного типа MDV-D18Q1/N1-D, MDV-D22Q1/ N1-D, MDV-D28Q1/VN1-D, MDV-D36Q1V/N1-D. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
1. Features
1.1 New panel The panel has digital display function, which can show temperature and warning message. 1.2 Compact design Slim body needs only 153 mm space above the ceiling. 1.3 Parts inside installation The throttling components and water pump are internally installed which means a lower cost, no…
-
1.7 Built-in water pump with 750mm pump head
1.8 Prevent condensation in air outlet by the patent of a new structure design By the adoption of this structure, the guide wing will always wrapped up by dry cold air, cutting off the contact route of moist hot air and the cold guide wing. As a result, the water vapour in mosit hot air gets no…
-
2. Specifications
MDV-D18Q1/N1-D Model Power supply Cooling Heating Indoor fan motor V-Hz-Ph kW Input W 41 41 Rated current A 0.24 0.24 Capacity kW 2.2 2.6 Input W 41 41 Rated current A 0.24 0.24 2.2 RPS12N Type Single-phase AC motor Brand Welling/ Broad-ocean Input(H/M/L) W 29.5/26.7/25.0 29.5/26.7/25.0 Capacitor μF…
-
Model Power supply Cooling Heating Indoor fan motor V-Hz-Ph 220-240V/50Hz/1Ph Capacity kW Input W 41 41 Rated current A 0.25 0.25 Capacity kW 3.2 4.0 Input W 41 41 Rated current A 0.25 0.25 2.8 3.6 Model RPS12N Type Single-phase AC motor Brand Welling/ Broad-ocean Input W 31.0/27.2/25.3…
-
3. Dimensions
-
4. Service Spaces
MDV-D18Q1/N1-D MDV-D22Q1/N1-D MDV-D28Q1/N1-D MDV-D36Q1/N1-D Please avoid installing in the following places : A place with flammable gas or material. A saline place such as a seashore vicinity. A place with sulphur gas. A place with oil gas,such as kitchen. A place with high-humidity air. An…
-
5. Piping Diagrams
-
6. Wiring Diagrams
MDV-D18Q1/N1-D MDV-D22Q1/N1-D MDV-D28Q1/N1-D HP set switch ENC1 definition list Indoor Unit Code Capacity Value 0 1800W(0.6HP) 0 2200W(0.8HP) 1 2800W(1.0HP) 2 3600W(1.2HP) 3 4500W(1.5HP) 4 5600W(2.0HP) 5 7100W(2.5HP) 6 8000W(3.0HP) 7 9000W(3.2HP) 8 11200W(4.0HP) 9 14000W(5.0HP) Code FM GM DM CS PMV…
-
7. Capacity Tables
-
7.2 Heating
-
Indoor temperature (℃ DB)
-
8. Electric Characteristics
Model Indoor Unit Power Supply IFM Hz Voltage(V) Min. (V) Max. (V) MCA MFA KW FLA MDV-D18Q1/N1-D 50 220-240 198 242 0.169 15 0.012 0.135 MDV-D22Q1/N1-D 50 220-240 198 242 0.169 15 0.012 0.135 MDV-D28Q1/N1-D 50 220-240 198 242 0.178 15 0.012 0.142 MDV-D36Q1/N1-D 50 220-240 198 242 0.178 15 0.012…
-
9. Sound Levels
-
17 Indoor unit
-
10. Accessories
Standard accessories Name Quantity Outline Indoor unit installation manual 1 This manual Installation paper plate 1 For installing the suspender and cutting the ceiling Protection sleeve for refrigerant inlet and outlet pipes 2 For heat insulation of the pipe connections Fastening belt 10 For…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.