1. Nomenclature
Main features for MDV product only: Possibility to connect additional air heater, electrical or water. Capacity of the additional heater can be calculated according to the air flow of HRV and the ambient temp. 1. If temperature of inlet air lower than -5'C, electricity auxiliary switch ON. 2. If…
-
3. Features
HRV (Heat Recovery Ventilation) employ advanced technique and technics, the heat exchanged core forming by special paper that be processed with chemical treatment, which could create the optimum result in temperature, humidity and cooling recovery. High efficiency heat exchanged core: When air flow…
-
50Hz HRV 4. Specifications Sale Model HRV-200 HRV-300 HRV-400 V-Ph-Hz 220V-1Ph-50Hz 220V-1Ph-50Hz 220V-1Ph-50Hz Temp. efficiency % Enthalpy % Temp. efficiency % Enthalpy % YDK-10-4 992A1 YDK-20-4 992A2 YDK-40-4 991A2T Insulation class B B B Safe class IP34 IP34 IP34 Power supply Cooling Heating…
-
Sale Model
HRV-500 HRV-800 HRV-1000 V-Ph-Hz 220V-1Ph-50Hz 220V-1Ph-50Hz 220V-1Ph-50Hz Temp. efficiency % Enthalpy % Temp. efficiency % Enthalpy % YDK-60-4 991T YDK-180-4 990B1T YDK-180-4 990A4T Insulation class B B B Safe class IP34 IP34 IP34 Power supply Cooling Heating efficiency efficiency Model Indoor…
-
Sale Model HRV-1500 HRV-2000 V-Ph-Hz 380V-3Ph-50HZ 380V-3Ph-50HZ Temp. efficiency % 60 60 Enthalpy % 50 50 Temp. efficiency % 70 70 Enthalpy % 60 60 SYB-250I (0.45-4) SYB-250II (0.45-4) B B IPX4 IPX4 Power supply Cooling Heating efficiency efficiency Model Insulation class Indoor fan motor Safe…
-
5. Dimension
-
50Hz HRV 5.3 HRV-1500 5.4 HRV-2000 Dimension 9
-
6. Maintenance Space
10 Maintenance Space
-
50Hz HRV 7. Wiring Diagrams 7.1 HRV-200 HRV-300 7.2 HRV-1500 HRV-2000 Wiring Diagrams HRV-400 HRV-500 HRV-800 HRV-1000 11
-
8. Electric Characteristics
Model Indoor Unit Power Supply IFM Hz Voltage Min. Max. MCA MFA KW FLA HRV-200 0.625 15 0.02 0.5 HRV-300 0.7 15 0.04 0.56 HRV-400 1.25 15 0.08 1 HRV-500 1.25 15 0.12 1 HRV-800 2.5 15 0.36 2 HRV-1000 0.36 2.4 HRV-1500 0.9 3.2 HRV-2000 4.5 15 1.1 3.6 Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse…
-
50Hz HRV 9. Operation Condition Limits Model Outdoor air temperature Room temperature Room humidity Lower than 80% All models -7℃~43℃ -7℃~43℃ If higher than 80%, the surface of indoor unit may be condensed or the condensate will be blown from air outlet. Operation Condition Limits 13
-
10. Exploded View
10.1 HRV-200 14 HRV-300 HRV-400 HRV-500 HRV-800 HRV-1000 Exploded View
-
50Hz HRV NO. Part Name Quantity 1.1 Inlet channel 2 1.2 Bypass part 1 1.3 Partition board 2 1.4 Electrical box 1 1.5 Electrical box ass'y (RoHS) 1 1.6 Chassis 1 1.7 Heat exchange core 1 1.8 Inlet/Outlet air 4 1.9 Fan Motor 2 1.10 Motor bracket 2 1.11 Guide plate 2 1.12 Motor capacitor 2 1.13 Fan…
-
10.2 HRV-1500
16 MCAC-KTSM-2011-04 HRV-2000 NO. Part Name Quantity 1.1 Chassis 1 1.2 Electrical box 1 1.3 Electrical box ass'y (RoHS) 1 1.4 Heat exchange core 2 1.5 Inlet/Outlet air 4 1.6 Fan 2 1.7 Room temp sensor ass'y (RoHS) 1 1.8 Temp. sensor (T1) (RoHS) 1 1.9 Display board ass'y (M54) (RoHS) 1 2 Wire…
-
50Hz HRV 11. Blast Pressure Graphic HRV-300 Air flow (m3/h) Air flow (m3/h) HRV-200 External static pressure (Pa) External static pressure (Pa) HRV-500 Air flow (m3/h) Air flow (m3/h) HRV-400 External static pressure (Pa) External static pressure (Pa) HRV-1000 Air flow (m3/h) Air flow (m3/h) HRV-800…
-
External static pressure (Pa)
18 HRV-2000 Air flow (m3/h) Air flow (m3/h) HRV-1500 External static pressure (Pa) Blast Pressure Graphic
-
50Hz HRV 12. Installation 12.1 Installation Preparation Warning: The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them. 1) Leave the unit inside its packaging while moving, until reaching the installation site. Where…
-
electric parts box so that the air filters, heat exchange elements, fans, can easily be inspected and serviced.) 2. Make sure the range of the unit’s external static pressure is not exceeded. 3. Open the installation hole (Pre-setting ceilings) Once the installation hole is opened in the ceiling…
-
50Hz HRV 13. Wiring Warning: Before obtaining access to terminal device, all power supply circuits must be interrupted. 13.1 Precautions When Laying Power Supply Wiring A circuit breaker of shutting down power supply to the entire system be installed. A single switch can be used to supply power to…
-
13.3 System connection diagram
Caution: 1. Never turn screws too tightly, or else the cover would be dented or the Liquid Crystal breaks. 2. Please leave enough space for maintain and upkeep the wire controller. 22 Wiring
-
50Hz HRV 14. Troubleshooting 14.1 Lamp flashes: No. Operation lamp Timer lamp Defrosting lamp Alarm lamp Explanation 1 ★ ○ ○ ○ T4 sensor error 2 ★ ★ ○ ○ T1 sensor error 3 ★ ○ ★ 4 ★ ○ ○ Current protection ★ Phase absent, phase error Note: ●:Light, ○:Extinguish, ☆:Slow flash, ★:Quick flash HRV-200…
-
14.2 Troubleshooting
T4 sensor error / T1 sensor error Yes Check whether the wiring of the temp. sensor is break off Connect the wiring well No Check whether the resistance of temp. sensor is wrong refer to the Annex 1 Yes Replace temp. sensor No Replace main controller panel Current protection Check: whether the…
-
50Hz HRV Phase absent, phase error Check: whether Lack of phase . No Check the connection between power supply and terminal, is the voltage in outdoor terminal is 3 phase. Connect it well. Yes Check: whether Phase sequence error Change the order of two of the wires to power supply. Switch on the…
-
15. Maintenance
1. 2. 3. 4. 26 During new use stage, one should check the fan operation regularly. The cleaning regulation for filter mesh depends on local environment. It could be clean by vacuum dirt exhauster or water, if heavy dust accumulates, it should use neutral detergent to clean it, and then dry it in…
-
50Hz HRV 16. Controller KJR-27B/E: The basic operation conditions of wired controller are as follows: 1. The range of power supply voltage: the voltage input is 5V DC. 2. Ambient temperature range: -15℃~+43℃. 3. Ambient humidity range: RH40%~RH90%. 4. The safety certification of electric control…
-
exit, the current clock will display
6 RESET button (hidden): Use a small stick with a diameter of 1mm to push the RESET button to cancel the current settings and get into the condition of resetting 7 ON/OFF button: Push the button at the condition of OFF, the OPERATION lamp lights, and the wire controller enters into ON operation…
-
50Hz HRV 4 CLOCK display Usually display the clock set currently. Press the button CLOCK for 4 seconds, the HOUR part will flash, press button ▲and▼ to adjust HOUR. Press the button CLOCK again, the minute part flash, press button ▲or▼to adjust MINUTE. After clock set or clock operation, it must…
-
17. Accessory
Name Quantity Installation and owner’s manual Butt-joint wire of wire control display panel (6 meters) HRV wire controller shape 1 Purpose must be delivered to the customer For connect wire control and display control box 1 For controlling HRV units 1 Annex 1 Characteristic of temp. sensor 30 Temp.℃…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.