Инструкция на VRF-системы V4 (сервис мануалы)
Наружные блоки (220) серии MDV-V80W/N1, MDV-V105W/N1-B, MDV-V105W/BDRN1, MDV-V105W/N1, MDV-V140W/N1, MDV-V140W/BDRN1, MDV-V160W/BDRN1. Сервис мануал.
Смотрите также: Коды ошибок CCM03 →
Загружаем документ…
Текст инструкции
-
Contents
Part 1 General Information 1 Part 2 Outdoor Units 5 Part 3 Installation 80 Manufacture reserves the right to discontinue, or change at any time, specifications or designs without notices and without incurring obligations.
-
Part 1
General Information General Information 1. Product Lineup 2 2. Nomenclature 3 3. Features 4 General Information 1
-
Product Lineup
-
Nomenclature
-
Product Lineup
MHVAC-HTSM-2011-07 3. Features 1. From 2.2kW to 16kW with different type indoor units, it is full compliance with residential and light commercial place. 2. Only two main refrigerant lines (liquid pipe and gas pipe) are required in one system. 3. In some large residential spaces or some light…
-
MCAC-DTSM-2011-07
1. Specifications Sale Model Power supply Cooling Heating V-ph-Hz MDV-V80W/N1 MDV-V105W/N1 220-240, 1, 50 220-240, 1, 50 10.5 Capacity kW 8 Input kW 2.56 3.26 Capacity kW 9 12.2 Input W 2.71 3.38 5216 Max. input consumption W 3766 Max. current A 17.3 25.4 TNB220FLHMC TNB306FPGM Model Compressor…
-
Dimensions
Sale Model Power supply Cooling Heating V-ph-Hz MDV-V105W/N1-B MDV-V140W/N1 220-240, 1, 50 220-240, 1, 50 Capacity kW 10.5 14 Input kW 3.26 4.36 Capacity kW 12.2 15 Input W 3.38 4.13 Max. input consumption W 4757 5770 Max. current A Model Compressor Outdoor fan motor Rotary Rotary Brand Mitsubishi…
-
MCAC-DTSM-2011-07
Sale Model Power supply V-Ph-Hz kW kW kW kW W A Capacity Input Capacity Heating Input Max. input consumption Max. current Model Type Brand Capacity Btu/h Compressor Input W Rated current(RLA) A Crankcase W Refrigerant oil ml Model Type Brand Insulation class Safe class Outdoor fan motor Input W…
-
Dimensions
-
Service Space
MHVAC-HTSM-2011-07 3. Service Space >300 Single unit installation (Wall or obstacle) Air inlet >300 N Maintain channel >600 P M Air outlet >6 0 c m >2000 Air inlet Fix with bolt 10 Outdoor Units
-
Piping Diagrams
4. Piping Diagrams MDV-V80W/N1 MDV-V105W/N1 MDV-V105W/N1-B MDV-V140W/N1 MDV-V105W/BDRN1 MDV-V140W/BDRN1 MDV-V160W/BDRN1-B Electronic expansion valve High pressure switch Evaporator Electronic expansion valve Compressor Oil separator Condenser High pressure liquid accumulator can Oil return Capillary…
-
5. Wiring Diagrams
-
Outdoor Units Wiring Diagrams MDV-V140W/N1 13
-
14 Outdoor Units
-
Outdoor Units 15
-
16 Outdoor Units
-
6. Field Wiring
-
Field Wiring
18 MHVAC-HTSM-2011-07 Outdoor Units
-
7. Capacity Tables
-
20 MHVAC-HTSM- 2011-07 33.00 5.94 1.56 7.09 2.00 8.17 2.47 8.29 2.49 8.40 2.50 8.60 2.52 8.83 2.55 35.00 5.94 1.66 7.09 2.14 8.03 2.56 8.14 2.58 8.26 2.59 8.46 2.62 8.69 2.64 37.00 5.94 1.77 7.09 2.27 7.91 2.66 8.03 2.67 8.11 2.68 8.34 2.71 8.54 2.73 39.00 5.94 1.88 7.09 2.42 7.77 2.75 7.89 2.76…
-
50% Outdoor Units Capacity Tables 43.00 10.00 4.31 1.29 5.14 1.58 5.97 1.95 6.40 2.18 6.83 2.36 7.66 2.82 7.73 2.83 3.77 0.62 4.51 0.73 5.23 0.85 5.60 0.92 5.97 0.98 6.69 1.12 7.43 1.26 12.00 3.77 0.62 4.51 0.74 5.23 0.87 5.60 0.94 5.97 1.00 6.69 1.14 7.43 1.28 14.00 3.77 0.63 4.51 0.76 5.23 0.88…
-
-10 7.06 2.83 7.03 2.91 7.03 3.00 7.00 3.04 7.00 3.08 6.97 3.17 -8.5 -9.1 7.20 2.86 7.17 2.95 7.17 3.03 7.17 3.07 -7 -7.6 7.46 2.92 7.46 3.00 7.43 3.08 7.43 3.12 7.14 3.11 7.14 3.19 7.43 3.16 7.40 -5 -5.6 7.86 2.99 7.83 3.07 7.83 3.14 7.80 3.24 3.18 7.80 3.22 7.77 -3 -3.7 8.23 3.06 8.23 2.78 8.20…
-
50% 24 MHVAC-HTSM- 2011-07 9.8 7.10 1.84 6.70 1.73 6.30 1.62 6.07 1.56 5.87 1.51 5.47 1.40 13 11.8 7.10 1.74 6.70 1.64 6.30 1.53 6.07 1.48 5.87 1.43 5.47 1.33 15 13.7 7.10 1.65 6.70 1.55 6.30 1.45 6.07 1.41 5.87 1.36 5.47 1.27 -13.7 -15 6.09 3.22 5.74 3.00 5.40 2.78 5.23 2.67 5.06 2.57 4.71 2.36…
-
26 MHVAC-HTSM- 2011-07 37.00 7.71 2.30 9.10 2.86 10.50 3.43 11.14 3.71 11.78 4.00 12.03 4.02 12.29 4.06 39.00 7.71 2.31 9.10 2.87 10.50 3.44 11.14 3.73 11.78 4.02 12.03 4.03 12.29 4.07 41.00 7.71 2.32 9.10 2.89 10.50 3.46 11.14 3.75 11.78 4.04 12.03 4.05 12.29 4.09 43.00 10.00 7.71 2.33 9.10 2.90…
-
50% Outdoor Units Capacity Tables 10.00 5.09 0.68 6.01 0.84 6.93 1.01 7.35 1.09 7.77 1.18 7.94 1.18 8.11 1.20 12.00 5.09 0.69 6.01 0.86 6.93 1.03 7.35 1.11 7.77 1.20 7.94 1.21 8.11 1.22 14.00 5.09 0.70 6.01 0.87 6.93 1.05 7.35 1.14 7.77 1.22 7.94 1.23 8.11 1.24 16.00 5.09 0.71 6.01 0.89 6.93 1.07…
-
-10 8.81 2.88 8.81 2.94 8.81 3.01 8.46 2.87 8.11 2.74 7.41 2.48 -8.5 -9.1 9.02 2.90 9.02 2.97 9.02 3.03 8.66 2.90 8.30 2.76 7.59 2.50 -7 -7.6 9.33 2.94 9.33 3.00 9.33 3.06 8.96 2.93 8.59 2.79 7.85 2.53 -5 -5.6 9.74 2.98 9.74 3.04 9.74 3.11 9.35 2.97 8.96 2.84 8.19 2.56 -3 -3.7 10.15 3.02 10.15 3.09…
-
50% 30 MHVAC-HTSM- 2011-07 9.8 8.54 2.03 8.54 2.07 8.54 2.11 8.20 2.02 7.86 1.93 7.18 1.74 13 11.8 8.54 1.95 8.54 2.00 8.54 2.04 8.20 1.95 7.86 1.86 7.18 1.68 15 13.7 8.54 1.88 8.54 1.92 8.54 1.96 8.20 1.88 7.86 1.79 7.18 1.62 -14.7 -15 4.65 1.56 4.65 1.59 4.65 1.62 4.46 1.55 4.28 1.48 3.91 1.34…
-
32 MHVAC-HTSM- 2011-07 37.00 10.40 3.01 12.40 3.87 13.85 4.52 14.05 4.54 14.20 4.57 14.60 4.61 14.95 4.65 39.00 10.40 3.20 12.40 4.13 13.60 4.68 13.80 4.70 14.00 4.72 14.35 4.77 14.75 4.82 41.00 10.40 3.23 12.40 4.16 13.49 4.71 13.69 4.73 13.89 4.76 14.17 4.80 14.31 4.85 43.00 10.00 10.40 3.26 12.40…
-
50% Capacity Tables 10.00 6.60 1.05 7.90 1.25 9.15 1.45 9.80 1.56 10.45 1.67 11.70 1.90 13.00 2.14 12.00 6.60 1.06 7.90 1.26 9.15 1.48 9.80 1.59 10.45 1.70 11.70 1.94 13.00 2.18 14.00 6.60 1.08 7.90 1.29 9.15 1.50 9.80 1.62 10.45 1.73 11.70 1.97 13.00 2.22 16.00 6.60 1.10 7.90 1.31 9.15 1.53 9.80…
-
70% 60% -5 -3 -14.7 -12.6 -10.5 -9.5 -8.5 -7 -5 -3 -14.7 -12.6 -10.5 -9.5 -8.5 -7 -5 -3 -14.7 -12.6 -10.5 -9.5 -8.5 -7 -5 -3 -14.7 -12.6 -10.5 -9.5 -8.5 Outdoor Units -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -15 -13 -11 -10 -9.1…
-
36 -7 -5 -3 -14.7 -12.6 -10.5 -9.5 -8.5 -7 -5 -3 MHVAC-HTSM- 2011-07 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 10.14 10.14 10.14 10.14 10.14 10.14 10.14 10.14 10.14 10.14 10.14 8.45 8.45 8.45 8.45 8.45 8.45 8.45 8.45 8.45…
-
38 MHVAC-HTSM- 2011-07 37.00 7.71 1.22 9.11 1.51 10.50 1.81 11.14 1.97 11.78 2.12 12.04 2.13 12.29 2.15 39.00 7.71 1.22 9.11 1.52 10.50 1.82 11.14 1.97 11.78 2.13 12.04 2.14 12.29 2.16 41.00 7.71 1.23 9.11 1.53 10.50 1.83 11.14 1.98 11.78 2.14 12.04 2.15 12.29 2.17 43.00 7.71 1.23 9.11 1.53 10.50…
-
50% Outdoor Units Capacity Tables 10.00 5.09 0.70 6.01 0.87 6.93 1.05 7.35 1.14 7.77 1.22 7.94 1.23 8.11 1.24 12.00 5.09 0.71 6.01 0.89 6.93 1.07 7.35 1.16 7.77 1.25 7.94 1.25 8.11 1.26 14.00 5.09 0.73 6.01 0.91 6.93 1.09 7.35 1.18 7.77 1.27 7.94 1.27 8.11 1.29 16.00 5.09 0.74 6.01 0.92 6.93 1.10…
-
70% Outdoor Units Capacity Tables -9.5 -10 8.31 3.08 8.31 3.14 8.31 3.21 7.98 3.07 7.65 2.93 6.99 2.65 -8.5 -9.1 8.50 3.10 8.50 3.17 8.50 3.23 8.16 3.09 7.83 2.95 7.15 2.67 -7 -7.6 8.79 3.14 8.79 3.20 8.79 3.27 8.44 3.13 8.09 2.98 7.40 2.70 -5 -5.6 9.18 3.18 9.18 3.25 9.18 3.32 8.81 3.17 8.45 3.03…
-
50% 42 9.8 8.05 2.17 8.05 2.21 8.05 2.26 7.73 2.16 7.41 2.06 6.77 1.86 13 11.8 8.05 2.09 8.05 2.13 8.05 2.18 7.73 2.08 7.41 1.99 6.77 1.80 15 13.7 8.05 2.01 8.05 2.05 8.05 2.10 7.73 2.00 7.41 1.91 6.77 1.73 -14.7 -15 4.38 1.66 4.38 1.70 4.38 1.73 4.21 1.66 4.03 1.58 3.69 1.43 -12.6 -13 4.62 1.69…
-
44 MHVAC-HTSM- 2011-07 37.00 10.29 1.47 12.14 1.83 14.00 2.19 14.85 2.37 15.71 2.56 16.05 2.57 16.39 2.59 39.00 10.29 1.47 12.14 1.84 14.00 2.20 14.85 2.38 15.71 2.57 16.05 2.58 16.39 2.60 41.00 10.29 1.48 12.14 1.84 14.00 2.21 14.85 2.39 15.71 2.58 16.05 2.59 16.39 2.61 43.00 10.29 1.49 12.14 1.85…
-
50% Outdoor Units Capacity Tables 10.00 6.79 0.85 8.01 1.05 9.24 1.26 9.80 1.37 10.36 1.48 10.59 1.48 10.81 1.50 12.00 6.79 0.86 8.01 1.07 9.24 1.29 9.80 1.40 10.36 1.50 10.59 1.51 10.81 1.52 14.00 6.79 0.88 8.01 1.09 9.24 1.31 9.80 1.42 10.36 1.53 10.59 1.54 10.81 1.55 16.00 6.79 0.89 8.01 1.11…
-
70% Capacity Tables -9.5 -10 11.20 3.51 11.20 3.59 11.20 3.66 10.75 3.50 10.31 3.34 9.42 3.02 -8.5 -9.1 11.46 3.54 11.46 3.62 11.46 3.69 11.00 3.53 10.55 3.37 9.64 3.04 -7 -7.6 11.85 3.58 11.85 3.66 11.85 3.73 11.38 3.57 10.91 3.41 9.97 3.08 -5 -5.6 12.37 3.63 12.37 3.71 12.37 3.79 11.88 3.62 11.39…
-
50% 48 MHVAC-HTSM- 2011-07 9.8 10.85 2.47 10.85 2.52 10.85 2.58 10.42 2.46 9.99 2.35 9.13 2.13 13 11.8 10.85 2.38 10.85 2.43 10.85 2.48 10.42 2.38 9.99 2.27 9.13 2.05 15 13.7 10.85 2.29 10.85 2.34 10.85 2.39 10.42 2.29 9.99 2.18 9.13 1.97 -14.7 -15 5.90 1.90 5.90 1.94 5.90 1.98 5.67 1.89 5.44 1.81…
-
50 MHVAC-HTSM- 2011-07 37.00 11.51 3.17 13.73 4.09 15.33 4.77 15.56 4.79 15.72 4.82 16.17 4.87 16.55 4.91 39.00 11.51 3.37 13.73 4.35 15.06 4.94 15.28 4.96 15.50 4.98 15.89 5.03 16.33 5.08 41.00 11.51 3.41 13.73 4.39 14.94 4.97 15.16 4.99 15.38 5.02 15.69 5.07 15.84 5.12 43.00 11.51 3.44 13.73 4.44…
-
50% Outdoor Units Capacity Tables 10.00 7.31 1.11 8.75 1.31 10.13 1.53 10.85 1.65 11.57 1.77 12.95 2.01 14.39 2.26 12.00 7.31 1.12 8.75 1.33 10.13 1.56 10.85 1.68 11.57 1.80 12.95 2.05 14.39 2.30 14.00 7.31 1.14 8.75 1.36 10.13 1.59 10.85 1.70 11.57 1.83 12.95 2.08 14.39 2.34 16.00 7.31 1.16 8.75…
-
-9.1 14.00 5.10 13.94 5.25 13.94 5.39 13.94 5.47 13.89 5.55 13.89 5.69 -7 -7.6 14.50 5.20 14.50 5.34 14.44 5.48 14.44 5.56 14.44 5.63 14.39 5.77 -5 -5.6 15.28 5.33 15.22 5.46 15.22 5.60 15.17 5.66 15.17 5.73 15.11 5.87 -3 -3.7 16.00 5.45 16.00 4.95 15.94 5.71 15.94 5.77 15.94 5.83 15.28 5.59 0 -0.7…
-
50% 54 MHVAC-HTSM- 2011-07 13 11.8 13.80 3.10 13.03 2.92 12.25 2.73 11.81 2.64 11.42 2.55 10.64 2.37 15 13.7 13.80 2.94 13.03 2.77 12.25 2.59 11.81 2.51 11.42 2.42 10.64 2.26 -14.7 -15 11.83 5.75 11.17 5.34 10.50 4.96 10.17 4.77 9.83 4.58 9.17 4.21 -12.6 -13 11.83 5.44 11.17 5.06 10.50 4.70 10.17…
-
8. Electric Characteristics
-
9. Sound Levels
-
10.Operation Limits
Outdoor Units 57
-
11.Troubleshooting
11.1 Troubles and causes of air conditioner If one of the following malfunctions occur, stop operation, shut off the power, and contact with your dealer. ■ The operation lamp is flashing rapidly (twice every second) This lamp is still flashing rapidly after turn off the power and turn on again. ■…
-
11.2 Troubles and causes of remote controller
Before asking for serving or repairing, check the following points. Symptoms Causes Solution Check whether the MODE indicated on the display is "AUTO" When the automatic mode is selected, the air conditioner will automatically change the fan speed. Check whether the MODE indicated on the display is…
-
11.3 Malfunction Code of Indoor unit
(1) For the Four-way Cassette (New designed): No. Malfunction Operation 1 Communication malfunction between in-outdoor unit 2 Room temperature sensor malfunction 3 Pipe temperature sensor malfunction 4 Pipe temperature sensor malfunction 5 Water level checking malfunction 6 EEPROM malfunction 7 Mode…
-
(3) For the other type indoor unit
No Troubleshooting Display Contents Malfunction 1 All lamps are off Standing-by 2 Operation lamp is on ON 3 PRE./DEF. lamp is on Anti-cooling or Defrosting 4 Timer lamp is on Timer function is on 5 Timer lamp flashes Indoor/outdoor communication malfunction 6 Operation lamp flashes Indoor unit’s…
-
① Indoor/outdoor communication malfunction
MHVAC-HTSM-2011-07 Indoor / outdoor communication alfunction Short circuit or open circuit of communication wire P, Q and E OK Repetition of address code to indoor unit Some indoor units are not power-on (reduction in the number of indoor units) Irregular connection of communication wire (causing E2…
-
Note
Press the “manual” button on remote control receiver of indoor unit in turn (display the address code of this indoor unit when pressing and holding for 5 seconds (display capacity code when pressing and holding for 10 seconds), check all address codes. Codes to be inspected are as follows: Indicator…
-
② Indoor unit’s temp. Sensor malfunction
MHVAC-HTSM-2011-07 Indoor unit’s temp. Sensor malfunction T1, T2 or T2B Connecting wire between sensorOK and mainboard gets loose Exist OK Temperature sensor is short-circuited or punctured Exist Reconnect and ensure that the connection is reliable. Replace sensor OK Chip fault, or chip foot sheds…
-
③ Mode-confliction malfunction
In the below table, “Yes” indicates existing mode conflict, “No” indicates no mode conflict. Troubleshooting Cooling Heating Air-supply OFF Cooling No Yes No No Heating Yes No Yes No Air-supply No Yes No No OFF No No No No When indoor unit receiving heating operation instruction, it will transmit…
-
⑤ EEPROM malfunction
EEPROM malfunction Yes EPROM chip is broken Replace EPROM No Yes Check whether the main control chip 9177 is broken Replace EPROM No Check PCB board or replace the main control board ⑥ Outdoor malfunction or protection Examine outdoor unit, and analyze according to actual condition ⑦ Congealing Dew…
-
11.4 Malfunction Code of Outdoor unit
Display Malfunction or Protection E0 EEPROM malfunction E2 Communication malfunction between indoor/outdoor units E3 Communication malfunction between DSP/Outdoor units E4 T4 temperature sensors malfunction E5 Outdoor unit voltage protection E6 PFC module protection (single-phase) P1 High pressure…
-
1) E0 malfunction
MHVAC-HTSM-2011-07 LED indicates E0 EEPROM malfunction No Judge 1: Check whether the EEPROM is inserted well Insert the EEPROM well Yes Replace the outdoor main board 68 Outdoor Units
-
2) E2 malfunction
Troubleshooting LED indicates E2 Communication malfunction between indoor/outdoor units No Judge 1: Check whether the indoor unit power is on Turn on the indoor unit power Yes Judge 2: Check whether the signal wiring is shield cable or whether the shield cable is grounded No Adopt the shield cable/…
-
3) E3 malfunction
MHVAC-HTSM-2011-07 LED indicates E3 Communication malfunction in outdoor PCB Check whether the indicator lights LED1 or LED2 on the main control board are flashing Yes Replace PCB No Yes Install the IC-U3 chip of the PCB over again, check whether the system can run normally Trouble is solved No Yes…
-
4) E4 malfunction
Troubleshooting LED indicates E4 Judge 1: Outdoor condenser’s middle temp. sensor (T3) is malfunction Check whether the wiring of the condenser’s middle temp. sensor is break off Yes Connect the wiring well No Check whether the resistance of condenser’s middle temp. sensor is wrong refer to the…
-
5) E5 malfunction
MHVAC-HTSM-2011-07 LED indicates E5 Outdoor unit voltage protection Check the voltage of outdoor unit power supply, whether the voltage between L1 and N is about 198--252V No Check the power supply Yes Replace the filter board, then check whether the system can run normally Yes Trouble is solved No…
-
6) E6 malfunction(for single phase)
Troubleshooting LED indicates E6 PFC module protection Check whether the connecting line between main board and the PFC module is connected tightly Check whether the voltage between P and N of IPM module is 270-380V No Connect it tightly, check normal or not Replace the outdoor main board Replace…
-
7) P1 malfunction
MHVAC-HTSM-2011-07 LED indicates P1 High pressure protection No Judge 1: Whether the wiring between the high pressure switch and main control board is connected well or correctly Connect it well Yes Judge 2: Whether the high pressure switch is broken Validate: Short connect the high pressure switch…
-
8) P2 malfunction
Troubleshooting LED indicates P2 Low pressure protection Judge 1: The wiring between the low pressure switch and main control board is connected well or correctly No Connect it well Yes Judge 2: Whether the low pressure switch is broken Yes Validate: Short connect the low pressure switch socket…
-
9) P3 malfunction
MHVAC-HTSM-2011-07 LED indicates P3 Outdoor unit current protection No Judge 1: Check whether the input current of the power supply wire is more than 15A Replace the filter board, then check whether the system can run normally Yes No Yes Trouble is solved Replace outdoor PCB Check whether the…
-
10) P4 malfunction
When compressor discharge temperature is more than 115°C, the unit will stop, and unit runs again when compressor discharge temperature is less than 90°C. LED indicates P4 Compressor discharge temperature protection Yes Check whether the compressor discharge temp. more than 115°C ? No Check whether…
-
11) P5 malfunction
When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C. LED indicates P5 Condenser high temperature protection Yes Check whether the condenser temperature is more than 65°C No Check whether the resistance of condenser temp. sensor…
-
12) P6 malfunction
Troubleshooting LED indicates P6 IPM protection Check whether the voltage range of P-N on IPM module is normal? DC 310-650V No Check whether the input power supply is correct? 380-415V, 3N, 50Hz 220V-240V,1N,50Hz Yes Regulate it to correct, then check whether the system can work normally? Yes Check…
-
1.Summarize of Installation
1.1 Installation Procedure Installation 81
-
1.2 Install indoor units
Procedure: Confirm installation position Label installation position Install hooks Install indoor units Note: (1) The hook must strong enough to sustain the weight of indoor unit. (2) Check the models of indoor units before installation. (3) Pay attention to the main devices, such as the pipeline.…
-
1.7 Heat-insulation
Procedure: Refrigerant pipe work Check the heat-insulated part Pressure test Heat-insulation work Note: For welding part, flare part and branch pipe, heat-insulation work must be done after finished the pressure test. 1.8 Install outdoor unit Note: (1) Gutter must be set around the foundation to…
-
Installation of Indoor Unit
MHVAC-HTSM-2011-07 2.Installation of Indoor Unit 2.1 Hanging and Transportation Please refer to Indoor unit Installation Manual. 2.2 Required Installation Place Cassette Type Type A B One-way Cassette Four-way Cassette C 1000mm above 1000mm above 2300mm above 2.2.1 Duct Type 2.2.2 Wall Mounted Type…
-
Installation of Indoor Unit
2.2.3 Ceiling and floor Wall mounting installation: D. Connecting point of refrigerant pipe (D. gas side) Drain point Hook E. Connecting point of refrigerant pipe (E. Liquid side) 2.2.4 Ceiling installation: Hanging arm E. Connecting point of refrigerant pipe (E. Liquid side) D. Connecting point of…
-
Outdoor Units Installation
MHVAC-HTSM- 2011-07 3.Installation of Outdoor Unit 3.1 Installation place Please keep away from the following place, or malfunction of the machine may be caused: There is combustible gas leakage. There is much oil (including engine oil) ingredient. There is salty air surrounding (near the…
-
Outdoor Units Installation
NOTE All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased (depend on model).The actual shape shall Prevail. Installation 87
-
4.Installation of Refrigerant Pipe
CAUTION To prevent the refrigerant piping from oxidizing inside when welding, it is necessary to charge nitrogen, or oxide will chock the circulation system. 4.1 Length and Drop Height Permitted of the Refrigerant piping Permitted value Piping ≤100m L1+L2+L3+L4+L5+L6 +A+B+C+D+E Actual Length ≤45m…
-
4.2 Pipe size selection
4.2.1 Selection of the refrigerant pipe Type of the pipe Connecting part No. Main pipe Between outdoor branch joint and first branch joint 1 Indoor main pipe Indoor pipe Between indoor branch joint 2 Between branch part and indoor unit 3 A 4.2.2 How to choose the Branch part and the refrigerant…
-
joint for indoor units
A≤16.6kW Ф19.1 Ф9.5 FQZHN-01C 16.6≤A≤230 Ф22.2 Ф9.5 FQZHN-02C 4.2.5 Select the indoor pipe 3: A: the total capacity and the gas side/liquid side pipe of indoor units Indoor unit capacity(×100W) Pipe diameter (R410A) Liquid pipe (mm) Gas pipe (mm) ≤45 Ф6.4 Ф12.7 ≥56 Ф9.5 Ф15.9 4.2.6 Modification main…
-
4.3 Refrigerant Amount to be added
Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit connection. Table 6-8 Liquid Side Piping Diameter Refrigerant to be added Per meter Piping Φ6.4 0.022kg Φ9.5 0.060kg Φ12.7 0.110kg Φ15.9 0.190kg Φ19.1 0.290kg Φ22.2…
-
5.Processing & Installation of Drainage Pipe
5.1 Gradients and Supporting 5.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble. 5.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the…
-
5.3 Upward drainage (drain pump)
5.3.1 For Four-way cassette(compact) 5.3.1 For Four-way cassette 5.4 Convergent drainage 5.4.1 The number of indoor units should be as small as possible to prevent the traverse main pipe overlong. 5.4.2 Indoor unit with drain pump and indoor unit without drain pump should be in different drainage…
-
5.5 Drainage test
5.5.1 Drainage without drain pump After finishing drainpipe installation, pour some water into the water plate to check if the water flows smoothly. 5.5.2 Drainage with drain pump 5.5.2.1 Poke the Water Level Switch, remove the cover, and use water pipe to pour 2000ml water into the water plate…
-
Insulation Work
6.Insulation Work 6.1 Insulation material and thickness 6.1.1 Insulation material Insulation material should adopt the material, which is able to endure the pipe’s temperature: no less than 70℃ in the high-pressure side, no less than 120℃ in the low-pressure side (For the cooling type machine, no…
-
Insulation Work
MHVAC-HTSM- 2011-07 Insulate for the jointing area, expanding area and the flange area Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes Make sure there’s no clearance in the joining part of the accessorial insulation material…
-
7.Electric Installation
CAUTION Please select power source for indoor unit and outdoor unit respectively The power supply has specified branch circuit with leakage protector and manual switch. Indoor unit connect with power supply which is 220-240V~50Hz. Outdoor unit connect with power supply which is 380-415V~ 50Hz…
-
MHVAC-HTSM- 2011-07 Fig.7-1 Power supply for 3- phase Power supply for 1- phase 98 Installation
-
Fig.7-2
CAUTION The reserved function is indicated in broken line table, users can select it when necessary. Indoor/Outdoor Unit Signal Wire Connect the wire according to their numbers. Wrong connection may cause malfunction. Wiring Connection Seal the wiring connection with the insulation material, or the…
-
7.2 Indoor Unit Wiring
Power Supply Table 7-2 Capacity (Btu/h) 36000~60000 Phase indoor Unit power 1- phase Frequency and Voltage 220-240V~ 50Hz 2 Power Wiring(mm ) 3-core×1.0 Circuit Breaker/Fuse (A) 15/15 2 Indoor unit/Outdoor unit Signal wire (Weak electric signal) (mm ) 3-core shielded wire 3X0.5 1.Signal wire is…
-
Indoor unit power supply wiring
Fig.7-3 CAUTION 1. Refrigerant piping system, indoor unit-indoor unit connection signal wires and indoor unit-outdoor unit connection signal wire are in the same system. 2. When power cord is parallel with signal wire, please put them into separate wire distribution pipes, and leave a proper…
-
Test Running
MHVAC-HTSM- 2011-07 8.Test Running Operate according to “gist for test running” on the electric control box cover. CAUTION Test running can not start until the outdoor unit has been connected to the power for 12hr. Test running can not start until all the valves are affirmed open. Never make…
-
Precautions on Refrigerant Leakage
9.Precautions on Refrigerant Leakage This air conditioner (A/C) adopts innocuous and nonflammable refrigerant. The locating room of the A/C should big enough that any refrigerant leakage is unable to reach critical thickness. So certain essential action can be taken on time. Refrigerant critical…