Напольные блоки серии MDVi-D22Z/N1-F1, MDVi-D22Z/N1-F2, MDVi-D22Z/N1-F3, MDVi-D28Z/N1-F1, MDVi-D28Z/N1-F2, MDVi-D28Z/N1-F3, MDVi-D36Z/N1-F1, MDVi-D36Z/N1-F2, MDVi-D36Z/N1-F3, MDVi-D45Z/N1-F1, MDVi-D45Z/N1-F2, MDVi-D45Z/N1-F3, MDVi-D56Z/N1-F1, MDVi-D56Z/N1-F2, MDVi-D56Z/N1-F3, MDVi-D71Z/N1-F1, MDVi-D71Z/N1-F2, MDVi-D71Z/N1-F3, MDVi-D80Z/N1-F1, MDVi-D80Z/N1-F2, MDVi-D80Z/N1-F3. Сервис мануал.
Смотрите также: Коды ошибок CCM03 →
Загружаем документ…
Текст инструкции
-
Accessories
MHVAC-DTSM-2010-03 Exposed & Concealed Floor-standing Type 1.Feaures 3 2.Nomenclature 201 3.Specifications 202 4.Dimensions 209 5.Service Space 211 6. Piping Diagram 212 7. Wiring Diagram 213 8. Capacity Tables 214 9. Electric Characteristics 220 10. Sound Levels 221 11. Exploded View 222 12.…
-
Exposed & Concealed Floor-standing Type
1.Feaures Exposed Concealed+ 1. Two intake directions: front and below. 2. 3. 4. 5. 6. 7. 8. 9. Built-in the electronic throttle kit Three speeds Low noise operation. Easy installation and maintenance. Air filter easily removed and cleaned Removable blades for easy and effective cleaning Streamlined…
-
Nomenclature
2.Nomenclature MDVi-D22Z/N1-F1 F1: Exposed front intake floor-standing type F2: Exposed below intake floor-standing type F3: Concealed below intake floor-standing type Refrigerant N1: R410A R22 N2: R407C Floor-standing type indoor unit Cooling Capacity(×100W) Digital Scroll A/C System…
-
3.Specifications
Model Power supply Cooling Heating Indoor fan motor MDVi-D22Z/N1-F1 MDVi-D22Z/N1-F2 MDVi-D22Z/N1-F3 V- Ph-Hz Capacity kW 2.2 2.2 2.2 Input W Rated current A 0.19 0.19 0.19 Capacity kW 2.6 2.6 2.6 Input W Rated current A 0.19 0.19 0.19 Model YSK20-4A YSK20-4A YSK20-4A Type AC motor AC motor AC motor…
-
Model
Power supply Cooling Heating Indoor motor fan MDVi-D28Z/N1-F1 MDVi-D28Z/N1-F2MDVi-D28Z/N1-F3 V- Ph-Hz 2.8 2.8 2.8 Capacity kW Input W Rated current A 0.2 0.2 0.2 Capacity kW 3.2 3.2 3.2 Input W Rated current A 0.2 0.2 0.2 Model YSK20-4A YSK20-4A YSK20-4A Type AC motor AC motor AC motor Brand Welling…
-
Model
Power supply Cooling Heating Indoor motor fan MDVi-D36Z/N1-F1 MDVi-D36Z/N1-F2MDVi-D36Z/N1-F3 V- Ph-Hz Capacity kW 3.6 3.6 3.6 Input W Rated current A 0.15 0.15 0.15 Capacity kW 4.0 4.0 4.0 Input W Rated current A 0.15 0.15 0.15 Model YSK20-6 YSK20-6 YSK20-6 Type AC motor AC motor AC motor Brand…
-
Model
Power supply Cooling Heating Indoor fan motor MDVi-D45Z/N1-F1 MDVi-D45Z/N1-F2 MDVi-D45Z/N1-F3 V- Ph-Hz Capacity kW 4.5 4.5 4.5 Input W Rated current A 0.22 0.22 0.22 Capacity kW 5.0 5.0 5.0 Input W Rated current A 0.22 0.22 0.22 Model YSK20-6 YSK20-6 YSK20-6 Type AC motor AC motor AC motor Brand…
-
Model
Power supply Cooling Heating Indoor fan motor MDVi-D56Z/N1-F1 MDVi-D56Z/N1-F2 MDVi-D56Z/N1-F3 V-Ph-Hz 5.6 5.6 5.6 Capacity kW Input W Rated current A 0.38 0.38 0.38 Capacity kW 6.3 6.3 6.3 Input W Rated current A 0.38 0.38 0.38 Model YSK28-4E YSK28-4E YSK28-4E Type AC motor AC motor AC motor Brand…
-
Model
Power supply Cooling Heating Indoor fan motor MDVi-D71Z/N1-F1 MDVi-D71Z/N1-F2 MDVi-D71Z/N1-F3 V- Ph-Hz 7.1 7.1 7.1 Capacity kW Input W Rated current A 0.57 0.57 0.57 Capacity kW 8.0 8.0 8.0 Input W Rated current A 0.57 0.57 0.57 Model YSK74-4E YSK74-4E YSK74-4E Type AC motor AC motor AC motor Brand…
-
Model
Power supply Cooling Heating Indoor fan motor MDVi-D80Z/N1-F1 V- Ph-Hz MDVi-D80Z/N1-F3 220-240V, 1Ph, 50Hz 8.0 8.0 8.0 Capacity kW Input W Rated current A 0.56 0.56 0.56 Capacity kW 9.0 9.0 9.0 Input W Rated current A 0.56 0.56 0.56 Model YSK74-4E YSK74-4E YSK74-4E Type AC motor AC motor AC motor…
-
Dimensions
-
таблицы и схемы — в просмотре
-
Service Space
5.Service Space Version Ⅰ Vertical unit with casing, with air intake from front and air outlet on top, for installation on a wall or on feet on the floor. Version Ⅱ Vertical unit with casing, with air intake from below and air outlet on top, for installation on a wall or on feet on the floor.…
-
Piping Diagram
MHVAC-DTSM-2010-03 6. Piping Diagram motor fan T2B T1 heat exchanger flare nut EXV gas side T2 flare nut liquid side 212 Exposed & Concealed Floor-standing Type
-
Wiring Diagram
7. Wiring Diagram Exposed & Concealed Floor-standing Type 213
-
8. Capacity Tables
-
Indoor
Outdoor Unit size temperature 23.0 (kW) (℃ DB) 25.0 4.5 5.6 7.1 Capacity Tables Indoor temperature (℃ WB/DB) 2.4 2.2 3.0 2.5 3.3 2.7 3.6 2.7 3.9 2.7 4.2 2.8 4.4 2.7 2.4 2.2 3.0 2.5 3.3 2.7 3.6 2.7 3.9 2.7 4.1 2.7 4.2 2.6 27.0 2.4 2.2 3.0 2.5 3.3 2.7 3.6 2.7 3.9 2.7 4.1 2.7 4.2 2.6 29.0 2.4 2.2 3.0…
-
Indoor
Outdoor Unit size temperature 20.0 (kW) (℃ DB) 21.0 8.0 216 MHVAC-DTSM-2010-03 Indoor temperature (℃ WB/DB) 5.0 3.8 5.8 4.2 6.7 4.6 7.1 4.7 7.5 4.8 8.4 4.9 8.5 4.6 5.0 3.8 5.8 4.2 6.7 4.6 7.1 4.7 7.5 4.8 8.4 4.9 8.4 4.5 23.0 5.0 3.8 5.8 4.2 6.7 4.6 7.1 4.7 7.5 4.8 8.4 4.9 8.3 4.5 25.0 5.0 3.8 5.8…
-
8.2 Heating
-
Indoor Unit
size (kW) 4.50 5.60 7.10 218 MHVAC-DTSM-2010-03 Outdoor 2.20 temperature (℃ ) 3.00 Indoor temperature (℃ DB) 3.76 3.76 3.76 3.76 3.68 3.36 4.10 5.00 3.88 3.88 3.88 3.88 3.68 3.36 6.00 7.00 4.00 4.00 4.00 3.88 3.68 3.36 7.90 9.00 4.12 4.12 2.93 3.88 3.68 3.36 9.80 11.00 4.24 4.24 4.00 3.88 3.68 3.36…
-
Indoor Unit
size (kW) 8.00 Capacity Tables Outdoor temperature -3.70 (℃) -3.00 Indoor temperature (℃ DB) 6.64 6.64 6.64 6.64 6.64 6.64 -0.70 0.00 7.12 7.12 7.12 7.12 7.12 6.72 2.20 3.00 7.52 7.52 7.52 7.52 7.36 6.72 4.10 5.00 7.76 7.76 7.76 7.76 7.36 6.72 6.00 7.00 8.00 8.00 8.00 7.76 7.36 6.72 7.90 9.00 8.24…
-
Electric Characteristics
-
Sound Levels
-
11. Exploded View
-
Part name
1 Exploded View Quantity No. Left sealed board ass'y 1 14 Temp. sensor 1 2 Volute shell 2 15 EEV solenoid 1 3 Filter bracket 1 16 Right seal board ass'y 1 4 Filter bracket 1 17 Evaporator connection board ass'y 1 5 Filter 1 18 Louver ass'y 1 6 Fan 2 19 Temp. sensor ass'y 1 7 Volute shell 2 20 Left…
-
224 Exposed & Concealed Floor-standing Type
-
No. Part name
Exploded View Quantity No. Part name Quantity 1 Filter bracket 1 15.3 Transformer 1 2 Volute shell 2 15.4 Wire joint, 2p 1 3 Filter 1 15.5 Wire joint 1 4 Left volute shell 2 16 E-Part box cover 1 5 Fan 2 17 Temp. sensor 1 6 Motor 1 18 EEV solenoid 1 7 Middle beam 1 19 Temp. sensor ass'y 1 8 Base 1…
-
226 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 3 17 E-Part box cover 1 2 Filter 1 18 Temp. sensor 1 3 Left volute shell 3 19 Baffle 1 4 Fan 3 20 Left cover seat ass'y 1 5 Coupling 1 21 Louver ass'y 4 6 Motor 1 22 EEV solenoid 1 7 Middle beam 1 23 Temp. sensor ass'y 1 8 Motor bracket 1…
-
228 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 3 16.5 Wire joint 1 2 Filter 1 17 E-Part box cover 1 3 Left volute shell 3 18 Temp. sensor 1 4 Fan 3 19 EEV solenoid 1 5 Coupling 1 20 Left cover seat ass'y 1 6 Motor 1 21 Temp. sensor ass'y 1 7 Middle beam 1 22 Louver ass'y 4 8 Motor…
-
230 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Filter bracket 1 14 Supporting board ass'y 1 2 Filter bracket 1 15 Temp. sensor 1 3 Right supporting shelf 1 16 Right seal board ass'y 1 4 Left supporting shelf 1 17 Evaporator connection board ass'y 1 5 Filter 1 18 Baffle 1 6 Fan 2 19 EEV solenoid 1 7…
-
232 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 2 14 E-Part box cover 1 2 Filter 1 15 Temp. sensor 1 3 Left volute shell 2 16 Right supporting shelf 1 4 Fan 2 17 Left supporting shelf 1 5 Motor 1 18 Left cover seat ass'y 1 6 Middle beam 1 19 Louver ass'y 3 7 Base 1 20 Right cover seat…
-
234 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 3 17 Right supporting shelf 1 2 Filter 1 18 Left supporting shelf 1 3 Left volute shell 3 19 Baffle 1 4 Fan 3 20 Left cover seat ass'y 1 5 Coupling 1 21 Temp. sensor 1 6 Motor 1 22 Louver ass'y 4 7 Middle beam 1 23 EEV solenoid 1 8 Motor…
-
236 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 3 17 E-Part box cover 1 2 Filter 1 18 Right supporting shelf 1 3 Left volute shell 3 19 Left supporting shelf 1 4 Fan 3 20 EEV solenoid 1 5 Coupling 1 21 Left cover seat ass'y 1 6 Motor 1 22 Temp. sensor 1 7 Middle beam 1 23 Louver ass'y 4…
-
238 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 2 11.3 Temp. sensor ass'y 1 2 Filter bracket 1 12 Supporting board ass'y 1 3 Filter bracket 1 13 Temp. sensor 1 4 Filter 1 14 Right seal board ass'y 1 5 Fan 2 15 Evaporator connection board ass'y 1 6 Volute shell 2 16 EEV solenoid 1 7…
-
240 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 2 11.5 Wire joint 1 2 Filter 1 12 E-Part box cover 1 3 Left volute shell 2 13 Covering plate 1 4 Fan 2 14 Temp. sensor 1 5 Motor 1 15 EEV solenoid 1 6 Middle beam 1 16 Temp. sensor ass'y 1 7 Base 1 17 Covering plate 1 8 Motor bracket 1 18…
-
242 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 3 14 E-Part box cover 1 2 Filter 1 15 Baffle 1 3 Left volute shell 3 16 EEV solenoid 1 4 Fan 3 17 Temp. sensor ass'y 1 5 Coupling 1 18 Covering plate 1 6 Motor 1 19 Covering plate 1 7 Middle beam 1 20 Supporting board ass'y 1 8 Motor…
-
244 Exposed & Concealed Floor-standing Type
-
Part name
Exploded View Quantity No. Part name Quantity 1 Volute shell 3 15.4 Wire joint, 2p 1 2 Filter 1 15.5 Wire joint 1 3 Left volute shell 3 16 E-Part box cover 1 4 Fan 3 17 Covering plate 1 5 Coupling 1 18 Covering plate 1 6 Motor 1 19 Supporting board ass'y 1 7 Middle beam 1 20 Evaporator connection…
-
Accessories
MHVAC-DTSM-2010-03 12. Accessories Name of Accessories 246 Quantity Outline Usage Owner's manual 1 / / Installation manual 1 / / Pipe insulation material 2 Heat insulation Signal receiver display board 1 Receive Signal Mounting screw (ST3.9x12-C-H) 4 / Remote controller 1 Control the indoor unit…
-
Console Type
Exploded View 247
-
1.Brief Introduction about Controlling System................................... 249
2.Indoor Unit Central Control Monitor System 256 3.Control System 274 248 Control System
-
1. Brief Introduction about Controlling System
The control system adopts modular design, that is, all indoor units communicate with outdoor units, refer to the following figures for the control structure between indoor units and outdoor units. In the structure, the indoor control board receives the information from users (for exam. set temp.…
-
T1
Indoor ambient temp. T2 Indoor evaporator middle part temp. T2B Indoor evaporator outlet pipe temp. Ts Indoor setting temp. T3 Main outdoor heat-exchanger outlet pipe temp. (Cooling mode) T3’ No.1 auxiliary outdoor heat-exchanger outlet pipe temp. (Cooling mode) T3’’ No.2 auxiliary outdoor…
-
Indoor electric control (take T2 as example)
1—EXY (NET) — Net control socket X, Y, E of all air-conditioners are connected together in Bus to the X, Y, E of CCM. 2—CN15 (ENC2) — Number Setting port from outside It has same function as ENC2 ((NUM_S) — Number Setting (for outdoor), the difference is that it is suitable for some special indoor…
-
board will display address setting, continue to press for 5 seconds, the display board will display power setting. The setting is as follows: Buzzer Operation lamp Timer lamp Defrosting lamp Alarm lamp OFF OFF OFF Communication Address OFF Indoor HP 0.8HP ~ OFF OFF OFF ON 0 1 1.0HP OFF OFF ON OFF 2…
-
OFF
ON ON ON 39 3.2 HP ON OFF OFF OFF 40 4 HP ON OFF OFF ON 41 5 HP ON OFF ON OFF 42 ON OFF ON ON 43 ON ON OFF OFF 44 ON ON OFF ON 45 ON ON ON OFF 46 ON ON ON ON 47 OFF OFF OFF OFF 0.8 HP ~ OFF OFF OFF Flash 48 49 1.0 HP OFF OFF Flash OFF 50 1.2 HP OFF OFF Flash Flash 51 1.5 HP OFF Flash OFF OFF 52 2 HP…
-
5—ENC1 (POWER_S) — Power Setting
The range is 0~9. In normal case, the power setting of indoor units has been set well. The matching capacity of indoor units is as follows: Power setting Capacity of indoor units 0 0.8 (2200W) 1 1.0 (2800W) 2 1.2 (3600W) 3 1.7 (4500W) 4 2.0 (5600W) 5 2.5 (7100W) 6 3.0 (8000W) 7 3.2 (9000W) 8 4.0…
-
12V AC output. Input 220V AC to transformer, then output 12V AC, and then input to the electric board. There are two commute filter circuits, one is 7805, output 5V to the chip, the other one is 7812, output 12V to 2003 and relays. 18—CN5—Water-level switch (WATER) Disconnect when full of water and…
-
2. Indoor Unit Central Control Monitor System
2.1 CCM03 Indoor CCM, max. 64 indoor units control. Single or all units query and control, such as ON/OFF/Mode setting/Temp. setting/Fan setting/Mode lock function, Blue background light, LCD display screen. 2.1.1 Basic conditions o f operating the electric controller: (1) Applicable range of supply…
-
Schematic diagram of network control system composition of air conditioner
Keywords and general function description 1. Power on or reset When the centralized controller is powered on or reset, all display segments of the LCD are luminous for 2 seconds and then goes off. 1 second later, the system enters the normal display status. The centralized controller is in the main…
-
the compulsory startup switch of the centralized controller is turned on, all air conditioners in the network of the centralized controller will start up compulsorily. By default, they will run in the cooling mode. The startup and shutdown operations of the centralized controller and the computer…
-
1) Query key
Any time when you press the key, the selected operation mode is to query the operation status of the air conditioner. By default, the first in-service air conditioner will be queried. Through the Increase and Decrease keys, you can change the parameter page to be queried; through the Up, Down, Left…
-
query mode. By default, it is the first in-service air conditioner
11) Upward key In the query mode, every time when you press the key, the operation status data of the air conditioner corresponding to the previous row of the matrix will be displayed. If it is currently in the first row, press the key, and the data of the air conditioner corresponding to the last…
-
concurrently, and the keys will be locked. If the keys are locked, pressing of any key other than the Unlock key will be ineffective. In the unified setting page, press the Up key and the Lock key concurrently to lock all air conditioner modules in the network. The mode locking is cancelled when the…
-
6. Liquid crystal matrix display description
262 MHVAC-DTSM-2010-03 Control System
-
1. The liquid crystal matrix is composed of 4*64 grids, and each grid is composed of two blocks of different sizes (as shown in the above figure). 2. The matrix includes horizontal coordinates 00-15 on the upper side and vertical coordinates 00+, 16+, 32+ and 48+ on the left side, which indicate the…
-
2. Description of the query page
MHVAC-DTSM-2010-03 1) The LCD displays the query page, and the air conditioner with the address of 08 is being queried. Mode of the air conditioner with the address 01 is: Cooling, strong air, swing on, indoor temperature 22°C, set temperature 20°C, cooling mode “lock”. 2) In the matrix, only the…
-
1) Query the air conditioner with the address of 08 in the query page. The air conditioner with the address of 08 is faulty, and the fault code is 08. The big black dot below (08, 0+) blinks. 2) In the matrix, only the big and small black dots from (00, 00+) to (16, 15+) illuminate. It indicates the…
-
Dimension
266 MHVAC-DTSM-2010-03 Control System
-
CCM09
Designed base on the CCM03, max. 64 indoor units control, weekly schedule timer function. Note: It can’t be connected to the network control system. Dimension: Control System 267
-
Installation Method
Connecting diagram of network-based air conditioning system (There are two types of indoor units, namely indoor unit with external network interface module on the main control board or built-in network interface module in the main control board.) General drawing of the liquid crystal display of the…
-
LCD icon description of the weekly-timer central controller
Indoor Unit Central Control Monitor System Key description of the weekly-timer central controller: General Key layout of the weekly-timer central controller: Control System 269
-
Key instructions of the weekly-timer central controller
Key Name MHVAC-DTSM-2010-03 Usage Press the ON/OFF button. All air conditioners will be shut down if they are running; on the contrary, they will be started up. If you press the button for less than 5 seconds, the startup mode is the last running mode of the air conditioner. If you press the button…
-
2-1 Query Button
Push it to enter into the query state. 2-2 Previous Button On the query state, push it to query in default the running states of other online air-conditioners. 2-3 Next Button On the query state, push it to query in default the running states of other online air-conditioners. 2-4 Page Up Button…
-
3) Data
MHVAC-DTSM-2010-03 3-1Common Display Data: 3-1-1 Figure means CCM is sending query order. 3-1-2 Figure communication. means CCM is in communication with PC, and it will be off in 20 seconds with no 3-1-3 Figure means CCM is in communication connection with outdoor unit, and it will be off in 20…
-
number
3-3-19 Page 9 displays the compressor current symbol 1 with “CURRENT A”, “1” and the number. 3-3-20 Page 10 displays the compressor current symbol 2 with “CURRENT A”, “2” and the number. 3-3-21 Page 11 displays the compressor current symbol 3 with “CURRENT A”, “3” and the number. 3-3-22 Page 12…
-
3. Control System
3.1 Remote Controller 3.1.1 R05 AUTO C O OL Mode setting 1 TE MP SET DRY H E AT 2 SET Fanspeedsetting F AN Adjust 3 4 Adjust 6 Airdirecti onsetting 9 Time setting 10 Time ON 11 Time OFF 14 Confirmbutton 16 Economic operation FAN S P EED MODE M ON/OFF 5 Horiz swing 7 Vert. swing 8 Reset 12 Lock 13 Co…
-
3.1.2 R51
TEMP down button TEMP up button MODE select button FAN SPEED button SWING button Control System Control System TIMER button VENT button CANCEL button ON/OFF button ECONOMIC RUNNING button RESET button LOCK button 275
-
3.2 Wired controller
-
3.2.2KJR-01B
1) Outlook Control System General constant wire controller is available for cooling & heating type as default Its function of Mid-speed Fan can be adjusted by the dial switch (Sw1) in the main panel of wire controller, which is shown as follows: 1 ON 2 ON 1 ON 2 OFF 1 OFF 2 ON 1 OFF 2 OFF Mid-speed…
-
2) Installation
2-1 Installation into the wall The diameter of Wire Controller wire must be suitable for its length. Wiring Tube must be suitable for the wires. Remove a screw at the concave on bottom panel of the Wire Controller to dismantle the Cover. 2-2 Installation on the wall Cut a hole that can let a…
-
3.3 Weekly Timer (CCM04)
3.5.1 Outlook 3.5.2General Introduction 1) Summarize Using condition: 1-1 Power Supply: 5V DC. 1-2 Operation temperature: -15℃ - +43℃. 1-3Operation Humidity: 40% - 90%, RH. 2) Function Summary Main Function: 2-1 Connecting to indoor unit by +5V, E, X, Y, E terminal. 2-2 Button setting action mode.…
-
3.5.3 Operation
1) Meaning of Screen displayed MHVAC-DTSM-2010-03 10 Week 1 Operation mode Mon Tue Wed 9 Lock Fri Sat Lock Temporary Set to Period Mode Fan o Heat High Cool Middle Error: Off Low Weekly Timer Off Auto Sun Fan speed 2 Thu Error 3 Month 8 Period 7 Time 6 Date Day 4 Temperature Year 5 Timer on/off 1-1…
-
2-4 Day button: Press this button and ADD or REDUCE button to select data, Press Confirm to save and
back. 2-5 Timer on/off button: Press this button, can turn off the weekly timer function. 2-6 Reset button: When press this button, All of the display part of LCD will be light last 2 second when weekly timer has been electrified or reset. Following the lamp will be closed and last 1 second. So the…