Selection Procedure
(Based on Cooling Load) 1. Introduction 248 2. Unit selection (Based on cooling load) 249 Selection Procedure (Based on Cooling Load) 247
-
1. Introduction
5 basic modules, which can be freely assembled. 2HP increments of capacity range, which meets customer’s needs accurately. Maximum capacity is 64HP, the maximum capacity in air-conditioner refrigeration industry. Note: when in project designing, it should never reach all the operating limit of the…
-
2. Unit selection (Based on cooling load)
2.1 Indoor unit selection 2.1.1 After calculated the heat load of rooms, please select the nearest load capacity of indoor units with given load according to the local weather parameter, area, cubage and structure of rooms. 2.1.1 Selecting the proper indoor units including the type of indoor units…
-
2.4.1.2 modification coefficient of outdoor D.B. temperature Capacity compensation value 1.2 1.1 1.0 0.9 0.8 15 Indoor W.B. Temp.( C) Outdoor D.B. Temp.( C) 2.4.1.3 Modification coefficient of the length and high difference of refrigerant pipe: H (m) % - 10 - 20 - 30 - L (m) L: Refrigerant pipe…
-
2.4.2.3 Modification coefficient of the length and high difference of refrigerant pipe
H (m) % 10 - 10 - 20 - 30 - L(m) L: Refrigerant pipe equivalent length H: Height difference between outdoor and indoor 2.4.2.4 Modification coefficient of indoor air-volume changing rate: Cacompensation value 1.1 1.0 0.9 Air-volume change rate( %) 2.5 Example for unit selection with cooling load…
-
zFor the 92% combination, calculate the cooling capacity of outdoor unit
(MDVi-280(10)W/ DSN1). 26.73kW ←90 % (Indoor temperature: WB 20°C, Outdoor temperature: DB 35°C) 28.30kW ←100 %( Indoor temperature: WB 20°C, Outdoor temperature: DB 35°C) Then calculated the outdoor capacity in 92% combination index: Therefore: 26.73 + {(28.30 –26.73)/ 10} ×2= 27.04; zOutdoor unit…
-
Specifications
MCAC-VTSM-2008-09 1. Specifications Model Power supply Cooling V-Ph-Hz MDVi-252(8)W/DSN1 MDVi-280(10)W/DSN1 MDVi-335(12)W/DSN1 380-50-3 380-50-3 380-50-3 Capacity kW 25.2 28 33.5 Input kW 6.07 7.73 9.88 Rated current A 10.3 13.1 16.7 Capacity kW 27 31.5 37.5 Input kW 6.21 7.72 9.1 A 10.5 13 15.3…
-
Specifications
Model Power supply V-Ph-Hz Cooling MDVi-450(16)W/DSN1 380-50-3 380-50-3 Capacity kW 40 45 Input kW 12.26 14.05 23.7 Rated current Heating MDVi-400(14)W/DSN1 A 20.7 Capacity kW 45 50 Input kW 11.18 12.6 A 18.9 21.3 Max. input consumption Rated current W 20700 20700 Max. current A Compressor quantity…
-
Dimensions
MCAC-VTSM-2008-09 2. Dimensions 2.1 MDVi-252(8)W/DSN1 MDVi-280(10)W/DSN1 (Unit: mm) 256 Selection Procedure (Based on Cooling Load)
-
2.2 MDiV-335(12)W/DSN1
Dimensions MDVi-400( 14)W/DSN1 MDVi-450(16)W/DSN1 (Unit: mm) Selection Procedure (Based on Cooling Load) 257
-
3. Service Space
3.1 Power supply equipment is preferred to be installed by the side of the outdoor unit; 3.2 Ensure there is sufficient space for the maintenance of the outdoor unit. The modules in the same system must be on the same height. 3.3 Proper space between outdoor units should be kept; 3.4 Distance…
-
3.5 Outdoor unit arrangement
Outdoor units are higher than the surrounding buildings Outdoor units are aligned in one line Outdoor units are aligned in two lines Selection Procedure (Based on Cooling Load) 259
-
More than 2 lines of outdoor units
3.6 Outdoor units are lower than the surrounding obstacles If the outdoor units are lower than the surrounding obstacles, in order to ensure an effective “heat exchange “a conduit is strongly recommended to help the heat emission and avoid the discharging air being absorbed into the system again.…
-
3.7 When there are obstacles above the outdoor unit
Note: If miscellaneous articles are piled around the outdoor unit, such articles must be 800mm below the top of the outdoor unit. Otherwise, a mechanic exhaust device must be added. Selection Procedure (Based on Cooling Load) 261
-
Piping Diagram
MCAC-VTSM-2008-09 4. Piping Diagram Take MDVi-400(14) W/DSN1 for example: SV3 SV6 ST2 SV1 Ф 15.9 EXV EXV Ф 31.8 ST1 SV5 Ф 6.4 5 SV2 Ф 19.1 SV4 4 Remark: 1: DC Inverter compressor 2/3: Fixed compressor 4: Gas-liquid separator 5: Oil separator Note: Model MDVi-252(8)W/DSN1 MDVi-280(10)W/DSN1…
-
Piping Diagram
8) SV4: oil returning valve. Opens when the unit is running for every 20 minutes and last 3 minutes 9) SV5: for defrost. In defrosting mode, the opening of SV5 can cut the refrigerant flowing circle, so the defrosting process will takes less time. 10) SV6: for by-pass. Closes when the unit stands by…
-
Wiring Diagram
MCAC-VTSM-2008-09 5. Wiring Diagram MDVi-252(8)W/DSN1 264 MDVi-280(10)W/DSN1 MDV-335(12)W/DSN1 MDVi-400(14)W/DSN1 MDVi-450(16)W/DSN1 Selection Procedure (Based on Cooling Load)
-
6. Field Wiring
6.1 Connection of control wire (taking multi-connected unit for example) Note: 1. The signal connecting line between outdoor units, indoor and outdoor units and indoor units has polarity. When connecting, be careful to prevent error connection. 2 2. Signal line shall adopt three-core shielded wire…
-
6.2 Control Wiring Connection Method
1) Correct connection 2) Typical wrong connection a. Annular connection of signal line b. Star connection of signal line ● Star connection of part signal line 266 Selection Procedure (Based on Cooling Load)
-
● Star connection of all signal line
c. Reverse connection of signal line ● Outdoor unit — indoor unit ●Indoor unit — indoor unit Caution: shielded layer shall be connected to electrical panel. Selection Procedure (Based on Cooling Load) 267
-
6.2.2 Specification of Control Wiring
Normal shield wires are as following: Model Item AVP Copper core PVC insulated shield wire AVP-105 Heat-resistant 105℃ PVC insulated shield wire RVP PVC insulated shielded flexible wire RVP-105 Heat-resistant 105℃ PVC insulated shielded flexible wire RVVP Copper core PVC-insulated PVC-sheathed metal…
-
6.3 Wiring Diagram (Indoor/CCM)
-
7. Electric Characteristics
7.1 Brief Introduction 7.1.1 All wires, parts and material must conform to concerning national standards. 7.1.2 All wiring work must be done by qualified person. 7.1.3 Grounded well. 7.2 Power circuitry installation Outdoors power supply wiring 7.2.1 Single power supply (no power supply device) Item…
-
7.2.2 With power supply device
7.2.3 Select the wire diameter Power wiring refers to the main wire (a) connecting to branch box and the wiring (b) between branch box and power facilities. Please select the wire diameter according to the following requirement. 7.2.3.1 The dimension of the main power wiring (a). Calculate the total…
-
7.2.4 Selection the fuse and manual switch of wire branch box
Total capacity of outdoor units (HP) Manual switch (A) Fuse (A) Total capacity of outdoor units (HP) Manual switch (A) Fuse (A) 10~14 100 75 37~47 300 250 15~18 100 100 48~50 300 300 19~28 150 150 52~64 400 400 29~36 200 200 Indoor power supply wiring The dimension of indoor power supply wiring Item…
-
RV
Fluorin resinoid insulating connecting soft wire, copper-core RVB Fluorin resinoid insulating connecting wire, copper-core, flat-type RVS Fluorin resinoid insulating connecting wire, copper-core, twist-type RVV Fluorin resinoid insulating connecting soft wire, copper-core, round-type RVVB Fluorin…
-
8. Capacity Tables
-
MDVi-280(10)W/DSN1
-
MDVi-335(12)W/DSN1
-
MDVi-400(14)W/DSN1
-
MDVi-450(16)W/DSN1
-
8.3 Heating
-
MDVi-280(10)W/DSN1
-
MDVi-335(12)W/DSN1
-
MDVi-400(14)W/DSN1
-
MDVi-450(16)W/DSN1
-
Operation Limits
MCAC-VTSM-2008-09 9. Operation Limits Item Model All model Outdoor temperature Cooling mode Indoor temperature Room relative humidity Heating mode Outdoor Indoor temperature temperature -5℃~48℃ ≥17℃ Below 80% -15℃~27℃ Cooling ≤30℃ Heating Range for continuous operation 25 20 Range for intermittent…
-
Sound Levels
-
11. Exploded View
MDVi-252(8)W/DSN1 322 Outdoor Units
-
Part
Name Quantity No. Part Name Quantity 1 Axial flow fan 1 28.2 Strainer 1 2 Motor 1 29 Pipe joint subassembly 1 3 Motor bracket 2 29.1 Pipe joint 1 4 Outdoor temp sensor assembly 1 30 Oil balance valve ass'y 1 5 Condenser coil assembly 1 30.1 Low pressure valve 1 5.1 Input pipe ass'y 1 31 Gas balance…
-
Part
Name Quantity No. Part Name Quantity 15.15 Transformer 1 39.1 Solenoid valve 1 15.16 Relay 2 39.2 Solenoid valve winding 1 15.17 Main control board subassembly 1 40 Oil balance pipe ass'y 2 15.18 Inverter module 1 41 Base ass'y 1 15.19 Radiator 1 42 Front-right supporting board 1 15.20 Three phase…
-
MDVi-280(10)W/DSN1
Outdoor Units 325
-
Part
Name Quantity No. Part Name Quantity 1 Axial flow fan 1 28.2 Strainer 1 2 Motor 1 29 Pipe joint subassembly 1 3 Motor bracket 2 29.1 Pipe joint 1 4 Outdoor temp sensor assembly 1 30 Oil balance valve ass'y 1 5 Condenser coil assembly 1 30.1 Low pressure valve 1 5.1 Input pipe ass'y 1 31 Gas balance…
-
Part
Name Quantity No. Part Name Quantity 21 Inductance board 1 52 Rear net 1 22 Electrical inductance 1 53 Rear-left supporting board 1 23 Inductance Holder 1 54 Cover board 2 24 Duct 1 55 Rear-right supporting board 1 25 Front cover 1 56 Net 1 26 Handle 1 57 Installation board ass'y 1 27 Accumulator…
-
MDVi-335(12)W/DSN1
328 Outdoor Units
-
Part
Exploded View Name Quantity No. Part Name Quantity 1 Top cover 2 37 Electrical inductance 1 2 Axial flow fan 2 38 Inductance board 1 3 Covering plate 2 39 E-part box cover board 1 4 Rear clapboard ass'y 1 40 Inductance cover 1 5 Baffle ass'y 1 41 E-part box ass'y 1 6 Cover board 2 41.1 Inverter…
-
Part
Name Quantity No. Part Name Quantity 22 4-way valve ass'y 1 41.20 Radiator 1 22.1 4-way valve 2 42 Compressor supporter ass'y II 1 22.2 4-Ways valve solenoid 2 43 Compressor supporter ass'y III 1 22.3 Pressure controller 1 44 Compressor supporter ass'y I 2 23 Electronic expansion valve 1 45…
-
MDVi-400(14)W/DSN1
Outdoor Units 331
-
Part
Name Quantity No. Part Name Quantity 1 Top cover 2 37 Inductance Holder 1 2 Axial flow fan 2 38 Electrical inductance 1 3 Covering plate 2 39 Inductance board 1 4 Rear clapboard ass'y 1 40 Inductance cover 1 5 Fixing board ass'y 3 41 E-part box cover board 1 6 Baffle ass'y 1 42 Duct 1 7 Cover board…
-
Part
Exploded View Name Quantity No. Part Name Quantity 21 Oil balance pipe ass'y 3 43.14 Resistance 2 22 Accumulator connection pipe ass'y 1 43.15 Compressor capacitor 1 22.1 Solenoid valve 2 43.16 Aluminum electro analysis capacitor 2 22.2 Solenoid valve winding 2 43.17 Resistor 2 22.3 One way valve 1…
-
MDVi-450(16)W/DSN1
334 Outdoor Units
-
Part
Name Quantity No. Part Name Quantity 1 Top cover 2 37 Inductance Holder 1 2 Axial flow fan 2 38 Electrical inductance 1 3 Covering plate 2 39 Inductance board 1 4 Rear clapboard ass'y 1 40 Inductance cover 1 5 Fixing board ass'y 3 41 E-part box cover board 1 6 Baffle ass'y 1 42 Duct 1 7 Cover board…
-
Part
Name Quantity No. Part Name Quantity 22.1 Solenoid valve 2 43.16 Aluminum electro analysis capacitor 2 22.2 Solenoid valve winding 2 43.17 Resistor 2 22.3 One way valve 1 43.18 Three phase bridge 1 23 4-way valve ass'y 1 43.19 Single-phase bridge 1 23.1 4-way valve 2 43.20 Radiator 1 23.2 4-Ways…
-
12. Troubleshooting
12.1 Indoor Units lamp flashes: No Display Contents Explanation of Malfunction 1 All lamps are off Standing-by 2 Operation lamp is on ON 3 PRE./DEF. lamp is on Anti-cooling or Defrosting 4 Timer lamp is on Timer function is on 5 Timer lamp flashes Indoor/outdoor communication malfunction 6 Operation…
-
① Timer lamp flashes: Indoor/outdoor communication malfunction
Timer lamp flashes: Indoor/outdoor communication malfunction (the outdoor PCB plate will display E2 or there is no power supply for the outdoor unit) Short circuit or open circuit of communication wire P, Q and E Check communication wire (generally measuring resistance between P, Q and E) Exist OK…
-
Note
1. Press the “manual” button on remote control receiver of indoor unit in turn (display the address code of this indoor unit when pressing and holding for 5 seconds (display capacity code when pressing and holding for 10 seconds), check all address codes. Codes to be inspected are as follows…
-
② Operation lamp flashes: Indoors temp. Sensor abnormal
Operation lamp flashes T1, T2 or T2B Connecting wire between sensor and mainboard gets loose Exist Reconnect and ensure that the connection is reliable. OK Temperature sensor is short-circuited or punctured Exist Replace sensor OK Chip fault, or chip foot sheds off, or chip is inverted (correct mode…
-
③ DEF. Lamp flashes:Mode-confliction malfunction
In the below table, “Yes” indicates existing mode conflict, “No” indicates no mode conflict. Cooling Heating Air-supply OFF Cooling No Yes No No Heating Yes No Yes No Air-supply No Yes No No OFF No No No No When indoor unit receiving heating operation instruction, it will transmit the operation mode…
-
⑤ Alarm lamp flashes slowly: Outdoor malfunction or protection
Examine outdoor unit, and analyze according to actual condition ⑥ Congealing Dew or Water Leakage in Indoor Units Congealing dew or water leakage in indoor unit Check the source of water leakage, and generally it is from condensing water or congealing dew; congealing dew is generally accumulated at…
-
12.2 Outdoor unit’s LED indication
No 1 Display E0 2 Malfunction or Protection Remark Communication error between outdoor units Only slave unit display E1 Phase protection All the outdoor units display 3 E2 Communication error between indoor unit and master unit All the outdoor units display 4 E4 Outdoor temperature sensor error All…
-
E0: Communication error between outdoor units
E0: Communication error between 0utdoor units Check address code setting of outdoor units: Master Unit is set to 0, Slave Unit 1 is set to 1, Slave Unit 2 is set to 2, Slave Unit 3 is set to 3; an address of above 3 is invalid Error Reset address code of outdoor units OK Check the connection of…
-
E1: Phase-sequence Error
E1: phase-sequence error of outdoor units Check phase-sequence of three-phase power: keep it consistent with the phase-sequence required by the operation of compressor, and reversed connection shall lead to the rollback of compressor (for the program in the chip only check phase-sequence during…
-
E2: Communication Error between Outdoor Unit and Indoor Units; and indefinite variation in the
number of indoor unit detected by outdoor unit E2: communication error between outdoor unit and indoor units; and indefinite variation in the number of indoor units detected by outdoor unit Short circuit or open circuit of communication wire P, Q and E Check communication wire (generally measuring…
-
Indicator OPERATION Code TIMER 8 DEF / FAN ALARM Address code Capacity (x 100W) Horsepower (HP) 0.8 1.0 1.2 1.6 2.0 2.5 3.0 3.2 4.0 5.0 For example: After pressing and holding for 5 seconds, "Operation" light and "Alarm" light is constant-on, which indicates that the address code is ( 8 + 1 ) = 9…
-
E4: Outdoor temperature sensor error
E4: Outdoor temperature sensor error T4 Connecting wire between sensor and mainboard gets loose Exist Reconnect and ensure that the connection is reliable. OK Temperature sensor is short-circuited or punctured Exist Replace sensor OK Chip fault, or chip foot sheds off, or chip is inverted (correct…
-
E9: Voltage error
E9: Voltage error Voltage of power is over-high or over-low Exist Provide with power supply stable OK Check heavy-current line: such as short circuit of compressor or fan, output error of frequency-conversion module etc Exist Replace frequency-conversion module or repair related parts OK Chip fault…
-
H2: Fault of Reduction in the Number of Outdoor Units
H2: Fault of reduction in the number of outdoor units During operation, communication wire between outdoor units gets loose (H1, H2, and E) Exist Reconnect and ensure that connection is reliable OK Some outdoor unit is power-down when in modules combination Exist Comes back to normal after being…
-
P0, P4: Temperature Protection for Top of Compressor or Discharge Temperature Protection (P0
refers to inverter compressor protection) P0, P4: Top of compressor or discharge temperature protection Supplemented refrigerant is too little or refrigerant in system is leaked Exist Supplement refrigerant or repair leakage OK Operation of low-pressure side heat exchanger is abnormal (such as heat…
-
Case
For V4 system, most feedback from market is that P4 protection is very usual, and its ultimate reason lies in lack of gas suction of compressor or no gas suction. To sum up, there are the following four reasons: 1) System is short of refrigerant. Symptom: Top temperature of all compressors and…
-
P1: High-pressure Protection
P1:High-pressure protection (R410a refrigerant is protected above 4.4MPa, and restores under 3.2MPa.) Heat dispersion function of outdoor heat exchanger is unqualified: For example, the heat exchanger is dirty, air outlet and air-back line is short-circuited, outdoor fan stops operating or air speed…
-
P2: Low-pressure Protection
P2:Low-pressure protection (R410a refrigerant is protected under 0.05MPa, and restored above 0.15MPa (another one is protected under0.14MPa, and restored above 0.3MPa). Supplemented refrigerant is insufficiency or refrigerant in system is leaked out Exist Supplement refrigerant or repair leakage OK…
-
P3, P7, P8: Current protection of each compressor (protection happens when current of single compressor is higher than 16A) Loading of system is over-large, such as high-temperature cooling or too many indoor units, which shall lead to over-high evaporating temperature Exist Regulate loading or…
-
P5: High-temperature Protection of Pipe Temperature
P5: High-temperature Protection of Pipe Temperature (temperature protection of condenser outlet) Exist Fault of thermo-sensor, connecting wire or terminals of connecting wire Replace thermo-sensor or connecting wire OK Loading of system is over-large, such as high-temperature OK cooling or too many…
-
P6: Inverter module protection
P6: Module protection Heat dispersion function of module is unqualified or over-high ambient temperature leads to over-high temperature of inner cavity of electric control Exist Ensure that module is working within normal temperature scope OK Over-large current causes module protection, for…
-
Accessories
MCAC-VTSM-2008-09 13. Accessories No Name 1 Installation manual of outdoor unit 1 / 2 Operation manual of outdoor unit 1 (Be sure to deliver it to the customer) 3 Operation manual of indoor unit 2+2 (Be sure to deliver it to the customer) 4 User service guide (containing a warranty card and a bar…