Инструкция на VRF-системы V4 (сервис мануалы)
Наружные блоки (380) серии MDVi-V105W/SN1, MDVi-V140W/SN1, MDVi-V160W/SN1. Сервис мануал.
Смотрите также: Коды ошибок CCM03 →
Загружаем документ…
Текст инструкции
-
Specification
-
Dimensions
-
Service Space
MCAC-HTSM-2008-04 3. Service Space 220 Outdoor Units
-
Piping Diagrams
4. Piping Diagrams MDVi -V105W/SN1 MDVi -V140W/SN1 MDVi -V160W/SN1 Electronic expansion valve High pressure switch Evaporator Electronic expansion valve Compressor Oil separator Oil return Capillary Low pressure switch Outdoor Units Condenser High pressure liquid accumulator can Low pressure liquid…
-
Wiring Diagrams
MCAC-HTSM-2008-04 5. Wiring Diagrams 5.1 MDVi -V105W/SN1 222 Outdoor Units
-
Outdoor Units Wiring Diagrams MDVi -V160W/SN1 223
-
Field Wiring
MCAC-HTSM-2008-04 6. Field Wiring For 36000-60000Btu/h 224 Outdoor Units
-
7. Capacity Tables
-
Heating
-
таблицы и схемы — в просмотре
-
Heating
-
Electric Characteristics
MCAC-HTSM-2008-04 8. Electric Characteristics Model MDVi -V105W/SN1 MDVi -V140W/SN1 MDVi -V160W/SN1 Hz Outdoor Unit Voltage Min. 380-415V 342V 380-415V 342V 380-415V 342V Max. 440V 440V 440V Power Supply TOCA MFA 20 25A 20 25A 20 25A Compressor RLA 9.62 9.62 9.62 kW 0.2 0.1 0.1 OFM FLA 1.4 0.751 x 2…
-
Sound Levels
-
Exploded View
MCAC-HTSM-2008-04 10. Exploded View MDVi -V105W/SN1 250 Outdoor Units
-
No
Part 1 Quantity No. Part Top cover ass'y 1 13 Front right clapboard ass'y 1 2 E-part box ass'y 1 14 Sponge 1 2.1 E-part box 1 15 Sponge 1 2.2 Contactor 1 16 Compressor electric heater 1 2.3 Compressor capacitor 1 17 Compressor 1 2.4 Inverter module 1 18 High Pressure Valve Ass'y 1 2.5 Main control…
-
Exploded View
-
No
Part Quantity No. Part 1 Top cover ass'y 1 19.4 Strainer Base 1 20 Accumulator cylinder 1 Axial flow fan 2 21 Accumulator cylinder 1 4 Rear clapboard ass'y 1 22 Motor bracket ass'y 1 5 Condenser ass'y 1 23 Motor 2 5.1 Condenser 1 24 Rear net 1 5.2 Capillary ass'y 1 25 Rear support board 1 5.3 Input…
-
Operation Limits
MCAC-HTSM-2008-04 11. Operation Limits Cooling Heating 48 30 Ambient Temp.(° C) Ambient Temp.(° C) 21 6 -15 -15 Remote Controller Temp.(° C) Remote Controller Temp.(° C) Outdoor Units
-
12. Troubleshooting
12.1 Troubles and causes of air conditioner If one of the following malfunctions occur, stop operation, shut off the power, and contact with your dealer. ■ The operation lamp is flashing rapidly (twice every second) This lamp is still flashing rapidly after turn off the power and turn on again. ■…
-
12.2 Troubles and causes of remote controller
Before asking for serving or repairing, check the following points. Symptoms Causes Solution Check whether the MODE When the automatic mode is selected, the indicated on the display is air conditioner will automatically change "AUTO" the fan speed. Check whether the MODE When dry operation is…
-
1. E0 malfunction
LED indicates E0 EEPROM malfunction No Judge 1: Check whether the EEPROM() is inserted well Insert the EEPROM well Yes Replace the outdoor main board Outdoor Units 257
-
2. E2 malfunction
LED indicates E2 Communication malfunction between indoor/outdoor units No Judge 1: Check whether the indoor unit power is on Turn on the indoor unit power Yes Judge 2: Check whether the signal wiring is shield cable or whether the shield cable is grounded No Adopt the shield cable/ shield cable…
-
3. E3 malfunction
LED indicates E3 Communication malfunction in outdoor PCB Check whether the indicator lights LED1 or LED2 on the main control board are flashing Yes Replace PCB No Yes Install the IC-U3 chip of the PCB over again, check whether the system can run normally Trouble is solved No Yes Check whether the…
-
4. E4 malfunction
LED indicates E4 Judge 1: Outdoor condenser’s middle temp. sensor (T3) is malfunction Check whether the wiring of the condenser’s middle temp. sensor is break off Yes Connect the wiring well No Check whether the resistance of condenser’s middle temp. sensor is wrong refer to the Annex 1 Yes Replace…
-
5. E5 malfunction
LED indicates E5 Outdoor unit voltage protection Check the voltage of outdoor unit power supply, whether the voltage between L1 and N is about 172--265V No Check the power supply Yes Replace the filter board, then check whether the system can run normally Yes Trouble is solved No Replace outdoor…
-
6. P1 malfunction
LED indicates P1 High pressure protection No Judge 1: Whether the wiring between the high pressure switch and main control board is connected well or correctly Connect it well Yes Judge 2: Whether the high pressure switch is broken Yes Validate: Short connect the high pressure switch socket, check…
-
7. P2 malfunction
LED indicates P2 Low pressure protection No Judge 1: The wiring between the low pressure switch and main control board is connected well or correctly Connect it well Yes Judge 2: Whether the low pressure switch is broken Validate: Short connect the low pressure switch socket, check whether the…
-
8. P3 malfunction
LED indicates P3 Outdoor unit current protection No Judge 1: Check whether the input current of the power supply wire is more than 15A Replace the filter board, then check whether the system can run normally Yes No Yes Trouble is solved Replace outdoor PCB Check whether the refrigerant system is ok…
-
9. P4 malfunction
When compressor discharge temperature is more than 115°C, the unit will stop, and unit runs again when compressor discharge temperature is less than 90°C. LED indicates P4 Compressor discharge temperature protection Yes Check whether the compressor discharge temp. more than 115°C ? No Check whether…
-
10. P5 malfunction
When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C. LED indicates P5 Condenser high temperature protection Yes Check whether the condenser temperature is more than 65°C No Check whether the resistance of condenser temp. sensor…
-
11. P6 malfunction
LED indicates P6 IPM protection No Check whether the voltage range of P-N on IPM module is normal? DC 350-650V No Check whether the input power supply is correct? 380-415V, 3N, 50Hz Yes Regulate it to correct, then check whether the system can work normally? Yes No Check whether the connecting line…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.