Trouble-shooting for MDV Indoor Units
I. Connection between indoor and outdoor units in MDV system Integrated power supply Three-core shielding wire, connection in series Supply integrated power to indoor units
-
T1: Indoor side ambient temp. sensor, is used to judge the setting temperature and decide the opening degree of EXV as well as the output capacity (every indoor unit has a T1 temperature sensor). Indoor unit EXV liquid pipe T2 T2B T2: Sensor of evaporator’s middle T1 Muffle and filter temperature…
-
Electronic expansion valve is characterized by wide regulative scope, precision in
regulation, and being nimble, stable and reliable. Refrigerant could flow through the electronic expansion valve in positive and opposite directions, which avoids the weakness caused by only one direction in thermostatic expansion valve and dramatically simplifies refrigerant system when applied to…
-
component and the flow of refrigerant; as for outdoor unit, EXV will shut down
completely and open to certain opening after few minutes later after the system is powered on, which also could be feel with hands), and at the same time, beat the body by using of hard object, so as to utilize the impulsive force of refrigerant to thrust obstruction aside. If this method does not…
-
Electronic
expansion valve view
-
III. Address code and capacity code setting
The present address setting has been put outside the electric control board for convenient setting, and the range is 0-F. Before indoor units are power on, the address setting must be finished and the address setting of indoor units that match with the same outdoor unit can’t be repeated, or it may…
-
OFF
Flash OFF Flash 21 OFF Flash Flash OFF 22 OFF Flash Flash Flash 23 Flash OFF OFF OFF 24 Flash OFF OFF Flash 25 Flash OFF Flash OFF 26 Flash OFF Flash Flash 27 Flash Flash OFF OFF 28 Flash Flash OFF Flash 29 Flash Flash Flash OFF 30 Flash Flash Flash Flash 31 Address Set Address Code 00 ~ 15 ~ 16 ~…
-
IV. Trouble-shooting for fault diagnosis
Indoor LED Malfunction Code Display Contents Explanation of Malfunction All lamps are off Standing-by Operation lamp is on ON PRE./DEF. lamp is on Anti-cooling or Defrosting Timer lamp is on Timer function is on Timer lamp flashes Indoor/outdoor communication malfunction Operation lamp flashes…
-
① Timer lamp flashes: Indoor/outdoor communication malfunction
Timer lamp flashes: Indoor/outdoor communication malfunction (the outdoor PCB plate will display E2 or there is no power supply for the outdoor unit ) Short circuit or open circuit of communication wire P, Q and E Check communication wire (generally measuring resistance between P, Q and E) Exist OK…
-
Note
1. Press the “manual” button on remote control receiver of indoor unit in turn (display the address code of this indoor unit when pressing and holding for 5 seconds (display capacity code when pressing and holding for 10 seconds), check all address codes. Codes to be inspected are as follows…
-
② Operation lamp flashes: Indoors temp. Sensor abnormal
Operation lamp flashes T1, T2 or T2B Connecting wire between sensor and mainboard gets loose Exist Reconnect and ensure that the connection is reliable. OK Temperature sensor is short-circuited or punctured Exist Replace sensor OK Chip fault, or chip foot sheds off, or chip is inverted (correct mode…
-
DEF. Lamp flashes:Mode-confliction malfunction In the below table, “Yes” indicates existing mode conflict, “No” indicates no mode conflict. Cooling Heating Air-supply OFF Cooling No Yes No No Heating Yes No Yes No Air-supply No Yes No No OFF No No No No When indoor unit receiving heating operation…
-
⑤ Alarm lamp flashes slowly: Outdoor malfunction or protection
Examine outdoor unit, and analyze according to actual condition ⑥ Congealing Dew or Water Leakage in Indoor Units Congealing dew or water leakage in indoor unit Check the source of water leakage, and generally it is from condensing water or congealing dew; congealing dew is generally accumulated at…
-
⑦ LED and LCD display on the new panel of 4-way cassette
No. Error or Protection OPERATION TIMER DEF/FAN ALARM 1 Room temperature sensor checking channel is abnormal X ☆ X X Yes E2 2 Evaporator temperature sensor checking channel is abnormal ☆ X X X Yes E3 3 Condenser temperature sensor checking channel is abnormal X X ☆ X Yes E4 4 Pump sensor malfunction…