Системы управления MDV. Сервис мануал.
Загружаем документ…
Текст инструкции
-
1. Wireless remote controller
Controller Appearance Model Description General functions with backlight, follow me, setting RM02A/BGE-A address ,keyboard locking function, 26℃ button and auto-mode (Normal). General functions with backlight, follow me, setting RM02A/BGE (T)-A addresse, keyboard locking function, 26℃ button and…
-
Remote controller specifications Model RM02A/BGE-A; RM02A/BGE (T)-A Rated Voltage 3.0V Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it gets 11m) -5°C~60°C Environment Temperature Range Performance Features 1. Operating Mode: COOL, HEAT, DRY, FAN and AUTO.…
-
(1) ON/OFF
For turning on or turning off the air conditioner. (2) 26℃ Button Press this button can operate the cool mode with the setting temperature 26℃. Considering about the comfort and energy saving, 26℃ is the best setting temperature. (3) Mode Select Once pressing, running mode will be selected in the…
-
(11)DRY·AUXILIARY HEAT/FOLLOW ME
When it is operating the dry cleaning function ,press the left of the button, will turn off the dry cleaning function; when it is operating follow me function ,press the right of the button, will turn off the follow me function.(Only available when remote controller is used with corresponding unit.)…
-
Setting addresses
For the V4 plus system, the RM02A can set the indoor units’ addresses. This function help the user assign the address to the indoor units freely. V4 series do not have this function. Press the Fan Speed button and ECO button simultaneously for more than 5 seconds, then the controller gets into…
-
Example
ΔT is 1°C, Ts is 25°C: when Tf-Ts>=+ΔT, it will operate COOL mode, the fan speed will be operated according to the setting fan speed. When Tf-Ts<=-ΔT, it will operate HEAT mode, the fan speed will be operated according to the setting fan speed. Notes: This function operation can be only available…
-
(1) Mode Button
Once pressing, running mode will be selected in the following sequence: AUTO → COOL → DRY → HEAT → FAN Notes: No heating mode for cool only type unit. (2) FanSpeed Fan speed will be selected in following sequence once pressing this button: AUTO → LOW → MED → HIGH (3) Adjust button ▼ Decrease the set…
-
(14)OK button
Used to confirm the time setting and modification. (15)COOL/HEAT (inner located) Press this button with a needle of 1mm to shift mode between COOL only and COOL&HEAT. During setting, backlight will be lightened. Factory default mode is COOL &HEAT. (16)ECO Button Activate or turn off economic…
-
1.3 R51/E (standard)
Remote controller specifications Model R51/E, R51C/BGE,R51D/E,R51I4/BGE Rated Voltage 3.0V Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it gets 11m) Environment Temperature Range -5°C~60°C Performance Features 1. Operating Mode: COOL, HEAT, DRY, FAN and…
-
(1) TEMP DOWN Button
Press the TEMP DOWN button to decrease the indoor temperature setting or to adjust the timer in a counter-clockwise direction. (2) Mode Select Button Each time you press this button, a mode is selected in a sequence that goes from AUTO, COOL, DRY, HEAT and FAN as the following figure indicates…
-
1.3.2 LCD display
AUTO COOL FAN HIGH DRY HEAT MED LOW 3 4 ①Transmitting display: This indicator lights when remote controller transmits signals to indoor unit. ②Mode display: Show the current operation modes-- AUTO, COOL, DRY and HEAT. HEAT is only available for heat pump model. ③Lock display: To displayed by…
-
2) Automatic Operation
When the Air Conditioner is ready for use, switch on the power and the OPERATION indicator lamp on the display panel of the indoor unit starts flashing. ※ Use the MODE select button to select AUTO. In the multi system, to avoid mode conflict; auto-mode is taken as cool mode. ※ Press the TEMP button…
-
After setting the TIMER there will be a one-half second delay before the remote controller transmits the signal to the Air Conditioner. Then, after approximately another 2 seconds, the set temperature will re-appear on the digital display. b. To set the STOPPING time. ※ Press the CANCEL button to…
-
Remote controller specifications Model R06/BGE, R06/BGCE Rated Voltage 3.0V Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it gets 11m) Environment Temperature Range -5°C~60°C Performance Features 1. Operating Mode: AUTO, COOL, HEAT, DRY, and FAN. 2. Timer…
-
(3)Swing Button
Press the button, the louver would swing up and down automatically. Press it again to stop. (4)Direction Button Press this button to change the swing angle of the louver. The swing angle of the louver is 6°for each press. When the louver swing at a certain angle which would affect the cooling and…
-
1.4.2 LCD display indications
(1)Transmission Indicator This transmission indicator light when remote controller transmits signals to the indoor unit. (2)Mode display Can display the current operational mode, including AUTO, COOL, DRY, HEAT (not applicable to cooling only models), FAN ONLY and back to AUTO. (3)ON/OFF display Can…
-
1.5 R71A/E
Remote controller specifications: General functions, button quantities reduce, but functions increase. 1. Operating Mode: COOL HEAT DRY FAN only and AUTO. 2. Timer Setting Function in 24 hours. 3. Indoor Setting Temperature Range: 17℃~30℃. 4. LCD (Liquid Crystal Display) of functions. 1.5.1 Parts…
-
(6) Sleep/Turbo Button
When you press the button, the operation mode is selected in a sequence as the following figure indicates. But this function cannot be used in DRY and FAN-only mode. SLEEP SLEEP OF F T URBO T URBO OF F (7) Swing Button Press the SWING button to activate the swing function, press it again to stop.…
-
2. Wired controller
2.1 KJR-10B/DP (T)-E KJR-10B/DP (T)-E Model Description General control function and without backlight. With the Air filter cleaning remind KJR-10B/DP(T)-E function, setting address, initialization settings and connected to the indoor unit display panel's corresponding port. KJR-10B/DPC(T)-E…
-
2.1.1 Parts name
(1) Mode Selection Button The mode is selected in a sequence as the following figure indicates: AUTT O → C OOL → DRYY → HEAT → FAA N Notes: no heating mode if wired controller is set as cooling-only. (2) Timer on Button Press this button to initiate the auto-on time. Each press will increase the…
-
(6) Reset Button (hidden)
Use a small stick with a diameter of 1mm to Press the RESET button to cancel the current settings and get into the condition of resetting. (7) ON/OFF Button Press the button at the condition of OFF, the OPERATION lamp lights, and the wired controller enters into ON operation, simultaneously sends…
-
2.1.2 LCD display
② ① ⑤ ⑥ F1 ④ ⑦ ⑧ ③ (1) Mode Display Press MODE button can select "AUTO""COOL", "DRY", "HEAT", or "FAN “mode.(HEAT is invalid for COOL ONLY wired controller.) (2) Fan Speed Display Press FAN SPEED to select fan speed from "AUTO", "LOW"," MED" to “HIGH”. Notes: some air conditioners have no MED fan…
-
2.1.3 Operating the wired controller
1)AUTO Operation ※ Insert the power supply of indoor unit, and operation lamp of indoor unit will flash. ※ Press MODE to select AUTO. ※ Set the desired temperature by Pressing the TEMP▲and TEMP ▼, usually the temperature range is set from 17°C to 30°C. ※ Press ON/OFF, the operation lamp of indoor…
-
5) Only Set the Time of Timer Off
※ Press button TIME OFF, the wired controller display SETTING, the icons of HOUR and OFF display on the timer setting area. The wired controller enters into the setting of timer off. ※ Press button TIME OFF again, and then adjust the time of timer off as desired. ※ Continuously Press the button, the…
-
Centigrade/Fahrenheit
6 ※ selection setting Centigrade (Default) Fahrenheit / / / Long press the FAN SPEED and MODE buttons for 5 seconds together, and enter into the initialization function setting interface. ※ After enter into the setting interface, the temperature display area will display YX. Y means the first…
-
(2) Preparation before Installation
Prepare for the following at installation site. NO. QTY. Name 1 Install into the wall 5-core Shield Cable 2 Switch Box 3 Wiring Tube(Insulating Sleeve and Tightening Screw) Remarks Install on the wall 0.05mm2×5 Cable no / / 1 / / more than 15M Notes: Do not turn screws too tightly, or else the cover…
-
(4) Dimensions: 120*120*15mm
(5) Wiring method LCD Infraed Pipe Wired Controller Wire Joint, 5p +5V 5-Core Shield Cable, the length is decided by installation GND RUN Indoor Unit Switch Board Indoor Unit Notes: When install the wired controller, an additional 5-terminal is needed to install in indoor unit, fasten an infrared…
-
2) Wiring diagram between wired controller and duct type of indoor unit
Indoor Unit Electric Controlling Box Plane of Indoor Unit Electric Controlling Box s ’ Plug CN10 Main Board 10-core Connecting Wire Group Signal Reciver 5-core Connecting Group 5-core Shield Cable Back of wired controller A BCDE 3) Wiring diagram between wired controller and high static duct type of…
-
KJR-12B/DP (T)-E Model Description KJR-12B/DP(T)-E General functions and integrates FOLLOW ME function. KJR-12B/DPBG(T)-E Bases on the KJR-12B/DP (T)-E and with backlight, vertical and level swing function. Dun-KJR-12B/DP(T)-E FOLLOW ME and configured with a 20M wire. There’s no brand and backlight…
-
2.2.2 Appearance
(1) Mode Button The mode is selected in a sequence as the following figure indicates AUTO COOL DRY HEAT FAN (HEAT is invalid for COOL ONLY wired controller.) (2) Timer on Button Press this button to initiate the auto-on time. Each press will increase the auto-on time in 30minutes increments. When…
-
(7) ON/OFF Button
Press the button at the condition of OFF, the OPERATION lamp lights, and the wired controller enters into ON operation, simultaneously sends the setting operation information (e.g. temperature, fan speed, timer etc.) to the units. Press the button at the condition of ON, the OPERATION lamp…
-
AUTO
COOL DRY HEAT FAN Notes: For cooling only model, heat mode is invalid. (2) TIMER ON/OFF Display When adjust setting on timer or only on timer is set, the "ON" is lighted. When adjust setting off timer or only off timer is set, the "OFF" is lighted. If on and off timer are both set, the “ON" and…
-
Never turn screws too tightly, or else the cover would be sunk or the Liquid Crystal breaks
Installation of wired controller KJR-12B/DP (T)-E is the same to KJR-10B/DP (T)-E. (1) Installation procedure ※ Circuit of wired controller is low voltage circuit. Never connect it with a standard 220V/380V circuit or put it into a same wiring tube with the circuit. ※ The shield cable must be…
-
A
B Wired Controller 5-terminal Group C D E Wires here adopts 5-core Shield Cable, the length should be accord with the actual conditions . (2) Dimension: 120*120*15mm (3) Wiring diagram 1) Wiring diagram between wired controller and four-way cassette of indoor unit: Indoor Unit Electric Controlling…
-
2) Wiring diagram between wired controller and duct type of indoor unit
Indoor Unit Electric Controlling Box Plane of Indoor Unit Plug Cn10 of Electric Controlling Box Main Board Wire Terminal Group A B C D E Signal Receiver 10-core Connecting Wire Group Signal Receiving Board 5-core Shield Cable A B C D E Grounding 5-core Connecting Group Connecting to wire controller…
-
2.3 Touch- style key wired controller: KJR-29B/BK-E
KJR-29B/BK-E Wired controller specifications Model Power Supply Voltage Ambient Temperature Range Ambient Humidity Range KJR-10B/DB(T)-E 5.0V DC -5°C~43°C RH40%~RH90% Performance Features 1. Operating mode: Cool, heat, dry, fan and auto. 2. Set the mode through buttons. 3. Indoor setting temperature…
-
2.3.2 Wired controller appearance
(1) Remote signal receiving function There is the signal receiver for wireless remote controller on the KJR-29B.You can use the wireless remote controller to control the air-conditioner through the wired remote controller when the system has been powered on. Notes: The wired controller will not…
-
(5)Temperature setting
Under AUTO, COOL, DRY, HEAT modes, press the Temp adjust Up/Down buttons to set the temperature, the adjusting range is 17℃~30℃ (or 62℉~88℉). The setting temperature cannot be adjusted under FAN mode. (6)Timer on and Timer off setting Press the timer/clock setting button, then enter into the timer…
-
function is turned on, the swing icon will be lighted up
(12)Follow me function When the system is running and the operating mode is AUTO. COOL or HEAT, press the left button will activate the Follow Me function. Press left button again will cancel follow me function. When the operating mode is changed, and then will cancel this function as well. When the…
-
Prepare for the following at installation site. NO. Qty.(embedded into wall) Name Specification remarks (only for reference) 2 Remarks 0.05 mm2×5 cable 1 4-core Shield Cable 1 RVVP-0.5 mm ×4 2 86 electrician box 1 / / 1 / / no more than 12M Wiring Tube (Insulating 3 Sleeve and Tightening Screw) ※…
-
Wiring figure: 1) Connect two terminals of embedded 4-core shielding wire with the switching wires of wired remote controller and signal receiving board. Make sure the sequence of 4 terminals (A/B/C/D) should correspond to the wire sequence of signal switching wires (A/B/C/D). C C D D +5V GND B D A…
-
2) Use three GB950-86 M4X20 screws to directly install the back cover on the wall
Screw hole installed on the wall,use three GB950-86 M4X20 3) Use two M4X25 GB823-88screws to install the back cover on the 86 electrician box, and use one GB950-86 M4X20 screw for fixing the wall. Screw hole fixed on the wall,use one GB950-86 M4X20 Screw hole installed on 86 Electrician box, use two…
-
Wiring 1) Wiring, three outlet positions Upper left wire outlet Top side wire outlet Left middle side wire outlet Cutting place of top side wire outlet Cutting place of upper left wire outlet Cutting place of left middle side wire outlet 2) Shielded wiring Putty Trap Putty Putty 3) Avoid water…
-
Wired controller initial parameters setting: 1. Change the related functions of the controller through adjusting the initial parameters, details refer to table 1 2. The wired controller initial parameter includes two codes "XY", the first code "X" means function class, and the second code "Y" means…
-
KJR-120A/BK-E 2.4.1 Functions summary: The controller has functions as follows: 1) Can compatible with the V4 plus heat recycling 3-pipe system and V4 plus 2-pipe system. 2) Setting the mode through buttons; 3) Timer function; 4) Auto-restart function; 5) Query function; 6) Indoor unit error display…
-
ON/OFF 2 MODE 3 CLOCK 4 TIMER ON 5 TIMER OFF 6 OK 7 CHECK 8 FAN SPEED 9 TEMP ▲ Increase the setting temperature 10 TEMP ▼ Decrease the setting temperature 11 SWING Activate/deactivate swing control Enter timer on setting mode 12 10℃HEAT Enter timer off setting mode 13 Confirm and back to main…
-
decrease 0.5 hour. When the timer on or off setting is more than 10 hours, each press ▲ or ▼button will increase or decrease 1 hour, the maximum timer on or off setting is 24 hours. Press OK button or wait for 5s will exit the timer setting and back to normal display. When the timer on/off has…
-
(10)Locking (Hidden)
Use a small stick with a diameter of 1mm to press the LOCK button to lock the current setting, press the button again to unlock (11)Cool-only/ Heat-only/ Cool-heat switching (Hidden) The factory default of the controller is cool-heat mode. Use a small stick with a diameter of 1mm to press the…
-
Disable the alarm function 1250 Hours 2500 Hours 5000 Hours 10000 Hours 2.4.3 Codes description The wired controller KJR-120A can display the fault codes when the units malfunction or protection, the code as follow: Codes Description E0 Modes confliction E1 Communication malfunction between…
-
4 Switch Box Wiring Tube(Insulating Sleeve and Tightening Screw) 1 / 1 / Notes: 1. This manual contains information about the procedure of installing the controller. 2. The circuit of the wired controller is a low voltage circuit, never connect it with a 220V/380V circuit or put it into a same…
-
4) Wiring principle
Turn a screwdriver at the concave on bottom panel of the Controller to remove the Back Cover Controller Back Cover Controller Top Cover Holes match with the 86X86 Wiring box Controller LCD Controller Board Controller Bottom Cover Wood Mounting Screw (M4X20) When installing the controller, you should…
-
2.5 KJR-90A-E
Model KJR-90A-E KJR-90A1-E Description General control function. To avoid mode confliction running mode is fixed to cool mode, other functions are the same as KJR-90A-E. Wired controller specifications KJR-90A-E/ KJR-90A1-E Model Power Supply Voltage 5.0V DC -5°C~43°C Ambient Temperature Range…
-
OFF. If having set TIMER ON or TIMER OFF, the wired controller will cancel these settings before entering into OFF, close the relevant indicator, and then send the OFF information. (3) Adjust Button ▲ Set indoor temperature up. If press and hold on, it will increase at 1 degree per 0.5 second. (4)…
-
2.5.3 LCD display
① AUTO COOL DRY HEAT FAN TIME ON TEMP SET ③ ④ TIME OFF ⑤ ② SPEED ⑥ (1) Mode display; (2) Temperature display; (3) Time on display; (4) Time display; (5) Time off display; (6) Fan speed display 2.5.4 Wired controller installation ※ Preparation before Installation: Make sure the following pasts has…
-
Simplified schematic of wired controller Transmitting tube RUN wired controller E B A D C E B A D C GND +5V Indoor unit signal received panel Indoor unit ※ Installation diagram Connective wires for the display panel (accessory) The shielded 5-core wire pre-embedded into wall. Display panel If there…
-
otes
No 1) Over O tighten the screw wou uld cause the rear r covers de eformed and LCD L damage. 2) When W installattion, please maintain m the sccrews and wire ed controller at a the same he eight level with hout deformed d. 3) When W installattion, please re eserve a certain length of wired controllerr…
-
2.6 Mode-button hidden wired controller: KJR-86C-E
KJR-86C-E Wired controller specifications Model Power Supply Voltage Ambient Temperature Range Ambient Humidity Range KJR-86C-E 5.0V DC -5°C~43°C RH40%~RH90% 2.6.1 Appearance KJR-86C is a Mode-button Hidden Wired Controller. Designed with succinct appearance can be apply for hotel, hospital and…
-
(3) Fan speed button
1) When the unit is turned on, press the FAN SPEED key to set the fan speed of the indoor unit. The fan speed switching order is: AUTO→LOW →MID →HIGH→ AUTO 2) Setting the fan speed to AUTO when the indoor unit will actually run at LOW speed. (4) Setting temperature When the unit is turned on, press…
-
1) Over tighten the screw would cause the rear covers deformed and LCD damage
2) When installation, please maintain the screws and wired controller at the same height level without deformed. 3) When installation, please reserve a certain length of wired controller connectivity cable for future maintenance to take off the wired controller. 2.6.2.2 Wiring figure 1) Wiring…
-
3) Wiring figure of the wired controller connect with the high-static pressure duct type indoor unit. Indoor unit electric controlling box Electric controlling boxs’ plug CN10 Main board Display panel A BC D Back of the wired remote controller 4-core shield cable 4) Wiring figure of the wired…
-
Preparation before Installation
Make sure the following pasts has been prepared. NO. Name QTY. REMARK 1 Wired controller 1 — 2 Installation & owner’s manual 2 — 3 M4×25 Cross head screwdriver 2 4 Installation and owner's manual 1 5 Connective wires to the signal receive panel. 1 For installing the wired controller on the…
-
3. Centraliized con
ntroller MD-CCM0 03 (A) K KJR-90B/M-E E (A) M MD-CCM09 CC CM30/BKE-A A KJRF-18 80A/MBT-E (A) 3.1 1 MD-CCM M03 (A) MD D-CCM03 iss a multifuncctional device e which is able to contro ol up to 64 in ndoor units. And the con nnection length can be up to 1200m. Both h of the follow wing wiring modes…
-
If one or more in-service air conditioners in the network are running, including under setting of timing start/shutdown, the indicator will be luminous. Otherwise, the indicator is off. 4) Locking of centralized controller After receiving the centralized controller locking command sent from the…
-
3.1.2 Buttons and Functions
-
4) Fan speed
In setting operation mode, press this button to set the fan of the indoor unit of the air conditioner to run in the automatic, high, medium or low level of air: 5) Time on In setting operation mode, press this button to set the timing startup of air conditioner; press the key again to exit the…
-
11) Upward button
In the query mode, every time when you press the button, the operation status data of the air conditioner corresponding to the previous row of the matrix will be displayed. If it is currently in the first row, press the key, and the data of the air conditioner corresponding to the last row will be…
-
operation, the shutdown command is issued to the air conditioners in the startup status only, and is not issued to those in the shutdown status. 15) Lock button In the mode setting mode, press the Lock button, and the remote controller of the currently selected air conditioner will be…
-
3.1.3 LCD display
70 Control System
-
таблицы и схемы — в просмотре
-
3.1.4 Query and Error code
The CCM03 centralized controller offers the function of query of indoor units’ running state and displays the error code when some of the indoor units fail down. 1. Press the query button to activate the query function. Firstly the display panel will display the 1st units’ state. 2. Use the UP…
-
E2
T1 sensor malfunction E1 Communication malfunction E0 Phase sequence disorder or loss of power phase 07# 06# 05# 04# 03# Communication malfunction between centralized controller and PC(gateway) 02# Communication malfunction between centralized controller and functional module 01# 00# Communication…
-
3.1.5 Installation
Note: The installation procedure show in Fig.1-1 ~ Fig.1-5 is for MD-CCM03(A) and UL-CCM03(A)/E 179 153 RS232 Pin hole: for connection to computer COM port 78 78 Emergency Open Swich,used to star up all air conditioners RS485 Converted RS232 module Emergency Stop Swich,used to shut down all air…
-
Note
The installation procedure show in Fig.1-6 ~ Fig.1-8 is for MD-CCM03/E, MD-CCM03/E(M),MD-CCM03/E(T), MD-CCM03/E(H) and MD-CCM03/ET(H). 92 136 Installation dimensions: As shown in the figure on the right side. Installation screw holes (4 holes) 70.5 48.5 83.5 Rotatetheflatheadscrewdriver slightly…
-
Network interface Centralized controller A maximum of 64 pieces Centralized controller POWER Junction Box Indoor unit Junction Box One centralized controller can be connected to 64 indoor units as a maximum Indoor unit Junction Box The shielded wire must be reliable grounded Junction Box Junction…
-
3.2 Touch-style key centralized controller:CCM30/BK-E, CCM30/BKE-B
The CCM30/BK-E is new designed and it is a touch-style key centralized controller. It can be connected up to 64 indoor units, and the connection length can be up to 1200m. The CCM30 centralized controller has the air filter cleaning reminding function and it is convenient to remind users to clean…
-
→ Single → Global the centralized controller press the “Reset”key five seconds to reset TIME OFF In the setting page, shift to the timing startup/shutdown setting page. RESET OK TIME ON SET On/Off the unit QUERY MODE FAN LOCK SWING DEC INC 1 In the setting page, set the temperature ,increase or…
-
(3) Mode key
Under the setting operation mode, press this key to set the operation. →cooling → heating → Fan only → off → (4) Fan key Under the setting operation mode, press this key to set the fan of the indoor unit to run in the automatic, high, medium or low level of air. → auto → low → medium → high → (5)…
-
any other time, press this key will select the previous corresponding position air conditioner
In the setting mode, if selected all the air conditioners to operate, this key is invalid. If it is on the first row, press this key again, and shift to the last row corresponding air conditioner. If you hold down this key, the row will decrease one by one. (12) Add key 1) Query mode: Press this…
-
H our
-
3.2.3 Other operations
※ Various locking functions 1. Centralized controller locking The centralized controller locking state will be recorded when powered off. It won't dismiss when re-power on until receiving the unlocking order. 1) Effect ① When the centralized controller is under locking state, it cannot change the…
-
2) Operation
Can set the heat and cool mode lock or not Under mode locking state, if set the new mode locking, it must be unlocking first, then can operate the new mode locking. ① Can lock or unlock through the computer. ② Can operate by a centralized controller. In the centralized controller setting interface…
-
1. Use "
" key to TURN ON and TURN OFF the unit: Press this key can operate a single air conditioner or all the air conditioners in the centralized controller network. 1) Choose the object. Press SET key to choose a single air conditioner or all the air conditioners in the centralized controller network. If…
-
※ Air filter cleaning remind function
1) The centralized controller records the total running time of the indoor unit. When the accumulated running time reaches the pre-set value, the air filter cleaning reminding icon “FL” will be lighted up to remind users that the air filter of the indoor unit need to be cleaned. When the centralized…
-
3.2.4 Fault and protection codes
Fault code Content EF Other faults EE Water level detection malfunction ED Reserved EC Cleaning malfunction EB Inverter module protection EA Current of compressor is too large (4 Times) E9 Communication malfunction between main board and display board E8 Wind blowing speed is out of control E7…
-
P5
Pressure of discharge is too high P4 Temp. of discharge pipe is abnormal P3 Temp. of compressor is abnormal P2 Condenser high-temperature protection P1 Anti-cool air or defrost protection P0 Evaporator temperature protection 3.2.5 Centralized controller installation ※ Dimensions (Unit: mm) There are…
-
CCM30/BKE-B
※ Installation diagram Insert the flathead screwdriver into the concave on the upper side of the box, and rotate slightly to open the upper cover(3 places). Fix the screws of the centralized controller (GB845/ST3.9*25) Base Dial code ON Address dial code Front cover ※ Dial code position Address…
-
3.3 Weekly schedule timer centralized controller: MD-CCM09 (A)
MD-CCM09/E is designed base on the CCM03, max. 64 indoor units control, weekly schedule timer function. With the function above, CCM09/E can’t be connected to the network control system. And actually it does not have the port F1, F2, E, which are needed if connects to the computer. 7 -days Weekly…
-
On-line condition matrix table of AC 0-63 8 Economy run 2 Query 9 Swing 3 Set 10 Electric auxiliary heater 4 Operate result 11 Locking keyboard 5 Date time 12 Remote controller locking: Does not respond signal from remote controller. 6 Run mode 13 Heating mode locking: only heating mode is effective…
-
The main interface of the weekly-timer central controller (user interface) 1) Under the other pages, press to return to the main interface. 2) Under the other pages, automatically return to the main interface when no operation for a period of time. 3) The main interface displays the on-line…
-
Setting interface of weekly timer parameters of single weekly-timer central controller
1) Under the main interface, press to display the parameter setting interface of single weekly timer. 2) Automatically return to the main interface if no operation is performed for a period of time. 3) Under this page, set the weekly timer parameters of single air conditioner, including startup…
-
3.3.4 Button names
Set Time On/Off Weekly-timer Confirm to save Query Airconditiner Enter the setting page of the weekly timer Set Airconditioner Used to select the air conditioner to be set or queried Set Set Set Swing Run Mode Fan Speed Reset Set Lock 1) On/Off key Press the ON/OFF button. All air conditioners will…
-
7) Mode key
When setting the indoor unit, it is used for setting the running mode of the indoor unit which includes Automation, Cooling, Heating, Fan mode, Dry and shutting down. 8) Fan key When setting the indoor unit, it is for setting the wind speed of the indoor unit which includes high speed, middle speed…
-
3.3.5 Operating the centralized controller
(1) How to set the running status of the air conditioner? Under the main interface 1. Press Set to enter the setting status interface of single air conditioner. Press the button repeatedly to select Single and All alternately, display “Set”. If you select Single, press to select one. 2. Selecting…
-
(3) How to lock and unlock the remote controller of the air conditioner?
Under the main interface 1. Press Set to enter the setting status interface of single air condit ioner, press the button repeatedly to select “Single” and “All” alt ernately, dis playing “Set”. If you select “Single”, press to select one. 2. Selecting “All” indicates to set the running status of all…
-
(6) How to set the function and relevant parameters of the weekly timer of the air conditioner?
Under the m ain interface 1. P re s s to e n te r th e s e ttin g s ta tu s in te rfa ce o f s in g le a ir co n d itio n e r, p re ss th e b u tto n re p e a te d ly to se le ct “S in g le” a n d “A ll” a lte rn a te ly, d isp la y in g “S e t”;if se le c t “s ig le” ,p re ss to s e le ct o n e .…
-
(7) How to turn off the weekly timer setting of a period of an air conditioner?
Under the main interface 1. P ress to ente r the se tting status interfa ce of sing le air co nditio ner, pre ss the bu tton repe ated ly to select “S ing le” an d “A ll” alternately, displa ying “S e t”;if sele ct “sigle” ,p ress to se lect on e. Press to select air conditioner to the next step…
-
(8)How to query the weekly timer setting parameter of the air conditioner?
4. Set the parameter of period 1, including shutdown time, startup time, running mode, Fan speed and temperature. First of all, set the startup and shutdown time. Press to select the startup time and shutdown time. Press to modify the startup and shutdown time. Press to save the parameter of the…
-
(10)How to modify the system time?
Under the main interface 1. Press for 5 seconds, enter the time-setting interface. 2. Press for a long time to select the minute/ hour/ day/ month/ year that need to be modified. 3. First, press to select the Year that needs to be modified. 4. Press modify “Year” 5. then Press to select the “Month”…
-
3.3.6 Installation
The thickness of the central controller cable shall be adjusted according to the length of the cable. A proper cable tube shall be used to install the cable of the central controller. Insert the flat tip screwdriver into the recess on the top panel of the case and slightly turn to open the top cover…
-
Emergency Open Swich,used to
star up all air conditioners Emergency Stop Swich,used to shut down all air conditioners Communication interface to the indoor unit Power AC 220V Fig.5 92 136 Note: The installation procedure show in Fig.6 ~ Fig.8 is for MD-CCM09/E and MD-CCM09/E(H) Installation screw 70.5 83.5 102 48.5 Fig.6…
-
Rotatetheflatheadscrewdriver slightly
toopentheupper cover (at points). Screws for fixing the centralized controller (GB845/ST3.9*25) Holder Address bits Bit location Address range ~ 00 ~ 15 X YE OFF Upper cover Fig.7 L N (Fig.8) Power connector of the central controller 220V/AC COM ON—COM:Emergency open switch, used to start up all air…
-
KJR-90B/M is a unified centralized controller, which allows us to control up to 16 indoor units simply and compactly. It commands the indoor unit to work at only 2 modes, cooling and heating. Besides this commanding, users could also modify the indoor units working mode by the remote wireless…
-
Notes: 1. if the red light flashes quickly, it means the corresponding indoor unit malfunctions
2. If no one presses the keys of the controller, the controller would turn itself into power saving mode, in which all the lights fade out. Press any key to stop this mode. (3) Unified mode setting key Press this key to set all the units’ mode. Only two modes can be set by this key. They are the…
-
Indoor unit
electric cabinet Indoor unit connected terminal (Blow up) The butted joint which is educed from indoor unit X Y E Pre-embed a shielded 3-core wire in wall 5V GND 5V The display control board component in the indoor unit accessory Connective wires for the display control board (accessory) GN D The…
-
3.5 Centralized controller KJRF-180A/MBT-E and KJRF-180A1/MBT-E
The only difference between KJRF-180A/MBT-E and KJRF-180A1/MBT-E is their cabinet’s shape. Their controlling functions are totally the same. Newly designed centralized controller with graceful appearance. Able to centralized control up to 16 indoor units, which group can contain 1 fresh air…
-
The signal wire should be 3-core shielded wire and the wire should be provided by licensed electricians. To make signal transmission steady and to protect the facilities, the signal transmission wires should not be near to the power line. An interval of 300mm-500mm should exist between these two…
-
⑧Display the set temperature of the air-conditioner
Display the current setting temperature of the corresponding air-conditioner. 3.5.3 Buttons and functions (1)Mode button: Press this button to change the indoor unit’s running mode. The changing sequence of the mode is as follows, Auto/ Cool/Dry/Heat/Fan. (2)Temperature setting button: Press this…
-
(11)TIMING button
Press this button to start setting the turning on and turning off schedule of the indoor unit. (12)UP and DOWN button: Used for adjusting the setting temperature the air conditioner and the water heater. Users can lock or unlock the keyboard by pressing the 2 keys synchronously. (13)CANCEL button…
-
Base cabinet: 1) KJRF-180A/MBT KJRF-180A1/MBT Control System 111
-
Detaching the shell Turn the slotted screwdriver lightly, then it can open the upper cover(3 places) Screw nail use to fix the multifunctional controller (GB845/ST3.9*25) Chassis Flip cover Front cover ※ Wiring at the back X Y E P Q E L N Power connector (198V-242V~50/60Hz) Connector connect with…
-
Available wiring diagram 3.5.5 Error and Diagnosis 1. If the centralized controller cannot detect the indoor units, and does not display the icons . Check the wiring from the malfunction indoor unit to the controller. Please make sure that the joint are tied steadily and the wiring obeys the…
-
4. Gateway
MD-LonGW64/E MD-CCM08/E GateWay01/E IMM441V4PA512 4.1 Lonworks BMS gateway: MD-LonGW64/E The new LonWorks gateway MD-LonGW64/E has been compliance with Lonworks standard and can be connected up to 64 indoor units to the LonWorks network directly. It can connect multiple refrigeration systems and do…
-
4.1.2 System configure
Indoor units can be connected to the MD-LonGW64 gateway, and we can gather all the units’ information and control the indoor units through MD-LonGW64. As a result, the indoor units need firstly connecting to the computer to make a central monitoring system. The composition of the whole network is as…
-
4.1.3 Connecting ports
LON- and LON+ port: The ports should be connected to the computer’s COM port, using the RS-232 communicative standard. X Y E port: These ports use a removable connecting way to help user connect the LonWorks network conveniently. POWER: This port should be connected to the AC 220V power adaptor.…
-
4.2 BACNET BMS gateway: MD-CCM08
MD-CCM08/E is a gateway to connect the indoor units and outdoor units to the BACnet. BACnet stands for the Building Automation and Control Network. MD-CCM08/E gathers the information of the IDU and ODU. Besides, MD-CCM08/E is able to send the command to the units. Be able to bridge the indoor and…
-
4.2.2 Connecting ports and functions
Ethernet interface, connect with BACnet/IP network Four groups of 485 interfaces, each one connect with a universal BACnet MD-CCM08 has some kinds of connecting ports. Ethernet and LonWorks ports are used for further function designed and do not function by now. Ethernet B port is an Ethernet…
-
4.2.3 Network example
Outdoor units MD-CCM08 Indoor units CCM02 CCM03 RS485 Outdoor units HUB BACnet/IP protocol TCP/IP Indoor units CCM03 Monitoring system BMS 4.2.4 Available BMS 1 Company BMS software SIMENS APOGEE Brand APOGEE A N Y W H E R E TM 2 TRANE Tracer Summit TRACER SUMMT 3 Honeywell Alerton 4 Schneider…
-
4.3 Modbus BMS gateway: GateWay01/E
GateWay01/E support the Modbus protocol network, bridge the Midea central AC system to the BMS, compose a Modbus network of up to 1024 indoor units and 64 outdoor units. support the Modbus protocol network Each GateWay01/E can connect 1 CCM02 and 1 CCM03, 64 indoor units and 4 outdoor units …
-
M-INTERFACE gateway is used for querying and controls the air conditioning indoor unit, and transmits the status information of the indoor unit to the computer and transmits the controlling and querying orders sent by the computer to the indoor unit. M-INTERFACE Gateway has 8 M-net terminals, 1 LAN…
-
Detailed drawing of installation holes (Unit: mm) Installation precautions: Install at a place where should not affect by electromagnetic wave or dust; Avoid to install at a place where affect by sunshine or heat source device etc; Avoid to install at a place where has high humidity or can…
-
4.4.3 M-INTERFACE Network
1) M-INTERFACE gateway can connect to the local area network or Internet network through a LAN terminal. 2) M-net terminals are listed to be two rows, 1 to 4 is XYE terminals, and 5 to 8 is K1, K2 and E terminals. Computer or other similar devices can visit M-INTERFACE WEB through browser, and then…
-
5. Network monitoring system
5.1 The 4thgeneration network monitoring system IMM – Intelligent Manager of Midea Intelligent Manager of Midea, designed specifically to control VRF systems, is based on a centralized format and dedicated to the complete control and monitoring of all the system’s functions. It can be used as a…
-
6. Accessories
Appearance Model DTS634/DTS636 MD-NIM05 MD-NIM09 MD-CCM02 KJR-31B/E Description Send the electric energy data to outdoor unit for realizing network fee charge function. Match hotel card system to control the air conditioner. Automatically turn off and turn on the indoor unit, saving energy. The…
-
6.1 Digital ammeter DTS634/DT636
The digital ammeter DTS634/DT636 is a device to calculate the power consumption of the outdoor unit and transmit the information when it is required. Steadily functioning and needs no adjusting. Be with great precision. Works in wide working temperature, from -35 ℃ to +55℃. Be able to be…
-
4) Three-phase three-wire system with current transformer and voltage transformer
A B C 6.1.2 Installation Notes: The ammeter device is an optional device. Without this device, the central AC system is also able to work normally. If users want to realize the network fee calculating function, this device is necessary. And each outdoor unit should equip one ammeter. Do remember to…
-
6.2 Hotel card key interface module
MD-NIM05/E and MD-NIM05/E-1 MD-NIM05/E and MD-NIM05/E-1 are mainly designed for the hotel card-insert system. It offers a smart way to save energy and manage the air conditioners. A smart way to save energy and money. Cooperates with the hotel card-insert system. Extra power supply is…
-
2) Wiring assy. 1 connects the CN1 of hotel card-insert assy. to wired controller of air conditioner. 3) Wiring assy. 2 connects the CN2 of hotel card-insert assy. to display board and main control board of air conditioner indoor unit. Notes: COM1 and GND terminals should be short to work and not be…
-
6.2.3 Operation description
1) Connect 5-place terminal at fixed rated wired controller via 5 terminals: A, B, C, D, and E. 2) Connect LCD at main control panel of indoor unit via terminals REV, C, D, and E. 3) Upon wiring according to the wiring diagram in, Please power to the wired controller and switch on it. When card has…
-
6.3 Infrared sensor controller: MD-NIM09/E
Infrared control box Infrared sensor module MD-NIM09/E is an infrared sensor, which is able to detect whether there is people nearby and auto change the air conditioner back to running mode. This humanistic device helps making a comfortable environment for the users and the turning down the…
-
Installation example
MD-NIM09 must be work together with the wired controller. As show above, the MD-NIM09/E has 3 connecting port. CN1 is used for connecting the wired controller. CN2 is used for connecting the indoor unit’s display panel. CN3 is used for connecting the infrared sensor. The switch S1 stands…
-
6.3.3 Installation
※ Dimensions Infrared sensor ※ Control box Connecting and Assembly Step 1 Control System Step 2 Step 3 Step 4 Step 5 133
-
Wires methods Connect to CN1 infra-red inductive control box. White Black Red Orange Blue E (only if E port is available) D C Wired controller B A Butt joint wire (Used for lengthen the wire only) From CN2 of infrared inductive control box Butt joint Connect to indoor main board Connect to display…
-
6.4 Outdoor unit controller: MD-CCM02/E
RS485 communication protocol Up to 8 systems, max.32 outdoor units can be connected to the Network monitoring and BMS. It can display the operating parameter of outdoor units Can display the error or protection code of outdoor units. 6.4.1 Summarize of outdoor CCM The functional only can be…
-
To differentiate the CCM02 and CCM03, the addresses of CCM02 range from 16-31. Every time we press the address button of a CCM02, the corresponding CCM02's address increase by 1. When the address come to the end 31, press the key again could make the address back to the starting address 16. ◆…
-
(7) Mode Button
Pressing the OK button to enter into the Mode Set, and select circularly between Forced Cooling and OFF state. (8) OK Button Pressing the OK button to confirm all setting and send the corresponding air-conditioners. (9) Lock Button All the other button will not be controlled anytime when Pressing…
-
Display
means the total number of online units Stand-by Page can display the address of CCM with the address format of “Addr XX”, here ”XX” equals the real address of CCM plus 16,and the range of “XX” is 16-31. Query Page Display: 1) Query Page Display the query icon. 2) Displaying the address of selected…
-
25) Page 15 displays the most advanced malfunction icon "MALFUNCTION" and the code
26) Page 16 will display the most advanced protection icon "PROTECTION" and the code. Notes: The page will increase or decrease by 1 every time you press “PAGE UP” or “PAGE DOWN”. Select the online outdoor unit by Press the “previous” or “next” freely. SET PAGE DISPLAY: 1) Set Page Displays” Set”…
-
6.4.4 Installation
1. Basic Requirements 1) Applicable Power Voltage Range: Input Voltage 220~240V/AC. 2) AC Input Power Frequency: 50Hz/60Hz. 3) Working Ambient Temp.:-15°C -+43°C 4) Working Ambient Humidity: RH40%~RH90%. 2. Dimensions: 120*120*15mm 3. System configure With MD-CCM02/E, we could both centrally display…
-
RS232 terminal
Plug in the COM port of computer RS485 invert RS232 module Good method of peeling communcation wires Connect other central controller Connect matched R120Ω in the front-end communication Connect matched R120Ω in the rear-end communication ModuleOniN OnlieNoutdr nigF lCOMP…
-
Remarks
(1) In the wiring, the part from Rs485 to Rs232 is only needed when connecting with PC. And one PC can connect maximum 16 outdoor MD-CCM02 and 16 indoor MD-CCM03. The addresses of MD-CCM03 ranges from 0 to 15, while the MD-CCM02 ones from 16 to 31. And the address of any two outdoor CCM can't be the…
-
5. Structure and composition
Back Cover Turn a screwdriver at the concave on bottom panel of the Wired Controller to remove the Back Cover Top Cover Holes matche with the 86X86 Wiring box LCD Board Bottom Cover Wood Mounting Screw (M4X20) When installing the Wired Controller, you should adjust the bottom of the Wired Controller…
-
6.5 Mode lock controller KJR-31B/E
KJR-31B/E is a wired centralized mode lock controller. With this device, we could lock the mode of all the units connected to this controller to avoid mode conflict. When the mode conflict happens, e.g. some indoor units request cooling and some heating, the outdoor unit could only work in either…
-
To establish a steady network the following should be noted
The signal cable and power cable of the central controller cannot be contained in the same cable tube. The distance between the signal cable tube and power cable tube shall be between 300mm -500mm at least. The total signal cable length of the central controller shall not exceed 1,200m. Make…
-
4. HEAT light
Press the mode switch leftwards to turn all the indoor units to heating only mode and the HEAT light will be on. This light indicates that all the indoor units are running at cooling mode. Users can only set the heating parameter such as temperature and fan speed by other controller. If the user…
-
Control System Controlling wiring connection Mode-loc king controller ※ Tie the screw ※ Assemble the front shell to the base ※ Connect the power adaptor to the controller Indoor unit The power supply of the KJR-31B/E should be 220-240V 56/60Hz. 147
-
6.6 Fault alarm controller: KJR-32B/E
KJR-32B is specially designed for engineering applications. It does not display the outdoor unit’s working parameters, but it can connect to the alarm device when outdoor unit is working abnormally, the RUN light will flash. Connect the outdoor unit through K1 K2 E terminals. Connect the RS485…
-
RS232 terminal
Plug in the COM port of computer RS485 invert RS232 module Connect other central controller F1 F1 F2 F2 E Better way of stripping the communication wire F1 F1 F2 F2 E Connect matched R120Ω in the front-end communication F2 F1 E K2 K1 Computer communication Air-conditioner communication connecting…
-
6.6.3 Installation
1. The RS485 shift RS232 module, connecting wire in the wiring figure can be used only when network monitoring need to connect the computer; 2. One computer cannot connect with one fault alarm and outdoor central controller at the same time, you must choose one for connection; 3. When connected to…
-
6.7 Indoor unit group controller: KJR-150A/M-E
KJR-150A is specially designed for V4 plus indoor units and its appearance is the same as KJR-32B. A group controller can connect up to 16 V4 plus indoor units through X1 Y1 E, but it cannot directly connect to the central controller. If you need to use a central controller or a PC, you can connect…
-
6.7.2 System wiring diagram
6.7.3 Installation 1. When selecting the old display board, please dial the first bit of SW1 to ON. When selecting the new display board, please dial the first bit of SW1 to OFF. 2. In the group, anti-cold air switches of all the indoor units have to be the same with the group controller's, or some…
-
Notes: Communication signal in CN5(X1 Y1) and CN6 (E) is a low voltage signal. Do not apply high voltage, or breakdown will occur and even cause fire. Group controller base Group controller main control panel Group controller cover Fix the base at the holes, and use the cross screwdriver to screw…
-
6.8 AHU control box 14&28&56kW: AHUKZ-01, AHUKZ-02, AHUKZ-03
Electrical mounting plate can be flipped, easy to install and maintain Can be used to connect VRF outdoor units with DX AHU or other brand indoor units, but cannot connect to the heat recovery system The Sheet Metal integration design Built-in electronic expansion valve One main control…
-
6.8.2 Error and protection codes
When the AHU control box is working abnormally, it can display the malfunction and protection codes through the new or old display panel. At the same time, you can check the temperature parameters by the LED display panel New display panel Codes FE H0 Old display panel Descriptions Without address…
-
6.8.3 Query instructions
Sequence Display contents Remarks 0 Normal display 1 Address of AHU control box 2 Capacity of AHU control box 3 Net address of AHU control box 4 Actual setting Temp. 5 T1 actual Temp. Minimum displays - 9 ℃ 6 T1 actual Temp. Minimum displays - 9 ℃ 7 T2 actual pipe Temp. Minimum displays - 9 ℃ 8 T2B…
-
6.8.5 Dial code definition
1) SW1 definition S W1 ON SW1 ● 1 means the factory test mode ● 0 automatic search address mode (factory default) ON 1234 SW1 1234 S W1 ON S W1 ON 1234 1234 SW1 S W1 ● 00 means DC fan static pressure selection 0 set (reserved) ON ON 1234 1234 2) SW2 definition y SW2 ON 1234 SW2 ON 1234 SW2 ON 1234…
-
6) J1, J2 definition
J1 7) 0/1 definition Table.7 12 J1 Jumperless for has power down memory function ON J1 Means 0 J1 Jumper for has no power down memory function J2 ON Reserved Means 1 6.8.6 Installation methods 1) Installation methods for vertically, and horizontal installation is invalid Install vertically Wrong…
-
6.9 HRV wired controller: KJR-27B/E
KJR-27B is individually designed for HRV—Heat Recovery Ventilator. The HRV can work in the following modes: exhaust, air supply, bypass, heat exchange, and auto. Wired controller specifications Model KJR-10B/DB(T)-E Power Supply Voltage 5.0V DC -15°C~43°C Ambient Temperature Range Ambient Humidity…
-
(2) Timer on button
Press this button can set TIMER ON, each time press this button, the time moves forward by o.5 hours. When the set time is over 10 hours, each time press the button to the time moves forward by 1 hour. If want to cancel the TIMER ON, then adjust the time of TIMER ON as 0.0. (3) Timer off button…
-
(9) Adjustment button
The button only for time adjustment, and press the ▲ button, time increases. (10) Adjustment button The button only for time adjustment, press the ▼ button, time decreases. (11) LOCK button (hidden) Use a small stick with the diameter of 1mm to press the LOCK button can lock the current setting…
-
3. Continuously press adjusts up button. The time of the timer will increase 0.5 hours per time. After the time of timer reaches to 10 hours, the time will increase 1hour each time. 4. 0.5 seconds later, after finishing the adjustment, the wired conditioner sends the information of time on, the…
-
(2) Wiring principle sketch HRV Electric Controlling Box Signal Receiving Board Electric Controlling Boxs’ Plug CN10 10-core Connecting Wire Group Main Board 5-core Connecting Group Wire Terminal Group Signal Receiving Board Grounding ABCDE 5-core Shield Cable Connecting to wire controller Back of…