Система управления OM LSQ-NET E (V2.1). Инструкция по эксплуатации.
Смотрите также: Информационный буклет →
Загружаем документ…
Текст инструкции
-
AIR-CHILLING HEAT PUMP MODULE
GROUP’S NETWORK CONTROLLING SYSTEM APPLICATION MANUAL Thank you very much for purchasing our air conditioner, Before using your air conditioner, please read this manual carefully and keep it for future reference.
-
1. SYSTEM INTRODUCTION
1-1 System Introduction This system is mainly composed by Epistatic Unit (network control system of epistatic unit), KJR-08B wire controller as well as sub-module. Each Epistatic Unit connects with a 485 bus via serial port; mostly 16 set of KJR-08B wire controller could be connected with a bus…
-
System structure as follows illustration
-
2. SOFTWARE INSTALLATION
1-1 Installation the FireBird database 1) Installation window as Fig. 2-1. Select English as the used language, click “OK” to continue: Fig.2-1 2) Installation window as Fig. 2-2, click “Next” to continue: Fig.2-2 3
-
3) Installation window as Fig. 2-3, select “I accept the agreement”,click “Next” to continue
Fig.2-3 4) Installation window as Fig. 2-4, click “Next”vvvv to continue: Fig.2-4 4
-
5) Installation window as Fig. 2-5, click “Browse…..” Key to select the installation address for
install the Firebird database (See Fig. 2-6), and then click “Next” to continue the installation: Fig.2-5 Fig.2-6 5
-
6) Installation window as Fig. 2-7, select the items as Fig. 2-7, and click “Next” to continue
the next step installation: Fig. 2-7 7) Installation window as Fig. 2-8, click “Next” to continue: Fig. 2-8 6
-
8) Installation window as Fig. 2-9, select the items as Fig.9, and click “Next” to continue the
next step installation: 9) Installation window as Fig.2-10, click “Install” to continue: 7 Fig. 2-9 Fig. 2-10
-
10) Installation window as Fig. 2-11, until the window as Fig. 2-12 displays, and then click
“Next” to continue the installation: Fig. 2-11 Fig. 2-12 8
-
11) Installation window as Fig. 2-13, click “Finish” to finish the installation
Fig. 2-13 2-2 Install the FireBird ODBC 1) Installation window as Fig. 2-14, click “Next” to continue: 9 Fig. 2-14
-
2) Installation window as Fig.2-15, select “I accept the agreement”,click “Next” to continue
Fig. 2-15 3) Installation window as Fig.2-16, click “Next” to continue: Fig. 2-16 10
-
4) Installation window as Fig.2-17, click “Browse…..” Key to select the installation address for
the Firebird database (See Fig. 2-18), and then click “Next” to continue the installation: Fig. 2-17 Fig. 2-18 11
-
5) Installation window as Fig. 2-19, select the items as Fig. 2-19, and click “Next” to continue
the next step installation: Fig. 2-19 6) Installation window as Fig. 2-20, select the shortcuts folder’s name in the Initial Program, click “Next” to continue the installation: Fig. 2-20 12
-
7) Installation window as Fig. 2-21, click “Install” to continue
Fig. 2-21 8) Installation window as Fig. 2-22, until the window as Fig. 2-23 displays, and then click “Next” to continue the installation: 13 Fig. 2-22
-
Fig. 2-23
9) Installation window as Fig. 24, click “Finish” to finish the installation. Fig. 2-24 14
-
2-3 Install the Air-Chilling Module Group Network Controlling Software
1) Run the “Setup.exe” tool in the installation disc, window shows like Fig. 2-25 , click “Next” to continue the installation: Fig. 2-25 2) Installation window as Fig. 2-26, click “Browse…..” Key to select the installation address, and then click “Next” to continue the installation: Fig. 2-26 15
-
3) Installation window as Fig. 2-27, click “Next” to continue
Fig. 2-27 4) Installation window as Fig. 2-28, until the window as Fig. 2-29 displays, and then click “Close” to finish the installation: Fig. 2-28 16
-
Fig. 2-29
2-4 Install the Softdog Drive-up 1)Run the “MicroDogInstdrv.exe” file in the installation disc, window as follows figure displays, and insert the Softdog to any USB serial port in the epistatic unit, click “Installation” key: 17 Fig. 2-30
-
2)Window as follows shows, select “Install the software automatically (Recommended)”,
click “Next”: Fig. 2-33 3)System will search the Drive-up programmer automatically, window as follows will show: Fig. 2-34 19
-
4)After find out the Drive-up programmer, the follows window will shows, click “Continue
Anyway” key to continue installation: Fig. 2-35 5)The follows windows will shows, click “Finish”;then the Softdog Drive-up programmer successfully be installed. Fig. 2-36 20
-
3. THE SOFTWARE INTRODUCTION
1. Control operation mode in the refrigeration system. 2. Query real-time operating parameter in the main system and subsystem. 3. Set up the weekly timing that could realizes the schedule management for the refrigeration system. 4. Record refrigeration system error. 4. SOFTWARE APPLICATION Premise…
-
3、The button where the red circle shows as Fig. 4-3 is “Start”, then click the button and open
the database server; if the button is “Stop” (display as Fig. 4-4), then it means that the database server has been opened. Fig. 4-3 Fig. 4-4 22
-
4-1 Software login
Fig. 4-5 1)The LOGIN window as Fig. 4-5. 2)User need to input the name and password (default name: Admin, default password: Admin);user’s name and password could be changed after login. 3)Select the computer serial port. The system default selection is COM1 (the software will checkout the available…
-
5)Be sure that the softdog has been inserted to USB port all the time while the software is
running, otherwise the softdog error dialogs displays like Fig. 4-7. Fig. 4-7 6)When provid a wrong USERE’S NAME, the window as Fig.4-8 will be display, while PASSWORD error, the window shows like Fig.4-9. Fig. 4-8 Fig. 4-9 7)In case the password error time exceed 6 times (i.e. the 7th times…
-
4-2 Detail Application Manual
Fig. 4-12 Main interface of this software as Fig. 4-12, detail as follows: 1)Menu includes:“System” “Equipment management” “Schedule management” “Communication parameter” “Help” 2)System configuration illustration (The ① show as Fig. 4-12): Not more than16 wire controllers could be connected to the…
-
For the meaning of the different color represent, please see ”4. AC system diagram in 4
Software Application” 3)“Lock KJR” (The ② show as Fig. 4-12): To lock or unlock the current selected wire controller to limit the wire controller setting the refrigeration system. 4)”System operate set” (The ③ show as Fig. 4-12): To set the operation of the selected refrigeration system. 5)“Query…
-
4-3 Menu Application
1)“System” includes:“Password Modification” “Re-login” “Exit the program” See Fig. 4-15. Fig. 4-15 ①Click “Password Modification” will display window as Fig. 4-16――input old password as requirement, and then reset a new password, click “OK” or “Modify”, window as Fig. 4-17 will show that new…
-
②Click “Re-login”, window as Fig. 4-20 will
③Click “Exit the program” to quit the display that interface ask user whether re- program, while click “Cancel”, system will login the system, if yes, please click “OK not quit. Click “Re-login”, system will close the main interface and enter to the login interface again. Fig.4-21 Fig.4-20…
-
Detail operation procedure as follows
a Add a wire controller: Select the wire controller address (0-15) at the “KJR Address”, fill the wire controller name at “KJR Name” and click “Save”. b Modify wire controller: Select an existing wire controller (by click the drop down list of the KJR Address at the left Chart or by click the drop…
-
a、Add module group: Select the existing wire controller address, and click the “New” key to
select the module model at the drop-down box (30KW(P) 35KW(P) 60KW(P) 65KW(P) 130KW(P) 200KW(P) 30KW(T) 35KW(T) 60KW(T) 65KW(T) 130KW(T) 200KW(T) ),and fill the module name in “Module Name” column, click “Save” key to complete the module group setting. When the numbers of modules under connect the…
-
Fig.4-32
a Add sub-module: Select the existing wire controller address from the “KJR Address”, and select the configured module group at the drop-down box of “Module name”, select the submodule address in the drop-down box of the configured “Sub-module address”, and then click “Add”. The sub-module would not…
-
b、Delete sub-module: Select the sub-module which wanted to delete (select the wanted
delete sub-module at the drop-down box of “Sub-module address”), and click “Delete” to finish this operation. 3)“Schedule management” includes: “Weekly timing setting” and “Error record” See Fig. 4-35 Fig.4-35 ①Click “Weekly timing set” a window as Fig. 4-36 would pop up——finish the weekly schedule…
-
a、KJR Address——Wire controller address, each wire controller represents one refrigeration
system. b Weekly timing function―-Display the weekly set status in the current wire controller is ON or OFF (ON or OFF could display as long as at least one weekly schedule has been set, otherwise, nothing would display.) c Detail weekly timing parameter―― Week, Period, Time On, Time Off, Timing…
-
e、Save(See the ② key in the Fig.4-36)―― Save the current settings or the modified
settings. f Modify(See the ③ key in the figure) ――Press this key the parameter of selected period become changeable, and then click “Save”. Press the key again, all parameters in this period become unchangeable. see Fig. 4-40. refrigeration system Fig.4-40 Select the setting Period, click “Modify”…
-
g、Delete key (See the ④ key in the figure) ――select a Period and click the key, the current
selected Weekly Timing setting period could be deleted. Click the key, window as Fig. 4-42 shows, click “OK” to delete Period. Successful delete the Period, message box as Fig. 4-43 will show. Fig.4-43 Fig.4-42 (1)Detail procedures of add a new Weekly Timing Schedule: a Select a wire controller: By…
-
Note: The ON/OFF time of the weekly timing can not be at the same time point, the following
will be not allowed for example if the ON time was 8:00 of Period1 and the OFF time was 8:00; and the OFF time of Period1 was 10:00 and the ON time of Period2 was 10:00. If there is error and then will pops-up prompt dialog box display as Fig. 4-46: Fig 4-46 If no Timing Status has been set, a…
-
If no Setting temperature has been set, a message box as Fig. 4-50 would pop up
Fig.4-50 (2)Detail procedures of modify a Weekly Timing Schedule: a Select a wire controller: By clicking the “System diagram for weekly timing AC” wire controller icon at the left side in the wire controller, or by selecting the wire controller at the drop-down box of “KJR Address”. b Select a wire…
-
Fig. 4-53
②“Error record”――Save the system operation error record, includes: Record time, Error prevented cord, Sub-module address and KJR address (see Fig. 4-54); click the “Record time” ”Protection code” ”Sub-module address” ”KJR address”can proceed ordering(see Fig 4-55) ;“Clear all record”in the Menu (See…
-
Fig.4-56
4)“Communication parameter” includes:“Serial port set” and “History set” See Fig.4-57 Fig.4-57 ①Click “Serial port set”, window as Fig. 4-58 will pop up—— modify or select the serial port in computer. The available serial port source is captured by software, and saved at the optional list for user…
-
Fig.4-60
②Click “History set”, an interface as Fig. 4-61 displays ―――to modify or select the history error saving duration. Fig.4-61 5)“Help” includes:“User guidance” and “About”. See Fig. 4-62 Fig.4-62 ①Owner’s manual——Software application manual, i.e. this manual. ②About——some relevant software information…
-
Fig.4-63
Specific operating status could be distinguished by colors of the treeview. See follows table for detail color information: No. Color Status Equipment OFF-LINE CONTROLLER( ) SUB-MODULE( ) NORMAL CONTROLLER( ) SUB-MODULE( ) ON-LINE ERROR ( SUB-MODULE ) 4-4-2 Right-click the blank space of “AC system…
-
Fig. 4-64
Select the “Expand All” and expand all nodes; select the “Collapse All” and collapse all the nodes. 4-4-3 Right-click a node of “AC system diagram”, then will pops-up the menu display as Fig. 4-65: Fig. 4-65 Select the “Expand This” and expand the selected node; select the “Collapse This” and…
-
Fig.4-66
Fig.4-67 Fig.4-68 Fig.4-69 43 Fig.4-70
-
Provided that the selected wire controller in lock status, the key would display “Unlock
KJR”(see Fig. 4-71), once successful unlock the wire controller, the message box (see Fig. 4-72) would display, then the key displays “Lock KJR”(see Fig. 4-73); If the set failed, message box (Fig. 4-74) would display, tells user that set failed because of timeout. Fig.4-71 Fig.4-72 Fig.4-73…
-
4-6 Query system parameter
Click “Query system parameter”, system will query the operating status (display the sub-module of 0 address’s operation status) and display the operative interface according to the selected wire controller (refrigeration system). In the querying, a message box (see Fig. 4-75) would pop up. Fig.4-75…
-
Fig.4-77
Whereas, “Query overtime” would display (see Fig. 4-78). Provided that the wire controller hasn’t been selected, namely the wire controller address is empty, a message box as Fig 4-79 would pop up. The query performance failed. Fig.4-78 Fig.4-79 46
-
Provided that malfunction occur, the corresponding error code will show in the System Query;
Provided that protection function perform, the corresponding protection code will show in the System Query; if move the mouse arrow to the these codes, a floating window as the follows Fig. 4-80 and 4-81 will appearance to giving the specific error or protection information. Fig.4-80 47
-
Fig.4-81
4-7 Sub-module Query Click the “Query”, system will query the operative status and display the information in the operation interface according to the current selected sub-module. In the querying, a message box (see Fig. 4-82) would pop up: “Query success” (see Fig. 4-83) to note you the query is…
-
Fig.4-82
Fig.4-84 Fig.4-83 Fig.4-86 Fig.4-85 Provided that malfunction occur, the corresponding error code will show in the Sub-module query; Provided that protection function perform, the corresponding protection code will show in the Sub-module query; if move the mouse arrow to the these codes, a floating…
-
4-8 More parameters
Click More Parameters, you could query more data (See Fig.4-89). If the sub-module hasn’t been selected, a message box as Fig. 4-90 would show. You must click a certain sub-module firstly, and then to click the “More parameters” key, more parameter could be queried; a message box (See Fig.4-91) will…
-
Fig.4-91
4-9 System operate set 1)During setting, message boxes as following might display. Click the “System operate set” in the conditioner of without wire controller has been selected, a message box as Fig. 4-92 would show. Fig.4-92 52
-
Click the “System operate set” in the conditioner of although the wire controller has been set, all
options in the System Set are empty (See Fig. 4-93), a message box as Fig. 4-94 would show. Fig.4-94 Fig.4-93 Click the “System operate set” in the conditioner of without Control Mode has been selected, a message box as Fig. 4-95 would show. Click the “System operate set” in the conditioner of…
-
2)Set wire controller separately: Do not tick the “Uniformly Set”. Select the wanted set wire
controller (refrigeration system) from the wire controller address column and select the corresponding set parameters, which include control Mode (Auto), Mode set (cooling/heating/Water pump/turn-off), Setting temperature (Cooling: 5~17℃; Heating:45~50℃ ). After set up all above parameters (See Fig.…
-
Fig.4-101
3)Uniformly set all wire controllers: Tick Uniformly Set as Fig. 4-102, and then select the corresponding parameters, click the System Operate Set, system starts to set up. A message box as Fig. 4-103 will display during the setting. Once successful setting, a message box as Fig. 4-104 will display…
-
4-10 Remark
Remark 1: Mostly 16 sets of SUB-MODULES are allow to connect under a WIRE CONTROLLER; MODULE GROUP directly under connects with a WIRE CONTROLLER; SUB-MODULE under connects with MODULE GROUP. The quantity conversion between MODULE and SUB-MODULE: add a 30KW(P) or a 35KW(P) module equal to add one…
-
2、The window “System Properties” will be popped-up after selecting the “Properties”, and
then select the “Device Manager” in the “Hardware” Fig.4-108 3 The window “Device Manager” will be showed up after clicking the “Device Manager” Fig.4-109 58
-
4、Click the icon “
” in front of the “Ports(COM&LPT)”, then can view the port names by the format as “COM”+number, these names are the usable serial port names for the computer (Note: the computer may has more serial ports or no ports) Fig.4-110 5 APPENDIX 1. Query list for malfunction status 59 E0 Water flow…
-
2. Query list for protection status
P0 System A High-pressure protection or air exhaust temperature protection P1 System A Low-pressure protection P2 System B High-pressure protection or air exhaust temperature protection P3 System B Low-pressure protection P4 System A current protection P5 System B current protection P6 System A…