Third Generation Network System
-
2. 3. As with the fault report of indoor units, the fault report of outdoor units shows the fault and protection information generated by all the outdoor units during a certain period. The report only outputs the fault and protection information generated by all the outdoor units during a maximum of…
-
Operating Data of Outdoor Unit Fig.5-4 1. As with the operating data report of indoor unit, the operating data report of outdoor unit shows the operating data of an outdoor unit generated during a certain period. 2.The report only outputs the operating data generated by one outdoor unit during a…
-
b
When the system is running in cooling mode (basic electricity consumption) Cooling indoor unit: Its electricity consumption includes the amortized electricity consumption of outdoor units and the electricity consumed by the indoor unit fan and the electric heater. Air supply indoor unit: Its…
-
2 System Configuration
2-1 System diagram 5.Electricity Expense Distribution and Reports V. Electricity Expense Distribution and Reports 5.1 Principles of Electricity Expense Distribution 1. 2. 3. a. b. c. d. Fig.2-1 1) 2) 3) 4) 2 The system can connect with 16 indoor central controllers and 16 outdoor central controllers…
-
3-1 Devices Required and Their Specifications
a b c Fig.4-16 A. List of all the floors. The drop-down list includes all the set floors. After you select a floor from the drop-down list, the plan of the floor is displayed in the right part. B. It is used to set an indoor unit. Select an indoor unit in the plan in the right part, and then set…
-
No
PC 4. System Operation Equipment specification Recommendation CPU: 3.0G or more frequency. Hard disk: 40G or more. Memory: 2G or more Communication port: two or more R-232 ports, and three or more USB ports. Operation system: WIN2000 or WIN XP. Printer: Ordinary laser printer or ink jet printer is…
-
Fig.4-13
1. b displays the status of the outdoor unit. If an item is not available to the outdoor unit, the corresponding box is blank. The information displayed is updated and synchronized with the information in the database. 2. C displays the status identifier of the outdoor unit. It identifiers the…
-
(2) The indoor central controller can communicate with the computer
through an RS485RS232 converter. Each computer can connect with 16 indoor central controllers and 16 outdoor central controllers. The computer can perform operations such as centralized control, management and status query on the indoor central controllers, outdoor central controllers, indoor units…
-
becomes red after being selected), and then double-click it. Then
the schedule management setting interface appears, showing the detailed settings of the task. 4-6 Interface of Indoor Unit a b c d Fig.4-10 1. 2. A displays the status of the selected indoor unit. After you click Query, the status of the current indoor unit is displayed in a. In this display area…
-
System Installation 4. System Operation 4-1 Installation and Setting 1. Install and run Firebird (see 4.2.1. Installing Firebird). 2. Install Firebird ODBC (see 4.2.2. Installing Firebird ODBC). 3. Install network monitoring system (see 4.2.3. Installing the Network Monitoring System). 4. Set…
-
2. 3. 4. 5. 51 Unified setting: It is used to set all the indoor units in the system, including mode setting, locking/locking, and mode locking/unlocking. a is used to set the indoor units. The remote control setting area is used to send locking command to all the indoor units so that they cannot…
-
6. On the interface as shown below, select the options as shown be
low, and then click Next 4-3 Interface of Outdoor Central Controller c d f a b e Fig.4-3 Fig.4-7 7. On the interface as shown below, click Next. Fig.4-8 8. On the interface as shown below, select the options as shown below, and then click Next. 1. a displays the relationship between outdoor central…
-
lock or unlock the controller. After the locking command is set, the controller is locked, the locking icon is displayed, and the indoor units under the controller cannot be operated. After the unlocking command is sent to the locked controller, the locking icon disappears, and the indoor units…
-
IV. System Operations
12. On the interface as shown below, click Finish. 4-1 Main Interface Fig 4-1 1. Fig.4-13 13. Open the Control Panel, and then double-click Firebird 2.0 Each icon on the main interface represents one operation interface in the system. 2. To change logo, simply replace LargelLogo.BMP and Small…
-
15. If the interface as shown below appears, it indicates that the Firebird database is running. New Floor Setting: Click Basic Data->New Floor. A B C A. B. C. D. E. F. D E F Fig 3-8 Tree-like list of the floors. Parameters of the selected floor, including its name and description. Click Browse to…
-
On the interface as shown below, click Next. Fig.4-19 4. On the interface as shown below, click Browse, select the destination folder, and then click Next. 3-6 Group Parameter Setting: Click Basic Data->Group Parameter Setting. A B C Fig 3-6 A. On the group parameter setting interface, all the…
-
B
6. On the interface as shown below, select the start menu folder, and then click Next. Set the parameters of indoor units: The address of an indoor unit is in the range of 0-63. Each indoor unit under a controller shall have a unique address. The unit name entered in the Unit Group Name box shall be…
-
3-4 When the interface as shown below appears, click Next. Outdoor Unit Setting: Click Basic Data->Outdoor Unit Setting. A B Fig.4-26 10. On the interface as shown below, click Finish. Fig.4-27 4-2-3 Installing the Network Monitoring System 1) Run SetupEx.exe in the installation CD to display the…
-
2) Indoor central controller Setting: Click Basic Data>Controller Setting. On the interface as shown below, click I accept the agreement, and then click Next. A B C Fig 3-2 A. B. Click Indoor to set indoor central controller. Set the parameters of the indoor central controller: Set the address of…
-
Click Next to display the interface as shown below. Select the start menu folder, and then click Making shortcut available to all users, and then click Next. III. System Building The procedure for building the system is as follows: l Setting indoor and outdoor central controllers. l Setting outdoor…
-
4-2-4 Setting Firebird ODBC 1. Open the Control Panel, and the double-click Administrative Tools. Ethernet controller port setting: Click Interface Set->AC TCP/IP Set. This port setting is used for the communication between the software system and the Ethernet controllers. It involves IP port…
-
Controller RS485 port setting: Click Interface Set->AC RS232 Set. Select the number of the serial port that is connected to the RS485 controller, and set BaudRate, DataBit, StopBit and Check as shown below. Fig.4-27 Fig 2-16 Fig.4-39 4. a: 6. On the interface that appears, enter the parameters as…
-
a. b. c. d. 5. Database setting: Click Database->Database Set. DSN: Enter NET_AC UID: Enter sysdba . PWD: Enter masterkey . Data File: The path of the database file. By default, the database file NETAC.FDB is located in the Dbase folder in the installation directory of the monitoring system. The…
-
On the interface as shown below, click Install the Software Automatically (Recommended), and then click Next. 3) The system automatically searches for the driver, as shown below. 2.3 Server Parameter Setting 1. Showing the server program Double-click on the taskbar to display the server interface…
-
4-2-6. Setting the OS I. Setting the auto restart function of Windows 2000 1. Enabling auto restart After the auto restart function is enabled, the computer will automatically restart after being powered on in case of power failure. (1) Click Start ->Setting/Control Panel, and then double-click…
-
2. Auto login
After Windows 2000 starts, you need to press Ctrl-Alt-Del to log into it. Our intelligent management system needs to be started after all the programs (including the management system) are closed. Therefore, the auto restart function is required. (1) Open the Control Panel, and then double-click…
-
3. Auto restart To enable our intelligent management system to automatically start after the startup of Windows 2000, do as follows: (1) Open the following folder: C:\documents and settings\all users\startmenu\programs\startup (2) Right-click, and then select New->Shortcut. Database setting: Click…
-
II. Setting the auto restart function of Windows XP
1. Enabling auto restart After the auto restart function is enabled, the computer will automatically restart after being aborted. (1) Click Start->Control Panel, and then double-click System. (2) Click the Advanced tab, and then click Settings in the Startup and Recovery area. 3. Classification of…
-
II. System Setting
2.1 Starting System and User Login Click Start->All Programs->NetACControlFBD->ACServer to start the server. When appears on the taskbar, it indicates that the server is running. Double-click on the desktop, or click Start->All Programs->NetACControlFBD->NetACControl to display the login interface…
-
I. System Overview
I. System Overview (4) Enter the current password, and then click Remove. The system consists of foreground interface, background database and background communication components. Through the foreground interface, the user can operate the system and query data. The background communication…
-
(4) Click Next. On the interface that appears, click Finish
Fig.4-60 (5) Restart the computer, and then check whether our intelligent management system automatically starts. 29
-
Third generation
Network System Operation Manual Thank you for your confidence and choosing the Third Generation Network System. To ensure correct use of the product, please read this manual and the indoor unit operation manual carefully before using the unit. For convenience of future reference, keep this manual…