Инструкция на Мультизональные VRF системы ARUN60LS2, ARUN50LS2, ARUN40LS2
Инструкция по монтажу
Загружаем документ…
Текст инструкции
-
© website Вир://у\лх Дезегусе.сопа
HSIMONA murs WV. System Outdoor Unit [R410A INSTALLATION MANUAL MODELS: ARUN Series ARUV Series (30, 380~415V, 50Н2/ 30, 380V, 60Hz) ONVIIVLI IMPORTANT * Please read this installation manual completely before installing the product. * Installation work must be performed in accordance with the…
-
To prevent injury to the user or other people and property damage, the following instructions must
be followed. № Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications. Г AWARNING This symbol indicates the possibility of death or serious injury. ) Ц ЛАСАЧТЮМ This symbol indicates the possibility of injury or damage to…
-
When installing and moving the air
conditioner to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit. ¢ Ifa different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged. Ventilate before operating air…
-
С №
{ ACAUTION ) Ш Installation Always check for gas (refrigerant) leakage after installation or repair of product. * Low refrigerant levels may cause failure of product. Keep level even when installing the product. * То avoid vibration or water leakage. Use power cables of sufficient current carrying…
-
Install and insulate the drain hose to ensure that water is drained away properly based on the
installation manual. * А bad connection may cause water leakage. Be very careful about product transportation. * Only one person should not carry the product if it weighs more than 20 kg. ¢ Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is…
-
Installation Process
[| Installation Process ( Determination of division work } Indicate clearly who is to be responsible for switch settings Make relationship between outdoor, indoor, remote controller, and option connections clear. ( Preparation of contract drawings }- (Prepare control circuit diagram) ( Sleeve and…
-
Outdoor Units Information
ЛА слотом Ratio of the connectable Indoor Units to the Outdoor: Within 50 ~ 130% Ratio of running Indoor Units to the Outdoor: Within 10 ~ 100% A combination operation over 100% cause to reduce each indoor unit capacity. Power Supply : Outdoor Unit (30, 380-415 50Hz/ 30, 380V, 60Н2] System(HP) Model…
-
Before Installation
[| Before Installation Environment-friendly Alternative * The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also considered during…
-
Select the Best Location
| Select the Best Location 1. Select space for installing outdoor unit, which will meet the following conditions: * No direct thermal radiation from other heat sources * No possibility of annoying neighbors by noise from unit * No exposition to strong wind * With strength which bears weight of unit…
-
* The following values are the least space for installation
If any service area is needed for service according to field circumstance, obtain enough service space. * The unit of values is mm. Ш Incase of obstacles on the suction side 1. Stand alone installation (Unit:mm] 2. Collective installation (Unit:mm] Installation Manual 11
-
1. Stand alone installation 1000 or more [Unit:mm] Ш In case of obstacles on the suction and the discharge side > Obstacle height of discharge side is higher than the unit 1. Stand alone installation L>H 1900 or more (Unit:mm] 12 sun. Outdoor Unit
-
2. Collective installation
L>H more > Obstacle height of discharge side is lower than the unit 1. Stand alone installation Installation Manual 13
-
Collective / Continuous In
Space required for collective installation and continuous installation: When installing several units, leave space between each block as shown below considering passage for air and people. 1. One row of stand alone installation a Pi SILI LSS и ‚ати жи ат Li PLL LLL LS ANNAN ААА ge (Unit:mm] 2. Rows…
-
Foundation for Installatio
* Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation. * Fix the unit securely by means of the foundation bolts. (Prepare 4sets of M12 foundation bolts, nuts and washers each which are available on the market.) *…
-
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure. 1) Cut the pipes and the cable. № Use the accessory piping kit or the pipes purchased locally. № Measure the distance between the indoor and the outdoor unit. Ш Cut the pipes a little…
-
(| FLARE SHAPE and FLARE NUT TIGHTENING TORQUE}
Precautions when connecting pipes * See the following table for flare part machining dimensions. «When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first. (Use ester oil or ether oil.) * See the following table for…
-
№ Connecting the pipes to the outdoor unit
1. Liquid pipe * Align the center of the pipings and sufficiently tighten the flare nut with fingers. * Finally, tighten the flare nut with torque wrench until the wrench clicks. - When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.…
-
Cautions for Handling Service Valve
* The service valves are closed at shipment from the factory A CAUTION Make sure to keep the valve open during operation The names of parts of the service valve are shown in the figure. 1. Service point 2. Shut-off Valve 3. Filed piping connection 4. Valve cover * since the side boards may be…
-
1. Use the following materials for refrigerant piping
* Material: Seamless phosphorous deoxidized copper pipe * Wall thickness : Comply with the relevant local and national regulations for the designed pressure 3.8МРа. We recommend the following table as the minimum wall thickness. Outer diameter [mm] 6.35 | 9.52 | 12.7] 15.88 | 19.05 | 22.2) 25.4)…
-
| ° | | Физ > им Val 1 Refrigerant piping 4 Taping 2 Pipe to be brazed 5 Valve 3 Nitrogen 6 Pressure-reducing valve A warnine When installing and moving the air conditioner to another site, be sure to make recharge refrigerant after perfect evacuation. - If a different refrigerant or air is mixed…
-
Outdoor unit Gas pipe }+—Liquid pipe Branching Main pipe > ® { J ® | ® ® ® | | ] ] Branching Indoor unit pipe © ®@ = SS Вл al, “oly No. Piping parts Name Selection of pipe size Size of main pipe Outdoor untt Outdoor unit capacity type trent dee т Ф | | Main pipe 4 HP 9.52(3/8) | 015.88(5/8) ist…
-
Allowable Length/Height Diff
-
Ш Header Method
-
Example : 5 Indoor Units connected ® & : Outdoor Unit (В : 1st branch (Y branch) © : У branch р © (B : Indoor Unit Эс © : Header ®7] © © : Sealed piping Е ol _ g B = L150m 140m Е owl ° : г 2 © or Branch pipe can not be used after header > Refrigerant pipe diameter from branch to branch (B,C)…
-
The Amount of Refrigeran
1. Normal condition The calculation of the additional charge should take into account the length of pipe. ® Product Charge(kg) Acdiionel charge (ka) Example : 5 НР ional charge Re, — Total liquid pipe (m) и la L3 Additional reingerant charge a b ы 3 x amount per liquid pipe 1m {Table 1) L1 |…
-
AXCAUTION
Ка negative result is obtained from the calculation, no refrigerant needs to be added. A wannina Regulation for refrigerant leakage : the amount of refrigerant leakage should satisfy the following equation for human safety. Total amount of refrigerant in the system ka / mm? Volume of the room at…
-
Distribution Method
1. Line Distribution 1A Main pipe Ostibuton 2nd Mainpipe Oistroution 2. Vertical Distribution Ensure that the branch pipes are attached vertically. 28 munrr¥. Outdoor Unit
-
Branch Pipe Fitting
@ Y branch ия © @® To Outdoor Unit ® Cote I Crp (В То Branch Piping or Indoor Unit * Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.) Horizontal . Facing downwards m = G) = wn <= A A Viewed from point A in direction of arrow И Within + 3° Within + 3° и…
-
*When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connection then cap pipes should be fitted to the surplus branches. Pinched pipe * Fit branch pipe lie in a horizontal plane a View from point B in the direction of the arrow *…
-
Selection of Y Branch and Header
-
2. Header
[unit:mm] Models Gas pipe Liquid pipe 1.0 0127 LD 06.35 4 branch 10919.05 100127 ARBLO54 are 0.0 019.05 1.0 012.7 00012710 09.52 1.0 015.88 1.0 0127 1.0 015.88 100127 1.0 915.88 7 branch 10.0127 1.0 019.05 ARBLO57 aie 0091905 | 100127 000127 100% 1.0 015.88 ‚Обет 100852 LD 015.88 129127 100635…
-
Leak Test and Vacuum Dr
1. Leak test Leak test should be made by pressurizing nitrogen gas to 3.8 MPa(38.7kgt/cm’). If the pressure does not drop for 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method, refer to the following figure. (Make a test with the service…
-
2. Vacuum
Vacuum drying should be made from the service port provided on the outdoor unit's service valve to the vacuum pump commonly used for liquid pipe, gas pipe. Vaccum of the pipe and the indoor units should be made from the port of the outdoor unit's service valve with the service valve closed. * Never…
-
3. Refrigerant charging
Follow following procedure to charge the refrigerant. 1. Open all service valves 2. Run the unit with cooling mode 3. Charging the refrigerant to gas service valve during operation. п = ra) = м <= Charging during cooling operation Refrigerant cylinder A caution Never charge the refrigerant with…
-
Thermal Insulation of Вей
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insulation work is…
-
1. Caution
1) Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company. Awarnina Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with…
-
Outdoor Unit Outdoor Unit
Indoor Indoor Indoor Indoor Unit Unit Unit Unt Remote Remote Remote Remote comirot control contol control Outdoor Unit Outdoor Unit 7 Indoor indoor fndoor Indoor Unit Unit Unit Unt Remot Remote Remote carne | ora’ control control 2-Core Shield Cable Multi-Core Cable ША слотом * This product have…
-
2. Transmission and Power Lines
1) Transmission cable * Types : shielding wire CVVS or CPEVS * Diameter : over 1.25mm* * Insulation material : PVC * Maximum allowable temperature: 60°C. * Maximum allowable line length: 300m 2) Remote control cable п = ra) = м <= * Types : 3-core cable 3) Simple central control cable * Types…
-
Wiring of Main Power Supply ana
Outdoor unit (30, 380~415V, 50Hz/ 30, 380V, 60Hz), Indoor unit (10, 220V, 50Hz/60Hz) 1. Separate power supply lines for the indoor units from outdoor unit. 2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections. 3.…
-
@ Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block. Power wire Round pressure terminal Ap When none are available, follow the instructions below. * Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)…
-
Example Connection of Transmis
1. 50Hz @ Example Connection of Transmission Cable Ш 1 Outdoor Unit - 10, 220~240V settle Single Phase 3 wire(L.N,GND} tte Transmission line (3 line}: Wired remote control жд Single Phase af power supply fino(L. М) Single Phase 3 wire (ouch beet ais, --#--- Transmission line (2 shield line): Between…
-
ЖА 3 Phase 4 Wires Power line(R, $, T,N) ды Transirission line (3 line}: Wired remote control s=fiex Single Phase of power supply fine(L, №) Power supply swatch ~-4# Transmission line (2 shield line}: Between indoor Unit and Outdoor Unit (Switch fuse : ELCB) 3 Phase 4 Wires Power supply ОН?…
-
Electrical
Wiring 2. 60HZ Ш 1 Outdoor Unit - 19, 220V stile 3 Phase 4 wire (R,S,T.N} =item Transmission line (3 line): Wired remote control smd Single Phase of power supply line(L, М} Single Phase 3 wire (Switch fuse : ELCB) (L,NGND) Power supply эм ~-H- Transmission line (2 shield line): Between Indoor Unit…
-
Wide 3 Phase 4 Wires Power line(R, $, Т, №} fff Transmission line (3 line): Wired remote control vie Single Phase of power supply line(L, №} Power supply switch (Switch fuse : ELCB) --##-: Transmission line (2 shield line): Between Indoor Unit and Outdoor Unit 3 Phase 4 Wires Power supply 60Hz 380V…
-
DIP Switch Setting
Ш Location of setting Switch . g Main PCB SwoiB SW02B (DIPS) (DIP S/W) Auto addressing Swo1V Data confirm Checking according to dip switch setting 1. You can check the setting values of the outdoor unit from the 7 segment LED. The dip switch setting should be changed when the power is OFF. 2. Н…
-
* If you set the Dip switch when power is on, the changed setting will not be applied immediately. The changed setting will be enabled only when Power is reset or by pressing Reset button. 1. Settings of outdoor unit Function SW01B Setting SW02B Setting Remarks Power reset is necessary Standard…
-
Used when snow piles up Snow On the ODU Fan. Fan operates periodically. Forced Accelerates defrost Defrosting operation . . Power reset is necessary Night Silent Fan RPM down Operation on night time Power reset is necessary Pump Down All the refrigerant flows back into the ODU Power reset is…
-
Automatic Addressing
¢ The address of indoor units would be set by auto addressing 1) Wait for 3 minutes after applying power supply swore SwoeB (outdoor unit, indoor unit). OPS) (ПРМ 2) Press the switch of the outdoor unit (SW02V) for 5 seconds. 3) A "88" is indicated on 7-segment LED of the outdoor unit PCB. 4) For…
-
Ф The Procedure of Automatic Addressing
Power On у Waiting 3 minutes у Press SWO2V for 5 sec, у 7-segment LED Bg = 88 у Waiting about 2-7 minutes Auto addressing start } } 225, : * Auto addressing setting end Numbers of indoor unit connection set whose : addressing is completed are indicated for 30seconds * оп 7-segment LED after…
-
Group Number Setting
-
Cool/Heat Selector Installation
Ш Using Cool/Heat Selector Installation and Connection ¢ Connect wires as below figure at the hole of backside of Outdoor Unit Dry Contact. * Insert the wire in the connection hole pushing the "Push" button. * Setting Main PCB Dip SW of Master Outdoor Unit. Outdoor Unit Mode Change Fan Cooling @| |Ж…
-
Checks before Test Run
1 Check to see whether there is any refrigerant leakage, and slack of power or transmission cable. 2 | Confirm that 500 V megger shows 2 MQ or more between power supply terminal block and ground. Do not operate in the case of 2 MQ or less. NOTE: Never carry out megaohm check over terminal control…
-
How to cope with Test Ru
The phenomena from master component failure Component Phenomenon Cause Check method and Trouble shooting Not operating Motor insulation broken | Check resistance between terminals and chassis Strainer clogged Change strainer Compressor Oil leakage Check oil amount after opening oil port Stop during…
-
Sensor Checking Functio
Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors is right or not. It checks 3 indoor temperature sensors, 9 outdoor temperature sensors, 2 outdoor pressure sensors. It is used for judging sensor abnormality. note 2) 2 G) = Start n у Note Мат РСВ | 1.…
-
Sensor Check Error Code Display
In case error occurs during sensor checking process, error display is as shown below. Following contents are displayed one after the other on the main PCB of master outdoor unit. Indoor sensor error : 319 у Outdoor sensor error : 309 Displaying error content + Displaying error content № Indoor unit…
-
Refrigerant Checking Func
This function charges appropriate amount of refrigerant automatically through cycle operation. This function judges refrigerant leakage and overcharging. Note Main 1. In case air temperature is out of guaranteed п = [2] = Ww = PCB | temperature, refrigerant checking function may end Wait for 3 min.…
-
Night Silent Operation
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load. Max. RPM setting method . ODU DIP switch No.12+14 ON swoiB - ODU Main PCB power reset swoi1s Note 1) - SW01V Setting the Fan Max. RPM swoe2V Setting complete…
-
Self-Diagnosis Function
Error Indicator * This function indicates types of failure in self-diagnosis and occurrence of failure for air condition. * Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table. * If more than two…
-
main PCB of outdoor unit
Display Title Cause of Error 32/14 Outdoor Unit Inverter Compressor | System is turned off by outdoor unit Inverter High Discharge Temperature Compressor High Discharge Temperature 3i4l4 High Pressure of Outdoor Unit System is turned off by excessive increase of high pressure of outdoor unit 351 Low…