Internal Use Only
http://biz.lgservice.com Multi Air Conditioner SVC MANUAL(Exploded View) CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
-
Indoor Unit
AMN H 07 6 L Q A 0 Serial Number Function A : Basic, L : Nano Plasma + Auto Clean(Wall Mounted) C: Plasma(Ceiling Cassette), G: Low Static Motor ART COOL(DELUXE) Type Front Panel Color B : Blue, D : Wood, M : Meta, R : Mirror, W : White Chassis Name Indoor Unit Type L : Wall Mounted , A : ART COOL D…
-
Panel (Cassette, Built in Duct)
-
Indoor Units
Category Wall Mounted Type General General ART COOL Ceiling Concealed Duct Ceiling & Floor SQ SR - - - - - ST - - - AMNH 186LTL0 AMNH 246LTC0 - - SP1 - AMNN 096AP*1 AMNN 126AP*1 - - - - SZ AMNH 076DZ*0 - - - - - - SU - - - - - AMNH 126DU*0 AMNH/C 126TCC0 AMNH/C 126TEC0 - TC AMNH 096DU*0 AMNH/C…
-
To prevent injury to the user or other people and property damage, the following instructions must
be followed. ■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications. WARNING This symbol indicates the possibility of death or serious injury. CAUTION This symbol indicates the possibility of injury or damage to…
-
Do not modify or extend the
power cable. Do not install, remove, or reinstall the unit by yourself (customer). Be cautious when unpacking and installing the product. • There is risk of fire or electric shock. • There is risk of fire, electric shock, explosion, or injury. • Sharp edges could cause injury. Be especially careful…
-
Do not plug or unplug the
power supply plug during operation. Do not touch(operate) the product with wet hands. Do not place a heater or other appliances near the power cable. • There is risk of fire or electric shock. • There is risk of fire or electrical shock. • There is risk of fire and electric shock. Do not allow water…
-
Do not open the inlet grill of the product
during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) When the product is soaked (flooded or submerged), contact an Authorized Service Center. Be cautious that water could not enter the product. • There is risk of physical injury, electric shock, or product failure.…
-
Do not install the product
where the noise or hot air from the outdoor unit could damage the neighborhoods. Use two or more people to lift and transport the product. Do not install the product where it will be exposed to sea wind (salt spray) directly. • It may cause a problem for your neighbors. • Avoid personal injury. • It…
-
on the product. (outdoor units) Always insert the filter securely. Clean the filter every two weeks or more often if necessary. Do not insert hands or other objects through the air inlet or outlet while the product is operated. • There is risk of personal injury and failure of product. • A dirty…
-
Indoor Unit
-
H
D W Installation plate MODEL DIM Unit SZ 7K SU 9K, 12K W mm 900 1030 H mm 272 290 D mm 135 153 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 13 - LGE Internal Use Only
-
4. Duct Type
-
5. CVT Type
-
1,000 (Ceiling opening) 4 16.7 7 1 30.8 931.6 893.4 860 846 328.4 (Hanging bolt) 30.8 430 (Ceiling opening) 390 931.6 893.4 (Hanging bolt) 194.4 390 328.4 50 42.7 37 91.6 97.7 116.3 Ø80 180 430 141.8 91.6 130 Ø55 180 180 1050 694.5 (unit : mm) Number Name Liquid pipe connection Gas pipe connection…
-
600 (Ceiling opening) 521(Hanging bolt) 269 570 Unit size 570 Unit size (Ceiling opening) 39.5 450 (Hanging bolt) 75 39.5 Unit:mm CLOSE OPEN OPEN CLOSE 190.5 120.4 (unit : mm) Number Name Liquid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grill Air…
-
790 (Ceiling opening) 572(Hanging bolt) 109 744 Unit size 744 Unit size (Ceiling opening) 658 (Hanging bolt) 66 109 Unit:mm (unit : mm) Number Name Liquid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grill Air suction grill Copyright ©2009 LG…
-
875 (Ceiling opening) 785 (Hanging bolt) 288 840 Unit size 840 Unit size (Ceiling opening) 45 101.5 672 (Hanging bolt) 101.5 45 950 Unit:mm Fresh Air Inlet 210.5 (unit : mm) Number Name Liquid pipe connection Gas pipe connection Drain pipe connection Power supply connection Air discharge grill Air…
-
Outdoor Unit
-
A8UQ566FA0 806 500(bolt hole) 153 730 700(bolt hole) Air outlet Air inlet 1512 1444 Air inlet 670 Service Panel 100 28 Knockout hole (For the control wiring, the power supply, refrigerant connecting pipe) 220 Knockout hole (For the control wiring, the power supply, refrigerant connecting pipe)…
-
Indoor Unit
Indoor Unit Type Wall Mounted Model Rated Cooling Capacity ★ Rated Heating Capacity ★ Air Circulation H/M/L Setting temperature range Fan motor Output Model No. of Poles Input Running Current Capacitor Fan Type No. Used / Diameter Fan RPM Cooling(H/M/L) Heating(H/M/L) Noise Level(Sound Press,1m)…
-
Indoor Unit
Indoor Unit Type Ceiling Cassette - 1way Model Ceiling Cassette - 4way AMNH(C)096TCC0 AMNH(C)126TCC0 AMNH(C)126TEC0 Rated Cooling Capacity ★ AMNH(C)186TEC0 AMNH(C)246TFC0 AMNH(C)306TFC0 AMNH(C)366TDC0 2267(2638) 9000 2520(2929) Rated Heating Capacity ★ 10000 9(317) Air Circulation H/M/L External…
-
Indoor Unit
Indoor Unit Type Ceiling Concealed Duct Model Rated Cooling Capacity Rated Heating Capacity Air Circulation H/M/L External Static Pressure Setting temperature range Fan motor Output Model No. of Poles Input Running Current Capacitor Fan Type No. Used / Diameter Fan RPM Cooling(H/M/L) Heating(H/M/L)…
-
Outdoor Unit - Multiple piping models
-
Outdoor Unit - Distributor type models
A6UW406FA0 A6UQ406FA0 A7UW486FA0 A7UQ486FA0 A8UW566FA0 A8UQ566FA0 kcal/hr 4032~12095 4032~14515 4032~16934 W 4689~14067 4689~16878 4689~19691 Btu/hr 16,000~48,000 16000~57600 16000~67250 W(kcal/hr) 4838~13356 4838~16027 4848~19051 5627~15533 5627~18636 5627~22152 Btu/hr 19,200~53,000 19200~63600…
-
LG Branch Distributor
Model Connectable Indoor Units Combination(Min~Max.) Btu/h PMBD3640 PMBD3630 PMBD3620 1~4 1~3 1~2 PMBD7230 1~3 7,000~24,000 7,000~24,000 7,000~24,000 7,000~36,000 Casing color - - - - Powre Source Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz ,220~240/220V Ø1 , 50/60Hz…
-
Read completely, then follow step by step
Select the best location of indoor unit 1. Split Type Indoor Unit Front • There should not be any heat source or steam near the unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily…
-
• Do not have any heat or steam near the unit
• Select a place where there are no obstacles in front of the unit. • Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway. • Ensure that the space around the left and right of the unit is more than 20cm. The unit should be installed as high on the wall…
-
6. CVT Type Indoor Unit
• There should not be any heat source or steam near the unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. More than 20cm More than 20cm R More than eye-level • A place where drainage can be easily obtained. • A place…
-
How to fix
1. Room Type Indoor Unit Installation Installation Plate The mounting wall should be strong and solid enough to protect it from the vibration. 1) Mount the installation plate on the wall with four Type "A" screws. (If mounting the unit on the concrete wall, consider using anchor bolts.) • Always…
-
The wall you select should be strong and solid enough
to prevent vibration 1) Open panel front • First,Pull the grille bottom, then remove screws (2 pieces), and close grille bottom again. • The moment of lifting the both lower parts of panel front, you can hear sound this panel came out, In this time panel front is separated • After pull down this…
-
■ Sticking the installation guide map and
fixing Indoor unit 1. Put an Installation Guide Map on the desired surface. 7. Drill the piercing part for connecting pipe as diameter 50mm. (In case of piercing rear surface) INSTALLATION GUIDE MAP Refer to No. 5 on this page when making a hole in the wall. 2. Make a hole with diameter of 6mm and…
-
3). Drill a hole in the wall
The wall you select should be strong and solid enough to prevent vibration • Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side. 1) Mount the installation plate on the wall with four type A…
-
4. Duct Type Indoor Unit
- BH/BG chassis A Install the unit above the ceiling correctly. B CASE 1 C E POSITION OF SUSPENSION BOLT D • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. F (G) (Unit:mm) Dimension A B C D E F (G) H I Capacity 18k, 24k…
-
- BT chassis
A Install the unit above the ceiling correctly. B CASE 1 POSITION OF SUSPENSION BOLT D C E • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. A B C D E F G H 9/12K 18K 1060 1030 • Install the unit leaning to a drainage…
-
C
A - BP chassis Install the unit above the ceiling correctly. G CASE 1 • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. D E H POSITION OF SUSPENSION BOLT (Unit:mm) Capacity F Dimension A B C D E F G H I J K B I 1-3 mm…
-
Piping and Drainage of Indoor Unit
1. Preparation of pipings Pipe cutter 1) Cut the pipes and the cable. • Use the accessory piping kit or the pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • Cut the pipes a little longer than the measured distance. • Cut the cable 1.5m longer than the length…
-
Connection of indoor unit piping
1. Split Type Indoor Unit • Preparing the indoor unit's piping and drain hose for installation through the wall. 3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to…
-
• When extending the drain hose at the indoor unit,
install the drain pipe. For right rear piping 1. Route the indoor tubing and the drain hose to the required piping hole position. Drain pipe Indoor unit drain hose Vinyl tape(narrow) Adhesive 6. Wrap the insulation material around the connecting portion. • Overlap the connection pipe insulation…
-
6) Connecting the pipings to the indoor unit and the
drain hose to drain pipe. 8) Reroute the pipings and the drain hose across the back of the chassis. • Align the center of the pipings and sufficiently tighten the flare nut by hand. Indoor unit tubing Flare nut Pipings • When extending the drain hose at the indoor unit, install the drain pipe.…
-
• When extending the drain hose at the indoor unit,
install the drain pipe. • Preparing the indoor unit's piping and drain hose for installation through the wall. 1) Route the indoor tubing and the drain hose in the direction of rear left or right. Drain pipe 2) Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is…
-
■ Panel Assembly
1. First, Check the side cover assembly exactly, Fix power cord in the bottom groove of cover side left. 2. Assemble connecting lead wire with controller and first fix the upper part of panel front, then match the lower part of panel front Panel Front Connector 3. Drive two screws. Copyright ©2009…
-
NOTE: If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended. Connection of piping Indoor • Preparing the indoor unit's piping and drain hose for installation through the wall. •…
-
5. Wrap the insulation material around the connecting
portion. • Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap. 4. Tape the drain hose and the connecting cable. • Connecting cable Plastic bands Insulation material 5. Indoor unit installation •…
-
7. Wrap the insulation material around the connecting portion
• Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap. 9. Set the pipings and the drain hose to the back of the chassis with the tubing holder. • Hook the edge of tubing holder to tap on chassis and…
-
CAUTION
Installation Information (For left piping) • Good case For left piping. Follow the instruction below. • Press on the upper side of clamp. ( ) • Bad case ■ Following bending type from right to left could cause problem of pipe damage. • Bend the tubing to the left side of chassis. • Bend the tubing to…
-
4. Duct Type Indoor Unit
1) Indoor Unit Installation • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling. Old building • Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set…
-
5. CVT Type Indoor Unit
- VB chassis ■ Before Installing, prepare Installation Plates • 'Installation Plates' are attached at the bottom of indoor unit. Detach them by removing each 3 screws at both sides. • Detach 'Side Plate (R,L)' by removing each 2 screws on both sides. • Pull the upper right and left side of 'Inlet…
-
• Insert the nuts and washer onto the suspension bolts
for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the anchor-nuts firmly. • Secure the Installation plates onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers. Anchor nut 1) Ceiling Nut Washer Suspension bolts Suspension bolts…
-
- VE chassis
The wall you select should be strong and solid enough to prevent vibration Installation Plate 1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a…
-
• Secure the Installation plates onto the Suspension
bolts (adjust level roughly.) using nuts, washers and spring washers. • Engage 2 hooks on the both left and right side of the unit to the lower slot of Installation Plates. Anchor nut Ceiling Nut Suspension bolts • Adjust a level with a level gauge on the direction of left-right, back-forth by…
-
CAUTION: Installation Information
For Declination CAUTION 1. Install declination of the indoor unit is very important for the drain of the convertible type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 7mm. 3. If the Installation Plates are fixed to horizontal line, the indoor unit after…
-
• Secure the unit to the Installation Plates with four M8
bolts and washers. R • Before working, refer to "Connecting pipe and cable to Indoor Unit". • Hook up the Inlet Grille Hook to the cabinet. • Hang the Inlet Hanger to the screw. Inlet hanger R Hook Cabinet Bottom • Fit the projection hooks of the side plates to the 'Side Panel' and the 'Front Panel'…
-
2) Installation on the Wall
• Select and mark the position for fixing bolts and piping hole. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor nut on the wall. 1076 mor e th 260 an 265 • Drill the piping hole on the wall…
-
Install the Indoor unit onto Installation Plate
• Insert 2 hooks on the both left and right side of the unit to the inner slot (wall side) of the Installation Plate. Inner slot • Secure the unit to the Installation Plate with four M8 bolts and washers. R • Before working, refer to "Connecting pipe and cable to Indoor Unit". • Hook up the Inlet…
-
3) Installation on the floor
From the left wall more than 760mm Installation of Mount Bracket. • Select and mark the position for Mount Brackets and the piping hole. • Drill the hole for the anchor nut on the wall. • Drill the piping hole using a ø70 hole-core drill. • Secure the Mount Brackets on the wall with four M4 screws.…
-
6. Ceiling Cassette Type Indoor Unit
- TC chassis 1) Ceiling opening dimensions and hanging bolt location • The dimensions of the paper model for installing are the same as those of the ceiling opening dimensions. Level gauge 328.4 (Hanging bolt) 30.8 931.6 893.4 (Hanging bolt) 860 430 (Ceiling opening) 390 Ceiling 1,000 (Ceiling…
-
2) Indoor Unit Installation
Nut (W3/8 or M10) Spring washer (M10) 103mm Ceiling Hanging bolt (W3/8 or M10) Keep the length of the bolt from the bracket to 40mm Flat washer for M10 (accessory) Ceiling board Flat washer for M10 (accessory) Nut (W3/8 or M10) Air Conditioner body Paper model for installation Adjust the same height…
-
7. Ceiling Cassette Type Indoor Unit
- TE/TF/TD chassis 1) Ceiling opening dimensions and hanging bolt location 600 (Ceiling opening) 521(Hanging bolt) 39.5 450 (Hanging bolt) Ceiling Level gauge 75 570 Unit size 570 Unit size CAUTION 600 (Ceiling opening) 39.5 TE 75 • The dimensions of cardboard for installing are the same as those of…
-
NOTE
• Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure…
-
Remote Controller Installation
• Although the room temperature sensor is in the indoor unit, the remote controller should be installed in such places away from direct sunlight and high humidity. Installation of the remote controller • Select places that are not splashed with water. • Select control position after receiving…
-
REMOTE CONTROL PREPARATION(OPTIONAL)
HOW TO MOUNT ONTO A WALL HOW TO INSERT BATTERIES Remove the battery cover from the remote controller. • Slide the cover according to the arrow direction. Insert the two batteries. • Be sure that the (+) and (-) directions are correct. • Be sure that both batteries are new. Re-attach the cover. •…
-
Connecting Pipings and the cable to Outdoor unit
1. Connecting the pipings to the Outdoor unit 2) Align the center of the pipings and sufficiently tighten the flare nut by hand 1) When piping installation work you must be used the connector. Indoor Units Gas A→B Liquid 18K/24K 30K/36K Ø9.52→Ø12.7 Ø9.52 →Ø15.88 Not available Not available A…
-
CAUTION: If a power plug is not to be used, provide a circuit breaker between
power source and the unit as shown below. Main power source Air Conditioner Circuit Breaker Use a 30A circuit breaker or time delay fuse. CAUTION GN The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H07RN-F…
-
2. Electric characteristics
Unit Model Type Power OFM MCA MOP MSC RLA KW FLA 7.25 13.05 8 6 0.067 0.68 8.00 14.40 8 6 0.067 0.68 9.75 17.55 14 7 0.067 0.68 9.75 17.55 14 7 0.067 0.68 13.50 24.30 23.1/14.0 6.1/7.0 0.041 0.73 13.50 24.30 23.1/14.0 6.1/7.0 0.041 0.73 A4UW306FA0 [FM30AH UE0] 15.25 27.45 26.0/14.0 8.1/7.0 0.041*2…
-
Checking the Drainage and Pipe forming
1. Split Type Indoor Unit 1) Remove the Grille from the cabinet • Set the up-and-down air direction louver to open position(horizontally) by finger pressure. • Remove the securing screws. • To remove the Grille, pull lower the left and right side of the grille toward you (slightly tilted) and lift…
-
3) Drain piping
• The drain hose should point downward for easy drain flow. 1) To remove the front panel from the indoor unit. • Set the air direction louvers up-and-down to the position(horizontally) by hand. • Remove the securing screws that retain the front panel. Pull the lower left and right sides of the…
-
4. Convertible Type Indoor Unit
To remove the front panel from the indoor unit. 1. Set the air direction louvers up-and-down to the position(horizontally) by hand. 2. Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off. Pull the right and the left…
-
5. Duct Type Indoor Unit
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 5mm. Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.…
-
6. CST Type Indoor Unit
• Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is…
-
Maximum Length of Pipe and Extra Charge of Refrigerant Charge
-
2. TPS Inverter Multi - Distributor Type
2.1 The maximum allowable level and piping length Outdoor Unit Installation of the outdoor unit in an upper position A BD Unit L1 Place the BD unit and indoor units within a level distance of 10m from each other. R L2 L3 30m B BD Unit L4 10m L5 Main piping Branch piping L6 • Total main piping length…
-
• A7UW486FA0
-
• A8UW486FA0
-
2.2 Refrigerant charge
The calculation of the additional charge should be taken in account for the length of pipe. A A6UW406FA0 charge = 4100g B Additional charge (g) A = Total Main pipe length - rated length x 50g/m + 7,9,12 k Branch pipe length - rated length x 20g/m + 18,24 k Branch pipe length - rated length x 30g/m A…
-
2.3 Piping connection size
A B Adjust to indoor unit piping size Liquid mm Ø 9.52 Gas mm Ø19.05 BD Unit A A A6UW406FA0 A B B B B B B Y-Branch 2.4 Necessity of a trap Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of…
-
2.5 Y-Branch(Standard accessory)
[unit:mm] Gas Pipe Liquid Pipe Ø19.05 Ø19.05 Ø9.52 Ø9.52 Ø9.52 Ø19.05 Y branch A To Outdoor Unit B A B To BD Unit • Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.) Horizontal plane Facing upwards Within +/- 10° A Viewed from point A in direction of arrow…
-
Test Running
SPLIT, ART cool, ART cool deluxe Type 1. Check that all tubing and wiring have been properly connected. 2. Check that the gas and liquid side service valves are fully open. 1) Prepare remote controller Remove the battery cover by pulling it according to the arrow direction. Insert new batteries…
-
CVT Type
1) Connection of power supply 1. Connect the power supply cord to the independent power supply. • Circuit breaker is required. 2. Prepare the remote control. • Insert two batteries provided. Remove the battery cover from the remote controller. • Slide the cover according to the arrow direction.…
-
5. Branch Distributor
PRECAUTIONS FOR SELECTING THE LOCATION The BD unit is for indoor use. Install in a location such as above a ceiling or behind a wall in accordance with the following conditions: • That the unit is fully supported, and is in a location with little or no vibration. • That the refrigerant pipes for the…
-
Piping length and elevation
(m) No. Length 6 room 7 room 8 room (1) Total main piping length A+B (2) Total branch piping length L1+L2+L3+L4+L5+L6+(L7)+(L8) (3) Max. each branch piping length L1, L2, L3, L4, L5, L6, L7,L8 (4) Total system piping length (Total main) + (Tatal branch) (5) Maxium Level in - out h1 (6) Maxium Level…
-
Installation of The Main Unit
NOTICE : • This unit has two different installation types: (1) Ceiling-suspended type and (2) wall-mounted type. • Choose the proper installation pattern according to the location of installation. • The installation location for printed wiring board can be changed. Follow the procedure specified in…
-
Connection of Piping
• When connecting indoor units, make sure to connect refrigerant pipes and connection wires to the appropriate connection ports maked with matching alphabets. (A, B, C, D) NOTICE : A B C D • Be sure to mark all the local refrigerant piping(liquid pipes, gas pipes, etc.) for each indoor unit…
-
Connection of Wiring
• Connect refrigerant pipes and connection wires to the appropriate ports maked with matching alphabets (A, B and C) on this unit. • Follow the instructions on the wiring nameplate to connect the connection wires of indoor/outdoor units to terminal board numbers.(1, 2 and 3) Always fix each ground…
-
Function of control
1. MAIN UNIT FUNCTION • DISPLAY Operation Indicator • On while in appliance operation, off while in appliance pause • Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on) Sleep Timer Indicator • On while in sleep timer mode, off when sleep timer cancel or appliance…
-
operates with the low or setting speed. When the indoor pipe temp is between 20°C and 27°C, it operates with Super-Low(while in sleep mode, with the medium airflow speed). • While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it operates with the…
-
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on. Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp ➲…
-
■ Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time. ■ Sleep Timer Operation • When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appliance…
-
■ Forced Operation
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions. • When the power is supplied while the slide switch is on the forced operation position, or…
-
Function of Indoor Unit
Split Type Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 seconds at the…
-
Art Cool Type Indoor Unit
Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 sec at the starting. Time Delay Safety…
-
Art Cool Deluxe Type Remote Controller
Operation ON/OFF Operation Mode Selection Cooling Operation Mode.( (Cooling (Heating model only) model only) ) Healthy Dehumidification Operation Mode.( Auto Operation Mode.( ) Heating Operation Mode.( ) ) Fan Speed Selection (Low) (Med) (High) Room, Temperature Checking : (High:39°C Low:11°C)…
-
Duct Type Remote Controller
Operation ON/OFF Operation Mode Selection (Cooling (Heating model only) model only) Cooling Operation Mode ( Heating Operation Mode ( Soft Dry Operation Mode ( Auto Operation Mode ( ) ) ) ) Fan Speed Selection LO (Low) MED (Med) HI (High) Room Temperature Display : High:39°C ↔ LOW:11°C Temperature…
-
CST Type Remote Controller
Operation ON/OFF Operation Mode Selection (Cooling (Heating model only) model only) Cooling Operation Mode ( Heating Operation Mode ( Soft Dry Operation Mode ( Auto Operation Mode ( ) ) ) ) Fan Speed Selection LO (Low) MED (Med) HI (High) JET AUTO Room Temperature Display : High:39°C ↔ LOW:11°C…
-
Convertible Type Remote Control
Operation ON/OFF Operation Mode Selection Cooling Operation Mode.( (Cooling (Heating model only) model only) ) Healthy Dehumidification Operation Mode.( Auto Operation Mode.( ) Heating Operation Mode.( ) ) Fan Speed Selection (Low) (Med) (High) (CHAOS) Heating Down to 16°C Up to 30°C Room…
-
Function of Outdoor Unit
Outdoor Unit Two Comp algorithm • Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion. Operating Frequency • Inverter Frequency varies considering condition such as room temp,outdoor temp, operating room number,Temp gap between room temp and set temp and…
-
Remote Control Operation
The Remote Controller transmits the signals to the system. Signal transmitter START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again. 2 OPERATION MODE SELECTION BUTTON Used to select the operation mode. 3 ROOM TEMPERATURE SETTING BUTTONS Used to…
-
Duct Type Remote Controller
AUTO SWING OPERATION SET TEMP Room Temp Operation unit 03 SUB FUNCTION AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE HI MED LO Time Timer On Off Set no. Time 01 FAN SPEED 1 Program set Signal receiver Timer Cancel Program Week Hour Min Holiday 14 SET/CLR RESET Operation display…
-
CST Type Remote Controller
1Way AUTO SWING OPERATION SET TEMP FAN SPEED Room Temp Time Timer Operation unit On Off Set no. Time 01 03 SUB FUNCTION AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE HI MED LO Heat Pump Model 1 Program set 4Way Timer Cancel Program Week 5 Holiday Min RESET Operation display Displays…
-
1) Two Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. • Position 1: The room temperature is controlled by the thermistor of the main body. • Position 2: The room themperature is controlled by the thermistor of the wired…
-
2) Group Control(Optional Wiring)
• You can use a group control operation after connecting the brown and yellow wire of each air-conditioner. • Remove the resistor "OP 7" in remote controller. • It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to prevent overcurrent. Wiring design…
-
Procedure of RPM change: Ex) External Static pressure is 4mmAq for Model 36K. • To protect the unit, compressor is designed to be off during E.S.P. setting. Push the"On/Off"button. 1 The unit will start. AUTO SWING OPERATION SET TEMP FAN SPEED Room Temp HI MED LO Time Operation unit Set no. Time 01…
-
Duct ESP control table
Chassis Static Pressure(mmAq) Ca(Btu/h) Setting Value CMM CMM CMM CMM CMM CMM CMM CMM Static Pressure(mmAq) 12K Ca(Btu/h) Step(Hi/Med/Lo) Setting Value 10.5 CMM CMM 8.5 CMM 11.5 CMM CMM 8.5 CMM 9K BP 12K Chassis Static Pressure(mmAq) Ca(Btu/h) Step(Hi/Med/Lo) Setting Value 16.5 CMM 14.5 CMM CMM CMM…
-
Simple Central Control
Features • Easy operation button. • Independent operation for 16 indoor units each. • Simultaneous turn ON/OFF for all of indoor units connected. • Easy change operation mode to cooling or heating • Set and clear lock-mode for each indoor unit • Simultaneously set and clear lock-mode for all of…
-
Electrical wiring
■ PICTORIAL VIEW OF THE CONNECTION Outdoor Outdoor unit unit PI485 : PNF-P14A0M MAIN PCB L PI485 MAIN PCB Control Box CN_CENTRAL MAIN PCB N CN_CENTRAL L 10 G A B PI485 CENTRAL CONTROL UNIT VCC GND C D CN OUT • Special purchase: Central control, PI485(PNF-P14A0M) ■ ONE SIMPLE CENTRAL CONTROL…
-
■ 2 OR MORE SIMPLE CENTRAL CONTROL CONNECTION
INDOOR UNIT 1 INDOOR UNIT 2 INDOOR UNIT 3 OUTDOOR MAIN PCB INDOOR UNIT 4 <Group Number 0> INDOOR UNIT 5 INDOOR UNIT 6 GND Vcc BUS B BUS A D C Master CN-POWER GND CN-COM B CN-POWER CN-COM A S2 S1 DIP SWITCH S4 L LED2 GND IC1P + S5 + + S9 + LED9 D LED4 + + S10 + LED14 S14 1. Adhere the PI485…
-
Indoor Unit Address setting Method
1. Press 13(program) and 16(set and clear) key more than 3 second then "Address Setting Mode" starts. 2. Set the address of indoor unit by using "Temperature setting" key. ■ Range of address : 00 ~ FF Using Wired Remocon AUTO SWING OPERATION SET TEMP Room Temp Timer Operation unit 03 SUB FUNCTION HI…
-
Test run method
1. Set the wiring of system and indoor unit. 2. Apply power to the setting. 3. Do auto addressing to the outdoor unit. 4. After addressing, initialize the central controller(Manual initialize: Total on + total off + 16 key). • Cooling: Setting basically(Total On + Total Off + 4 key) • Heating: Total…
-
■ INSTALLATION ORDER
1. Remove upper & lower case. 2. Fixate screw in the holes of the 3. For Dip switch, and Rotary case bottom. 4. For wiring connection, refer page switch setting, refer to the page “How to Install”. 5. Adjust the upper case in accor- “Installation Procedure” 6. Check the operation by supply- dance…
-
■. ROTARY SWITCH SETTING(INSTALLATION FOR 2 OR MORE SIMPLE CENTRAL CONTROL)
The setting of Group Number in the Central Control is done by the rotary switch as shown in the figure below. It is possible to set 0~15 Group(Total 16 Groups). All the numbers on the rotary switch represent the different Group Numbers. By changing the knob we can set rotary switch to the group…
-
Deluxe Central Control
2.1.1 Summary Deluxe Central control is a product available for individual and integrated monitoring and control of maximum 256 of TPS Inverter Multi air conditioner systems. Specially, operation status of the individual air conditioner can be particularly checked. Individual or simultaneous…
-
Major Characteristics
Figure 2) Deluxe Central control 1. Individual/Integrated Operation/Monitoring ■ You can identify operation status of the air conditioner, operation mode, wind quantity, wind direction, locking, temperature setting and error, etc by selecting the installed air conditioner through individual…
-
6. Convenient GUI / Touch Screen
■ Not requires special education for using the Deluxe Central control, conveniently used only by pressing the buttons on the screen, and its function can be understood with intuitive pictogram. Especially schedule setting is done by simply by dragging, different from the existing system requiring to…
-
Figure 3) Deluxe Central control
Table 1) Comparison Between Central control Characteristics Internet Central control PC Central control Deluxe Central control Dedicate PC Non-required Required Non-required Configuration User S/W User S/W, Engine S/W Main Body of Web Pad Deluxe Central control Position of program Download to i-GW…
-
Major Function of Deluxe Central Control
[ System Control ] To check general monitor function of the air con central control system such as selection of group and air conditioner, air conditioner control monitor function etc. PQCSW501A0, PQCSW502A0 [ System Monitor ] To check the ctual time status of all air conditioners. PQCSW501A0…
-
System Configuration
Scenario 1 : In case of not using Internet access function B part A part Product Control System Interface Delux Central Control CNU PI485 PI485 Cross UTP Cable (Cross LAN Cable) RS-485 Cable PI485 PI485 * CNU: Central control Network interface Unit PI485: Product Interface unit for IEEE485…
-
Disassembly of the parts (Indoor unit)
Indoor unit 1. Split Type Indoor unit CAUTION: Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”. To remove the Grille from the Chassis. • Set the up-and-down air discharge louver to open position (horizontally) by finger pressure. • Remove the…
-
• Remove securing screws
• Pull the control box out from the chassis carefully. 3) To remove the Discharge Grille. • Pull the discharge grille out from the chassis carefully. 4) To remove the Evaporator. • Remove screws securing the evaporator and the holder eva. • Unhook the tab on the right inside of the chassis at the…
-
CAUTION: Disconnect the unit from
power supply before making any checks. Be sure the power switch is set to “OFF”. 1. To remove the Grille from the Chassis. - Pull the grille bottom, the remove 2 securing screws. - Lift the both lower parts of panel front. - After pull down this panel a bit, separate connecting wire with product.…
-
3) To remove the Evaporator
- Remove 4 screws securing the evaporator. - Pull the evaporator out from the chassis carefully. 4) Before removing the Turbo Fan. - Remove the securing screws from the chassis. - Pull the pipe cover, top cover and the air guide. Air Guide Top Cover Pipe Cover 5) To remove the Motor. - Remove the…
-
CAUTION: Disconnect the unit from
power supply before making any checks. Be sure the power switch is set to “OFF”. To remove the Grille from the Chassis. • Hold up Inlet Grille Horizentally. • To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward. • To…
-
• Remove securing screws
• Pull the control box out from the chassis carefully. 3) To remove the Discharge Grille. • Unhook the discharge grille and pull the discharge grille out from the chassis carefully. 4) To remove the Evaporator. • Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right…
-
• Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator toward you until the tab is clear of the slot. 5) To remove the Motor Cover • Remove 2 securing screw. • Pull the motor cover out from the chassis carefully. Motor cover 6) To remove the Cross-Flow Fan • Loosen the screw securing the cross-flow fan to…
-
3. CVT Type - VB chassis
Warning : Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”. 1. Remove the air filter. • Pull the inlet grille slightly toward you. • Pull out the air filter. (2 pieces) R Inlet Grille 2. Remove the girlle from chassis • Remove the screws…
-
VE chassis
Warning : Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”. To remove the Grille from the Chassis. • Set the up-and-down air discharge louver to open position (horizontally) by finger pressure. • Remove the securing screws. • To remove the…
-
• Remove securing screws
• Pull the control box out from the chassis carefully. 3. To remove the Discharge Grille. • Unhook the discharge grille and pull the discharge grille out from the chassis carefully. 4. To remove the Evaporator. • Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right…
-
• Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator toward you until the tab is clear of the slot. 5. To remove the Motor Cover • Remove 2 securing screw. • Pull the motor cover out from the chassis carefully. 6. To remove the Cross-Flow Fan • Loosen the screw securing the cross-flow fan to the fan motor…
-
4. Remove air guide upper, crossflow fan and
motor. • Remove the screws of both sides and center securing the upper air-guide. • Remove 2 screws fastening the bracket of door switch. Door Switch R • Remove a bearing assembly by removing a screw and the bearing cover. • Remove 4 screws securing the motor cover. • Loosen the screw securing the…
-
6. Remove the front panel
• Remove the screws of both sides fixing the front panel. • Push the upper side of front panel strongly to pull out the front panel from the inner hook of diffuser frame. • Pull down the front panel carefully not so as to harm the display PCB wires and thermistor wires. 7. Remove the diffuser…
-
9. Remove the vane-upper, vane-lower and step
motor. • Remove 2 screws securing the step motor assembly and pull it out from the vanes carefully. • Unhook the vanes from the vane supporter and remove the upper vane and lower vane by pulling the center of vanes with care. Step Motor Vane Supporter Lower Vane Upper Vane 10. Remove the drain pan…
-
Electronic Control Device
-
2) Art Cool Type
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 135 - LGE Internal Use Only
-
LGE Internal Use Only
-
U
-
C10K
-
IC04D
-
Wiring Diagram
-
5. Duct Type Indoor Unit - BH/BP chassis 6. CVT Type Indoor Unit - VE chassis
-
5. Outdoor Unit
-
5. A2UW146FA0
-
Components Locations
1. Indoor Unit MAIN P.C.B ASM 1) Split Type • DC part • AC part Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 147 - LGE Internal Use Only
-
2) Art Cool Type
TOP VIEW Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes BOTTOM VIEW - 148 - LGE Internal Use Only
-
TOP VIEW
-
4) Duct Type
• High static (BH/BG chassis) • Built in type (BP chassis) Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 150 - LGE Internal Use Only
-
• Low static (BT, BT1 chassis)
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 151 - LGE Internal Use Only
-
5) Casset Type
• 1 way(TC chasis) Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 152 - LGE Internal Use Only
-
58 B Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 153 - LGE Internal Use Only
-
6) Convertible type
• VE chassis AC part TOP VIEW BOTTOM VIEW TOP VIEW BOTTOM VIEW DC part Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 154 - LGE Internal Use Only
-
• VB chassis
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 155 - LGE Internal Use Only
-
2. Display ASSEMBLY
1) Split Type 2) Convertible Type VE chassis TOP VIEW PWB ASM:6871A20390 PCB:6870A90065K BOTTOM VIEW VB chassis 3) Art Cool Type TOP VIEW BOTTOM VIEW Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 156 - LGE Internal Use Only
-
4) Art Cool Deluxe Type
-
3. Outdoor Unit
1) Component side Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 158 - LGE Internal Use Only
-
2) Solder side
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 159 - LGE Internal Use Only
-
3) Central control PCB
1) Top View 2) Bottom View Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 160 - LGE Internal Use Only
-
1) Art Cool Type TOP VIEW BOTTOM VIEW Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 161 - LGE Internal Use Only
-
Refrigerant Flow Cooling Heating Field Piping Liquid Field Piping Gas Room A Room B Room C 3 rooms model Room A Room B Room C 3 rooms model Header LEV-A LEV-B LEV-C Accumulator Low Pressure S/W Th2 Drier Compressor Th1 Reversing Valve Exchanger Heat OUTDOOR UNIT Troubleshooting Guide Troubleshooting…
-
Heating Cooling Refrigerant Flow Field Piping Liquid Field Piping Gas LEV-C LEV-B LEV-A Room C Room B Room A Accumulator LEV-D Header Room D 4 room model Room A Room B Room C Room D Th2 Oil Seperator Th3 Inverter Compressor Drier Low Pressure S/W Constant Compressor Check Valve(2) Th1 Valve(1) Check…
-
Room A Room B Room C Room D Room A Room B Room C Heating Cooling Refrigerant Flow Liquid Field Piping Field Piping Gas Room D Header LEV-A LEV-B LEV-C LEV-D Accumulator Drier Low Pressure S/W Constant Compressor Check Valve(2) Th3 Inverter Compressor Th2 Oil Seperator Th1 Check Valve(1) Heat…
-
OUTDOOR UNIT
Refrigerant Flow Reversing Valve Cooling Heating Check Valve(2 ) Accumulator Th2 Constant Compressor Low Pressure S/W Field Piping Gas(Ø 19.05) Th1 Solenoid Valve(1) Check Valve(1 ) Oil Seperator Heat Exchanger Inverter Compressor Th3 Drier L.E.V. Field Piping Liquid (Ø 9.52) Receiver Notes: • Th…
-
Outdoor Unit Main Liquid Main Gas Piping ( Ø 9.52) Piping ( Ø 19.05) LEV-A D Liquid(Ø9.52) Cooling Heating Refrigerant Flow 5. BD Unit LEV-B B Liquid(Ø9.52 or Ø12.7) LEV-D LEV-C A Liquid(Ø9.52 or Ø12.7) D Liquid(Ø6.35) C Liquid(Ø6.35) B Liquid(Ø6.35) A Liquid(Ø6.35) [Indoor Unit] Copyright ©2009 LG…
-
Field Piping Liquid (Ø 9.52) Field Piping Gas(Ø 19.05) Cooling Heating Refrigerant Flow Th3 Check Valve(2) Drier Low Pressure S/W Constant Compressor 2 Constant Compressor 1 Accumulator Check Valve(3) Receiver Th4 Inverter Compressor Th2 Check Valve(1) Th1 Oil Seperator Reversing Valve Solenoid…
-
Self-diagnosis Function
n Error Indicator • The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble. • Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table. • If more than two troubles occur simultaneously, primarily…
-
Cycle Troubleshooting Guide
Trouble analysis 1. Check temperature difference between intake and discharge air, and operating current. Temp. difference Current : approx. 0°C : less than 80% of rated current All amount of refrigerant leaked out. Check refrigeration cycle. Temp. difference Current : approx. 8°C : less than 80% of…
-
Electronic Parts Troubleshooting Guide
1. A2UW186FA0, A2UW146FA0, A3UW186FA0 g Refer to electronic contorol device drawing & schematic diagram. Trouble 1 The Product doesnʼt operate at all. Turn off the main power and wait until LED on outdoor PCB is off. Turn on the main power again. Does "Beeping" sound is made from the indoor unit? NO…
-
Trouble 2
Product doesn't operate with the remote controller. Turn on main power. While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped. When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is…
-
Trouble 3
The Compressor/Outdoor Fan don't operate Turn on the main power. Operate Cooling Mode by setting the disired temperature of the remote controller is less than one of the Indoor temperature by 1°C at least. When in air circulation mode, compressor/outdoor fan is stopped. Check the sensor for Indoor…
-
Trouble 4
When indoor Fan does not operate. Turn off main power. Check the connection of CN-FAN. Check the Fan Motor. Check the Fuse(AC250V, T2A). Check the related circuit of indoor Fan Motor. • The pin No. 38 of micom and the part for driving SSR.(Q01M) • Check the related pattern. • Check the SSR. - SSR…
-
Trouble 5
When the louver does not operate. • Confirm that the vertical louver is normally geared with the shaft of Stepping Motor. • If the regular torque is detected when rotating the vertical louver with hands ⇒ Normal • Check the connecting condition of CN-U/D or CN0L/R Connector • Check the soldering…
-
General Information
n Error Indicator (Indoor) • The function is to self-diagnosis air conditioner and express the troubles if there is any trouble. • Error mark is displayed on display window of indoor units and wired-remote controller, and LED of outdoor unit control board. • If more than two troubles occur…
-
n Error Indicator (Outdoor)
Outdoor Error Ex) Error 21 (DC Peack) 2 Times 2 Times 2 Times LED01G (RED) 1 Sec. 1 Sec. 1 Time 1 Sec. 1 Time 1 Time LED02G (GREEN) 2 Sec. 2 Sec. LED01G LED02G (Green) (Red) Case of error Outdoor Status 1 time Compressor malfunction,IPM Fault Off 2 times 2 times Current is 14A Off DC Link Low Volt.…
-
n Error Indicator (Outdoor)
Outdoor Error Error code LED01G LED02G (Green) (Red) Contents Case of error Outdoor Status CT Circuit malfunction Off 1 time Open / Short Off 4 times 4 times Open / Short Off Cond. Pipe sensor (open/ short) 4 times 5 times Open / Short Off 46 Suction pipe sensor (open/ short) 4 times 6 times Open /…
-
Display code Title 01 Indoor air sensor • Open / Short • Soldered poorly • Internal circuit error Normal resistor : 10KΩ/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged) 02 Indoor inlet pipe sensor • Open / Short • Soldered poorly • Internal circuit error Normal resistor : 5KΩ/ at…
-
2) Troubleshooting CH03
Display code Title 03 Communication Wired R/C Cause of error Wired R/C 12V S • Open / Short • Wrong connection Indoor Unit GND 12V S • Connection of wire • Main PCB Volt. DC12V • Noise interference CN-REMO GND 12Vdc 12Vdc V V Check the Volt. Check point & Normal condition Check the Volt. Check Point…
-
3) Troubleshooting CH04
Display code Title 04 Drain pump / Float switch Cause of error • Float switch Open. (Normal : short) Check point & Normal condition • The connection of wire(Drain pump/ Float switch) • Drain pump power input. (220V) • Drain tube installation. • Indoor unit installation. (Inclination) CN Float…
-
4) Troubleshooting CH05, CH53
Display code 04 / 53 Title Communication (Indoor ’ Outdoor) Cause of error Check point & Normal condition • Communication poorly • Power input AC 220V. (Outdoor, Indoor) • The connector for transmission is disconnected. • The connecting wires are misconnected. • The GND1,2 is not connected at main…
-
5) Troubleshooting CH21
Display code Title 21 DC Peak Cause of error • Instant over current • Over Rated current • Poor insulation of IPM Comp U U-V V-W W-U W Comp • An instant over current in the U,V,W phase - Comp lock - The abnormal connection of U,V,W • Over load condition - Overcharging of refrigerant - Pipe length. •…
-
6) Troubleshooting CH22
Display code Title Cause of error Check point & Normal condition 21 Max. C/T Over current (14A↑) Malfunction of compressor Blocking of pipe Low voltage input Refrigerant, pipe length, blocked, … 22 C/T Internal circuit Initial current error Malfunction of current detection circuit. (Open / Short)…
-
7) Troubleshooting CH23, CH28
Display code Title 23 DC Link Low voltage. • DC link volt. is 140Vdc↓. • Check the power source. • Check the components. 28 DC Link High voltage • DC link volt. is 420Vdc↑. • Check the power source. • Check the components. Cause of error Check point & Normal condition Check Point 1. Check the power…
-
8) Troubleshooting CH24, CH25
Display code Title 24 Press S/W Open 25 Input voltage Cause of error Check point & Normal condition • Low / High press S/W open. • Check the connection of “CN_Press”. • Check the components. • Abnormal Input voltage (140Vac↓, 300Vac ↑. • Check the power source. • Check the components. TRANS1 50Hz…
-
9) Troubleshooting CH26, CH27
Display code Title 26 DC Compressor Position • Compressor position detect error • Check the connection of comp wire “U,V,W” • Malfunction of compressor • Check the component of “IPM”, detection parts. 27 PSC Fault • Over current at “IGBT” • Check the component of “IGBT” . • Check the components.…
-
10) Troubleshooting CH32, CH33
Display code Title 32 D-pipe (Inverter) temp. high (105°C↑) • Discharge sensor (Inverter) temp. high • Check the discharge pipe sensor for INV. • Check the install condition for over load. • Check the leakage of refrigerant. • Check the SVC V/V open. 33 D-pipe (Constant) temp. high (105°C↑) •…
-
Display code Title 41 D-pipe sensor (Inverter) • Open / Short • Soldered poorly • Internal circuit error • Normal resistor : 200KΩ / at 25°C (Unplugged) • Normal voltage : 4.5Vdc / at 25°C (plugged) 44 Air sensor • Open / Short • Soldered poorly • Internal circuit error • Normal resistor : 10KΩ / at…
-
12) Troubleshooting CH51, CH60
Display code Title 51 Over capacity • Over capacity Combination • Check the indoor unit capacity. • Check the combination table. 60 EEPROM Check sum • Check sum error • Check the PCB ASM P/No. • Check the poor soldering. Cause of error Check point & Normal condition Model Gross max. capacity Max.…
-
13) Troubleshooting CH61, CH62
Display code Title Cause of error 61 Condenser pipe sensor temp. high • Condenser pipe sensor detected high temp.(65°C) • Check the load condition. • Check the sensor of Condenser pipe sensor. 62 Heat sink sensor temp. high • Heat sink sensor detected high temp.(85°C) • Check the fan is locked. •…
-
3-way Valve (Liguid Side)
3-way Valve (Gas Side) Valve cap Valve cap Open position Closed position Open position Closed position Pin Pin To piping connection Service Service port cap port To outdoor unit 1. To piping connection Service Service port cap port To outdoor unit Works Shaft position Service port Shaft position…
-
(1) Pumping down
Indoor unit Liquid side 2-Way valve Close Outdoor unit Gas side 3-Way valve Indoor unit Open Liquid side 2-Way valve Close Gas side 3-Way valve Open manifold gauge Lowhandle (CLOSE) Hi- handle (CLOSE) • Procedure 1. Confirm that both the gas side and liquid side valves are set to the open position.…
-
(2) Evacuation
(All amount of refrigerant leaked) Indoor unit Liquid side Open 2-Way valve Outdoor unit Gas side Open 3-Way valve Indoor unit Liquid side Open 2-Way valve Gas side Open 3-Way valve manifold gauge Vacuum pump Lowhandle (OPEN) Hi- handle (OPEN) • Procedure 1. Confirm that both the liguid side valve…
-
(3) Gas Charging
(After Evacuation) Indoor unit Liquid side 2-Way valve Open Outdoor unit Gas side 3-Way valve Indoor unit Open Liquid side 2-Way valve Open Gas side 3-Way valve Charging cylinder Open manifold gauge Low-handle Check valve (OPEN) Hi- handle (OPEN) • Procedure 1. Connect the gauge to the charging…
-
Indoor Unit
SQ/SR chassis 135316 152313 135314 152302 733010 131410 359011 342800 159830 354210 135316 352115 352116 159901 268712 346810 35211B 263230-2 135516 263230-1 352150 135311 146811 266090 267110 268716 268715 W0CZZ 249951 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and…
-
ST chassis
-
135316 268717 159830 152302 268712 267110 266090 249951 146811 359012 144710-1 268714-1 268714-2 146811 144710-2 146811-2 135500-3 - 197 349600 346810 135311-1 147581 330870 354210 135311-3 146811-3 135500-2 352380 263230-1 135500-1 147581 263230-2 35211B 131410 352150 352116 352115 135515 146811-2…
-
Art Cool Deluxe Type(SU, SZ chassis)
135316 146811 152302 668713-1 146811-1 145200 668713-2 135080-1 135313 135511 263020 135080-2 263230-2 263230-1 733010 267110 359011 159830 342800 266090 352111 131410 346810 352150 249951 352114 352118 W0CZZ 35211B 266090 146811 159901 135311 268714 Copyright ©2009 LG Electronics. Inc. All right…
-
Duct Type - High Static(BH, BG chassis)
359012 237210 346810 359012 336610-1 336610-2 W0CZZ 249951 354210 152302 352111 268714 263230-1 263230-2 552111 263230-3 267110 352118 330860 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 199 - LGE Internal Use Only
-
Duct Type - Low Static (BT, BT1 chassis)
152302 346810 336610 359012-2 W0CZZ 359012-1 267110 354210 249951 263230-1 268714 552111 352118 352111 263230-2 330860 263230-3 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 200 - LGE Internal Use Only
-
Built in Duct type (BP chassis)
137214 267110-2 249951 267110-1 263230-1 263230-2 336610-1 359012 263230-3 268714 137210 158591 346810 359012-1 352118 336610-2 352111 354210 152302 330860 137202 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 201 - LGE Internal Use Only
-
137211 267110-2 268712 267110-1 - 202 152302 146811 135312 152312 140570 330860 352116 263230-1 359011 W1SZ 352115 346810 263230-2 263230-3 266090 266012 354212 158591 159830 W0CZZ 354210 268714 130911 249951 Exploded View Cassette Type - 1 way (TC chassis) LGE Internal Use Only
-
Cassette Type - 4 way(TE chassis)
266090 249951 263230C 263230B 263230A 268711B 159830 35211A 354211 352118 158591 266010 330870 W51620 Applied for 18K Model Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 203 - LGE Internal Use Only
-
Accessory Front Panel
130412 349600 W0CZZ 346811 359012 146811 268712 152312 130911B 352150B 135312-2 135802 130911A 267110A Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes 267110B - 204 - 352150A LGE Internal Use Only
-
Cassette Type - 4 way(TE1 chassis)
266090 249951 263230C 263230B 263230A 249941 W6640 268711B 159830 35211A 354211 352118 158591 266010 330870 W51620 Applied for 18K Model Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 205 - LGE Internal Use Only
-
Accessory Front Panel 130411 349600 346811 359012 146811 268712 140570 152312 130911B W50011 135312-2 135802 130911A 267110B Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 206 - 352150A LGE Internal Use Only
-
Cassette Type - 4 way(TF chassis)
-
550140 W0CZZ 346810 359012 352150B 130911B Option 267110A 267110B 352150A 130911A Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 208 - LGE Internal Use Only
-
Cassette Type - 4 way(TD chassis)
249951 266090 268714 159830 263230-1 263230-2 130411 263230-3 354211 352118-1 552111 352118-2 330870 158591 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 209 - 266012 LGE Internal Use Only
-
W0CZZ 146811 268712 346810 152312 359012 140570 130911-2 130912-1 135313 135802 267110-1 137211 130912-2 130911-1 267110-2 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes 352150-2 - 210 - LGE Internal Use Only
-
Convertible Type (VE chassis)
137211 135310 268712 147581 152302 135313 146811 733010 131410 267110 W0CZZ 330870 266000 135500 346810 263230-1 131410 354212 35211B 268715 352150 268716 263230-2 W4810 266000 359011 249951 342800 330780 159830 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service…
-
552113-1 437210 559010 558511 447910 546810 430410 W0CCZ 658740 554031 - 213 - 552113-2 554160-1 263230-2 561410 552204-1 552204-2 552203-2 552203-1 552203-2 552203-1 561411 263230-1 649950 435511 552116 668711 437212 Exploded View Outdoor Unit A2UQ166FA0 LGE Internal Use Only
-
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes 437211 559010 558511 552113-1 - 214 430411 447910 546810 658740 566000 W0CCZ 554031 552113-2 554160-1 552204-2 552204-1 552116 668711 435511 561410 263230-2 263230-1 552203-2 552203-1 552203-2 552203-1…
-
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes 437211 559010 558511 552113-1 - 215 430411 447910 546810 658740 566000 W0CCZ 554031 552113-2 554160-1 552204-2 552204-1 552116 668711 137213-1 437212 561410 263230-2 263230-1 552203-2 552203-1 552203-2…
-
558511 352113 552116 548490 437210 559010 552115 552204 552111 546810-2 546810-1 Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 217 430410 447910 554160 W0CZZ-2 649950 554031-2 668711 554031-1 552113 W0CZZ-1 137213-1 554161 561410 658740 552203-2…
-
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes - 218 - 237204 435511 559010 435512 546810-2 546810-1 430410 447910 566000 552113 35211A W0CCZ-2 554160 669200 658740 552203-1 554161 552116 554031-1 546810-1 W0CCZ-1 668713 552203-2 554031-2 552115-2…
-