Текст инструкции
-
FUNCIONAMENTO BRUGER- OG MONTERINGSVEJLEDNING INSTALLATIE- EN BEDIENINGSHANDLEIDING HANDBOK FÖR INSTALLATION OCH ANVÄNDING ÅÃ×ÅÉÑÉÄÉÏÅÃÊÁÔÁÓÔÁÓÇÓÊÁÉËÅÉÔÏÕÑÃÉÁÓ ENGLISH SVENSKA Do not perform installation work, without referring to our installation manual. No realice la instalación de este equipo…
-
– Hazards or unsafe practices which COULD result in minor personal injury or
CAUTION product or property damage. PRECAUCIÓN – Riesgos o prácticas poco seguras que PODRÍAN provocar lesiones personales de menor importancia o daños en el producto u otros bienes. VORSICHT – Gefährliche oder unsichere Anwendung, die geringfügigen Personen-, Produkt- oder Sachschaden verursachen…
-
1. SAFETY SUMMARY Ö DANGER: DO NOT pour water into the remote control switch (hereafter called “controller”). This product is equipped with electrical parts. If poured, it will cause a serious electrical shock. Õ WARNING: DO NOT perform installation work and electrical wiring connection by yourself.…
-
INSTALLATION WORK 2.3. INSTALLATION SPACE In case of installing the controllers in vertical line, keep a distance more than 50mm between the controllers vertically. If the distance is insufficient, the front cover of the controller can not open wide enough. More than 50mm 2.4. INSTALLATION…
-
- When Using Switch Box Prepare field-supplied JIS Box (JIS C 8336-1988). JIS Box (JIS C8336 – 1988) ? M4 Screws (Field Supplied) Insert the connector 4. Attach the controller onto the holding bracket. At first, attach the upper side, and then the lower side. ? ? 3. ELECTRICAL WIRING 3.1. STANDARD…
-
ELECTRICAL WIRING 3.2. ELECTRICAL WIRING FOR MULTIPLE UNITS This remote control switch can control sixteen units, as the maximum. In case of this modification, wiring connection and other works shall be performed as indicated in the following procedures. Two Remote Controls can be connected in the…
-
CAUTION: - Use the twist (shield) pair cable (2x0.75mm²) as transmitting wire cable for prevention of the malfunction (The total cable length is max. 200m). When the total cable length is within 30m, other type cable (more than 0.3mm²) can be used. - Keep a distance more than 30cm between the remote…
-
OPERATION 5. OPERATION ºC HITACHI Temperature Indication RUN LED (Red) RUN/STOP Switch Temperature Setting Switch FAN SPEED (Green) FAN SPEED Setting Switch-High FAN SPEED Setting Switch-Medium FAN SPEED Setting Switch-Low To Start To Stop 1. When turning ON the…
-
6. OPTIONAL FUNCTION Normal mode (When unit is not operating) Press the ( ) ( simultaneously Change to the function setting mode Press the ( ) ( ) and ( ) Switch simultaneously for more than 3 seconds. ) and ( )Switch Mode Setting Press the < = Switch and select the operation mode ºC…
-
ALARM INDICATION 7. ALARM INDICATION The Run LED (Red) is flickering. Refrigerant Cycle Number Indoor Unit No. and Alarm Code is indicated as shown in the right figure. Indoor Unit Number ºC (*) Model Code Model $ UTOPIA The other code Not Used DC Inverter Total Number of connected units (A ~ G…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.