Инструкция на Тепловые насосы воздух-вода General Waterstage серии Comfort
Тепловые насосы воздух-вода General Waterstage серии Comfort. Руководство по монтажу.
Загружаем документ…
Текст инструкции
-
Document n° 1350-3 ~ 02/02/2009
FR NL DE EN IT Heat pump air/water split single service Installation and operating manual intended for professionals To be saved for future consultation Fujitsu General (Euro) GmbH Werftstrasse 20 40549 Düsseldorf - Germany Subject to modifications without notice. Non contractual document.
-
Packing list
Heat pump Designation Outside unit Code Model Hydraulic module Model Code AOYA18LALL WSYA 050 DA 023600 AOYA18LALL WSYA 065 DA 023601 AOYA24LALL WSYA 080 DA 023602 AOYA30LBTL WSYA 095 DA 023603 AOYA45LATL AOYA45LBTL WSYA 128 DA 023604 AOY54LJBYL WSYA 155 DA 023605 Optional equipment • 2nd circuit…
-
Contents
Description of the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 4 Package . . . . . . . . . . . . . . . . . . P. 4 Heating power curve . . . . . . . . . . . P. 6 Definitions . . . . . . . . . . . . . . . . . P. 4 Description. . . . . . . . . . . . . . . . P. 11…
-
Configuring the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 46
Configuration 1, 2, 3 or 4: heat pumps with electric back-ups . . P. 47 Electrical connections . . . . . . . . . . P. 47 Parametering the setting . . . . . . . . . P. 47 Hydraulic connections . . . . . . . . . . . P. 47 Special cases . . . . . . . . . . . . . . . P. 47 Electrical wiring diagrams . .…
-
Specifications Designation, Model . . . . . . . . . . . . . . . . . . . . . . . . 050 . . . . 065 . . . . 080 . . . . 095 . . . . 128 . . . . 155 Nominal heating performances (outside temperature/ initial temperature) Heat output +7 °C / +35 °C - Floor heating system . . . . kW . . . . . . 5 . . . .…
-
Heating power curve Values according to standard EN 14511, for which it is necessary to add the power absorbed by the heating circulation pump 5 050 8,00 Floor heating system Very low temperature radiator 7,00 Heat output Power (kW) 6,00 5,00 4,00 3,00 Power absorbed 2,00 1,00 -20 -15 -10 -5 Outside…
-
095 13,00 Heat output Floor heating system 11,00 Very low temperature radiator Power (kW) 9,00 7,00 5,00 Power absorbed 3,00 1,00 -20 -15 -10 0 -5 Outside temperature (°C) 13 128 19,00 Floor heating system 17,00 Very low temperature radiator Heat output 15,00 Power (kW) 13,00 11,00 9,00 7,00 Power…
-
F Outside unit, AIR Model 050, 065, 080 320 Overflow hole (Ø 20) Sight of lower part 300 4 Holes Ø 10) 790 AIR A B S5 050 S6 065 S8 080 1/4” 1/2” 1/4” 5/8” 66 578 A B Front view 189 347 Side view Top view F Outside unit, 650 Model 095 AIR 370 Overflow hole (Ø 20) 4 Holes Ø 10) Sight of lower part…
-
F Outside unit,
650 Model 128, 155 Air 370 Overflow hole (Ø 20) Sight of lower part 900 4 Holes Ø 10) 77 Air 1290 Air 3/8” 5/8” Front view 170 400 Side view Top view Figure 2 - Dimensions in mm 450 F Hydraulic module 1000 1034 235 Heating flow Ø M 26x34 88 Heating return Ø M 26x34 Front view 480 Side view Figure 3…
-
Outdoor sensor QAC34
1 mbar = 10 mmCE = 100 Pa mbar Ω 600 500 43907 kΩ, 25°C 10000 2490 1 1000 100 0 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 338 3 m /h Fig. 4 - Hydraulic pressures and flow rates available -50 -25 °C Condensation sensor Heat pump return sensor Heat pump flow sensor Ω 32500 30000 27500 25000 22500 20000 17500 10…
-
Description F Model 050, 065, F Model 128, F Model Legend 1 - Low-noise, high-output coil 2 - Electric variable speed "inverter" motor 3 - "Inverter" control module 4 - Vacuum start (pump down) and control light 5 - Connection terminal blocks (power and interconnection) 6 - Refrigerant accumulator…
-
Legend 1 - Electric box 2 - Regulator / User interface 3 - Start/stop switch 4 - Heating circulation pump 5 - Initial heating 6 - Gas refrigeration connection 7 - Fluid refrigeration connection 8 - Heating return 9 - Drain valve 10 - Safety valve 11 - Safety thermostat () 12 - Manometer 13 - Manual…
-
Domestic hot water (DHW) operating principle
Two domestic hot water (DHW) temperatures can be parametered: comfort temperature (line 1610 to 60 °C) and reduced temperature (line 1612 to 40 °C). Setting for reduced temperature can be useful to prevent the DHW from switching on too often and for too long during the day. The production of…
-
2 Installation
Regulation installation and maintenance conditions 2.1 2.2.3 Accessories provided The appliance must be installed and the maintained by an approved professional in accordance with the prevailing regulations and code of practice, in particular: The legislation on the handling of refrigerants.…
-
• The outside unit is able to withstand bad weather
but avoid installing in a position where it is likely to be exposed to significant dirt or flowing water (under a defective gutter for example). • Water may drain away from the outside unit when it is operating. You can let this defrosted water run off over a gravel or sand bed or a concrete slab…
-
Heat pump
model Gas and fluid conduits Gas Fluid Minimum length (L) * M a x i m u m M a x i length (L) level difference (D) 1/2" ¼" 5/8" ¼" 5/8" 3/8" PAC Module hydraulique PAC mini L 5m D Unité extérieure * : Without additional charge of R410A : Taking into account the possible additional load of…
-
The appliances are not fireproof and should not
therefore be installed in a potentially explosive atmosphere. Installing the hydraulic module 2.5 2.5.1 Installation precautions 2.5.2 Positioning the hydraulic module • The room in which the appliance operates must comply with the prevailing regulations. - 1, 2, 3 : Remove the front panel (2 screws…
-
Refrigeration connections B F This appliance uses refrigerant R410A. Comply with the legislation for handling refrigeration fluids. Flaring tool L Flare nut 2.6.1 Rules and precautions • After every intervention on the refrigeration circuit and before final connection, take care to replace the plugs…
-
2.6.4 Shaping the refrigeration pipes
2.6.5 Connecting the flared connections The refrigeration pipes must be shaped only on a bending machine or with a bending spring in order to avoid any risk of crushing or breaking them. F The small pipe must always be connected F Warning before the large one. F Take particular care positioning the…
-
- Depending on the case, connect an adapter
(reducer) ¼’’- 3/8’’ or 1/2’’- 5/8’’. (see figure 19). - Remove the plugs from the pipes and the refrigeration connections. - Present the pipe to the flared connector and screw the nut by hand while holding the connector with a wrench until contact. - Comply with the recommended tightening torques.…
-
Filling the installation with gas F This operation is reserved for installers familiar with the legislation for handling refrigeration fluids. Manometer kit (manifold) Low Lo pressure Hi Vacuum meter High pressure F Creating a vacuum with a vacuum pump is essential. Vacuum pump F Never use equipment…
-
Model 050 - Model 065
20 g of R410A per additional meter Length of the connections 10 m 15 m 20 m Additional charge none 100 g 200 g Model 080 20 g of R410A per additional meter Length of the connections 15 m 20 m 25 m 30 m Additional charge none 100 g 200 g 300 g Model 095 40 g of R410A per additional meter Length of…
-
Connecting the heating circuit hydraulically 2.8.1 General The connection must comply with good trade practice according to local building regulations. The heating circulating pump is built into the hydraulic module. Connect the central heating pipes to the hydraulic module, complying with the…
-
Electrical connections Ensure that the general electrical power supply has been cut off before starting any repair work. A : Rigid wires B : Flexible wires Round terminal tightened Loop 25 mm 10 mm 2.9.1 Characteristic of the electrical supply The electrical installation must be conducted in…
-
2.9.3 Overview of all the electrical connections
The wiring diagram for the hydraulic module is shown in detail on page 56. Outdoor sensor Cable 2 x 0.75 mm² Interconnection between the external unit and the hydraulic module Phase, Neutral, Earth, Communication bus Cable 4 x 1.5 mm² Remote control (option) : cable 3 x 0.5 mm² Room thermostat…
-
2.9.5 Electrical connections on outside unit
side Access to the connection terminals • Model 050, 065, 080 - Remove the cap (figure 32). • Model 095, 128, 155 - Remove the front panel - Remove the cap (figure 34). Make the connections in accordance with the diagram(s) Fig. 33. Use cable clamps to prevent the conductors from being disconnected…
-
2.9.6 Electrical connections on the hydraulic
module side Cable clamp Access to the connection terminals - Remove the front panel (2 screws) (fig. 16, p. 17) - Remove the cover of the electric box. - Make the connections in accordance with the diagram(s) Fig. 37. Cables (supply and interconnection) Cable clamp Flexible insulation plate Do not…
-
Hydraulic module
Outside unit Rp ECS Rp 1 Rp 2 HP and electric back-ups 3 way distribution valve (deviation boiler) Boiler room thermostat terminals Interconnection between the outside unit and the hydraulic module Power supply to the electrical back-ups L N Electricity supply 230 V L N L N Connexion to the DHW tank…
-
Outdoor sensor
M B9 Room thermostat circuit 1 CLCL+ 2 CLCL+ 1 EX6 EX5 EX4 External fault Tariffs, day / night, peak times/off-peak times Power shedding or EJP (peak day removal) 2 1 Room thermostat circuit 2 or G+ CLCL+ 5 6 Remote control External component contact* (faults, load shedder, power meter) * If the…
-
CL- terminals on the heat pump control board (fig. 38, p. 29) using the connector supplied. • Installation equipped with a room thermostat and a remote control - Connect the sensor to one of the CL+ or CLterminals on the heat pump control board (fig. 38, p. 29). - Connect the remote control to the…
-
3 Regulation system
User interface and remote control (Option) 3.1 Ref. Function - Definitions 1 Selection of the DHW operating regime (Domestic hot water) - If the installation is fitted with a DHW tank. ON Off 2 Digital display Figure 39 - ON: Production of DHW according to the time program. - Off: Preparing the…
-
Room thermostat (Option) °C Figure 40 - Room thermostat (option) Ref. Function - Definitions 10 Selecting the heating regime - Heating operating according to the heating programme (Summer/winter mode switchover is automatic). - Constant comfort temperature. - Constant reduced temperature. - Stand-by…
-
Heating flow temperature (°C)
Heat pump, Split, single service Heating curve slope 70 1,25 Boiler connexion application 1 Heat pump application only 0,75 0,5 30 0,25 Low temperature radiator Floor heating system -5 -10 -15 -20 External temperature (°C) Heating flow temperature (°C) Figure 41 - Heating curve slope (line 720) 30…
-
3.6.2 Setting parameters
Parametering the setting 3.6 3.6.1 General Only the parameters accessible to levels: U End user I Start-up S Specialist Are described in this document. The access levels are specified in the second column of the table by means of the letters U, I and S. The OEM parameters are not described and…
-
I Function Setting range or display Operation HC2 Jointly with HC1 | Independent Setting increment Basic setting Jointly with HC1 This function enables you to choose whether you wish the room thermostat (as an option) to act on both zones or just a single zone. 46 I Operation HCP 70 S Software…
-
U Function Setting range or display Standard values no, yes Setting increment Basic setting no Time programme 5 / Cooling If the installation is fitted with the cooling kit (Only with the cooling kit option) 600 U Pre-selection (day / week) Mon-Sun Mon-Fri Sat-Sun Monday Tuesday… Mon-Sun 601 U 1st…
-
S Function Setting range or display Setting increment Basic setting Limit of daily heating -10 °C … 10 °C 1 °C -3 °C This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons. Increasing the value delays the switchover to summer regime.…
-
S Function Setting range or display Change of regime None, Protection mode, Reduced, Comfort, Automatic Setting increment Basic setting 1 Protection mode Operating mode at end of concrete slab drying period Cooling circuit 1 901 U Regime off, Automatic off 902 U Comfort ambient temperature setpoint…
-
Function
Setting range or display Setting increment Basic setting 1014 U Frost-free ambient temperature setpoint from 4°C… to reduced temperature 0,5 °C 8 °C 1016 S Maximum comfort setpoint 20…35 °C 1 °C 28 °C 1020 I Heating curve slope 0.1... 4 0,02 0.5 1021 I Off-set of the heating curve -4.50 °C… 4.5 °C…
-
Function
Setting range or display 1200 S Change of regime None, Protection mode, Reduced, Comfort, Automatic Setting increment Basic setting 1 Protection mode 1 60 °C 1 40 °C Operating mode at end of concrete slab drying period DHW setting (domestic hot water) (Only with the DHW kit option) 1610 U Comfort…
-
Function
Setting range or display Setting increment Basic setting Released : HP = ON _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON Locked (Blocked on standby) : HP = off _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON Additional generator…
-
Function
Setting range or display Setting increment Basic setting 6741 S Temperature alarm initiation CC2 ---, 10… 240 min 10 min 6745 S DHW load alarm ---, 1… 48 h 1h 6746 S Temperature alarm initiation Cold 1 ---, 10… 240 min 10 min 6800 S History 1 Time, Date, Error code 6802 S History 2 Time, Date, Error…
-
Function
Setting range or display Setting increment Basic setting Inputs / outputs test 7700 I Relay test No test This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check that the relays are working and that the cabling is correct. Check that each…
-
Function
Setting range or display 8058 I History 5 Time, Date, State code 8060 I History 6 Time, Date, State code 8062 I History 7 Time, Date, State code 8064 I History 8 Time, Date, State code 8066 I History 9 Time, Date, State code 8068 I History 10 Time, Date, State code Setting increment Basic setting…
-
Function
Setting range or display 8740 U Room temperature 1 0 … 50 °C 20 °C Ambient temperature setting 1 4 … 35 °C 20 Flow temperature 1 0 … 140 °C 50 Flow temperature setpoint 1 0 … 140 °C 50 Cooling flow temperature 1 0 … 140 °C 0 Cooling flow temperature setpoint 1 0 … 140 °C 0 8760 I Circulation pump…
-
4 Configuring the installation
F Optional DHW kit F Optional boiler connection kit DHW tank control (with electrical back-up) requires the use of the DHW kit. Warning: The tank must be fitted with an electric back-up, particularly for anti-legionella cycles. Please refer to section (Operating principle, page 13) The connection of…
-
Configuration 1, 2, 3 or 4: heat pumps with electric back-ups F Parameter 5700 Configuration 1 : 1 heating circuit (See Figure page 48) Configuration 2 : 1 heating circuit and DHW tank. (See Figure page 49) Configuration 3 : 2 heating circuits (See Figure page 50) Configuration 4 : 2 heating…
-
Configuration 1
1 heating circuit. F See detailed instructions on Page 47 Overall hydraulic layout SE SA CC R SP Overview of all the electrical connections SE SA 3 CC R SP Legend CC - Heating circulation pump R - Radiators (or fan convectors) 48 SA - Room thermostat (option) SE - Outdoor sensor SP - Heated floor…
-
Configuration 2
1 heating circuit and DHW tank. F See detailed instructions on Page 47 Overall hydraulic layout SE SSa KS SA AE CC R CAR VD M SP Overview of all the electrical connections 4 6 SE 5 8 SSa KS SA 10 3 AE 9 CC R 7 VD M SP Legend CAR - Non-return valve AE - Electric back-up CC - Heating circulation pump…
-
Configuration 3
2 heating circuits F See detailed instructions on Page 47 Overall hydraulic layout Circuit 2 SE SA2 Circuit 1 SA1 R K2c CC2 CAR CC1 M VM1 SDp1 SP CAR Overview of all the electrical connections Circuit 2 SE 5 SA2 3 Circuit 1 SA1 11 R K2c CC2 Legend CAR - Non-return valve CC1 - Heating circulation…
-
Configuration 4
2 heating circuits and DHW tank. F See detailed instructions on Page 47 Overall hydraulic layout Circuit 2 SE SA2 SSa R AE Circuit 1 KS M SA1 R VD CC2 CAR K2c CC1 M VM1 SDp1 SP CAR Overview of all the electrical connections SE 5 Circuit 2 SA2 SSa R 10 3 AE Circuit 1 9 R KS M SA1 VD CC2 11 K2c 1 2…
-
5 Electrical wiring diagrams
Yellow Yellow Reactance Evaporator outlet Red White Black Black Brown Brown Discharge Temperature sensors Compressor Compressor Brown Brown Evaporator centre Black Black Red White Black W7 W8 W9 CN71 CN801 CN73 Red Red Brown Blue Orange Yellow White Black White Yellow Blue White S (S) Black FM CM C…
-
CN64
Red Red HP pressure switch Brown Brown Compressor Blue Blue Outside Black Black Evaporator centre Discharge CN400 CN62 CN61 CN60 Brown Brown 3 3 Black CN500 2 2 Black W306 Blue Blue Yellow Yellow W302 W301 Connector N1 W7 White W12 P Black CN1 + L2 L1 W304 TM102 W303 V W305 TM101 W U Coil Brown…
-
Temperature sensors
Evaporator outlet Discharge Evaporator centre Compressor Black Blue Brown Brown Black Red Outside Compressor Red Red Red R(R) Fuse S(S) C(T) Terminal block Red Brown Red Orange Module filtre actif Black White Yellow Brown Regulation board Yellow White 4-way valve Black Black Black HP pressure switch…
-
Compressor
Compressor casing Black Compressor Blue Brown Outside Black Brown Discharge Evaporator Temperature sensors Filter EMI Connector Red Red White White Black Black HP pressure switch Red Red Black Terminal block Red Brown Red Orange Active filter unit Black White Yellow Brown Regulation board Red Black…
-
CN106
-
6 Troubleshooting
Depending on whether the fault comes from the outside unit or the hydraulic module, the fault may be indicated by the digital display or the diode on the interface cards. 6.1 Faults displayed on hydraulic module The display shows the “Bell” symbol . Press the Info key for more details on the origin…
-
Faults displayed on the outside unit To access the electronic board, you must remove the front (right-hand) facing from the outside unit. Faults are coded by diode flashes. Outside unit, Ref. AOYA18LALL (Model 050 and 065) Outside unit, Ref. AOYA24LALL (Model 080) Diode display Erroneous element 0,1…
-
Outside unit,
Ref. AOYA45LATL, AOYA45LBTL (Model 128) and Ref. AOY54LJBYL (Model 155) Diode display Erroneous element 1 Flash Transmission error, "hydraulic module - outside unit" 2 Flashes Defective “discharge” temperature sensor 3 Flashes Defective “evaporator” temperature sensor 4 Flashes Defective “outside”…
-
7 Instructions for the user
Explain to the user how his installation operates, in particular the functions of the room thermostat and the programmes accessible to him from the user interface. Emphasise that a heated floor has significant inertia and that therefore any adjustments must be made progressively Also explain to the…