EV3 CHILL/HPRU & EVD CHILL/HPRU
Single and dual-circuit controllers for chillers and heat pumps Application manual ver. 3.0b June 2020 | ENGLISH Code 1443DCHE304 page 1 of 110
-
Important
Read this manual carefully before installation and before using the devices and take all the prescribed precautions. Keep this manual with the devices for future consultation. Only use the devices in the ways described in this manual. Do not use these devices as safety devices. Disposal The devices…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 INTRODUCTION EV3 CHILL/HPRU and EVD CHILL/HPRU are controllers for single and dual-circuit air-water and water-water chillers and heat pumps with up to 6 compressors. EV3 CHILL/HPRU is available in the standard 74 x 32…
-
Models available, purchasing codes and technical features 1.1.1 Controllers The table below shows the models available, the purchasing codes and the technical features of the controllers. EV3 CHILL EVD CHILL EV3 HPRU EVD HPRU Dimensions 74 x 32 mm • • 4 DIN modules • • • • • • • • • • • • User…
-
Communications ports
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Remote user interfaces The table below shows the models, purchasing codes and technical features of the EV3K01 remote user interfaces. Dimensions 74 x 32 mm • User interface Two-line LED display + 4 capacitive keys •…
-
The table below shows the models, purchasing codes and technical features of the EVJ LCD remote user interfaces. Dimensions 111.4 x 76.4 mm • • • • • • • • • • • • • • • • • • • • • User interface Static two-line LCD display + 6 capacitive keys Installation Panel-mounted • Wall-mounted Wall mounting…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 I/O expansions The table below shows the models, purchasing codes and technical features of the EVD094 I/O expansions. Format 4 DIN modules • User interface Blind version • Installation Inside an electric box •…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 DESCRIPTION The following paragraphs describe the various devices that can be used to control chiller and heat pump units. 2.1 Description of EV3 CHILL/HPRU The drawing below shows the layout of the EV3 CHILL/HPRU. The…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Description of EVD CHILL/HPRU The diagram below shows the layout of the EVD CHILL/HPRU. The table below describes each part of the EVD CHILL/HPRU. Part 1 Description male Micro-Fit connector for cabling analogue…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Description of EV3K01 The diagram below shows the layout of the EV3K01. The table below describes each part of the EV3 CHILL/HPRU. Part Description 1 display 2 on/off key (subsequently also called the “on/stand-by…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Description of EVJ LCD The diagram below shows the layout of the EVJ LCD. The table below describes each part of the EVJ LCD. Part Description 1 display 2 on/off key (subsequently also called the “on/stand-by key”) 3…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Description of EVD094 The diagram below shows the layout of the EVD094. The table below describes each part of the EVD094. Part 1 Description male Micro-Fit connector for cabling analogue inputs, digital inputs…
-
MEASUREMENTS AND INSTALLATION 3.1 Measurements and installation of EV3 CHILL/HPRU The diagram below shows the measurements of EV3 CHILL/HPRU; measurements are expressed in mm (inches). Installation is on a panel with the snap-in brackets provided. The thickness of the panel must be between 0.8 and…
-
The diagrams below show how to install EVD CHILL/HPRU and EVD094
1 2 To remove EVD CHILL/HPRU and EVD094, first remove any plug-in screw terminal blocks fitted in the lower part, then, using a screwdriver, loosen the DIN rail clip as shown in the diagrams below. 3 4 To re-install EVD CHILL/HPRU and EVD094, first press the DIN rail clip fully in. page 17 of 110
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Measurements and installation of EV3K01 The diagram below shows the measurements of EV3K01; measurements are expressed in mm (inches). Installation is on a panel with the snap-in brackets provided. The thickness of the…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Models to be mounted on the wall The diagram below shows the measurements of the EVJ LCD models for wall installation; measurements are expressed in mm (inches). Installation is on the wall (with fixing screws and…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Models to be mounted on the wall with rear housing in a built-in box The diagram below shows the measurements of the EVJ LCD models for wall installation with rear housing in a built-in box; measurements are expressed…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 ELECTRICAL CONNECTION N.B. - use cables of an adequate section for the current running through them - to reduce any electromagnetic interference, locate the power cables as far away as possible from the signal cables…
-
Part
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Description 12 reference (GND) 13 analogue output AO2 (0-10V/PWM/phase cut) 14 INTRABUS port signal 15 auxiliary power supply output 12 VDC, max. 100 mA 16 reference (GND) 17 EV3 CHILL/HPRU power supply (12 VAC not…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Example of EV3 CHILL/HPRU electrical connection The diagram below shows an example of the EV3 CHILL/HPRU electrical connection with Triac (optional) and RS-485 communication port (optional). N.B. - do not power another…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Description of EVD CHILL/HPRU connectors The diagram below shows the layout of the EVD CHILL/HPRU connectors. The tables below describe the EVD CHILL/HPRU connectors. Connector 1 Part Description 1 electro-mechanical…
-
analogue input IN5 (NTC or dry contact) 13 reference (GND) 14 dry contact digital input IN6 15 ratiometric analogue inputs power supply (5VDC, max 40 mA) 16 auxiliary power supply output 12 VDC, max. 40 mA 17 open collector digital output OC1 (12 V, max. 40 mA) 18 reference (GND) Connector 4 Part…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Example of EVD CHILL/HPRU electrical connection The diagram below shows an example of the EV3 CHILL/HPRU electrical connection. N.B. Protect the power supply with a 1 A-T 250 VAC fuse page 26 of 110
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Description of EV3K01 connectors The diagram below shows the layout of the EV3K01 connectors. The tables below describe the EV3K01 connectors. Connector 1 Part 1 Description EV3K01 power supply (12 VAC/DC not…
-
The diagram below shows an example of the EV3K01 electrical connection. In the example EV3K01 is powered by an EVD CHILL/HPRU controller. N.B. - EV3K01 must not be powered with an EV3 CHILL/HPRU controller - the maximum permitted length for connection cables of the INTRABUS port is 10 m (32.8 ft)…
-
Description of EVJ LCD connectors 3.9.1 Models to be fitted to a panel The diagram below shows the layout of the EVJ LCD connectors for panel installation. The tables below describe the EVJ LCD connectors for panel installation. Connector 1 Part Description 1 INTRABUS port reference (GND) 2 INTRABUS…
-
The diagram below shows an example of the connection of the EVJ LCD models for panel installation. In the example EVJ LCD is powered by an EVD CHILL/HPRU controller. N.B. - EVJ LCD must not be powered with an EV3 CHILL/HPRU controller - the maximum permitted length for connection cables of the…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Example of electrical connection of EVJ LCD models for wall installation The diagram below shows an example of the connection of the EVJ LCD models (with INTRABUS port) for wall installation. In the example EVJ LCD has…
-
The diagram below shows an example of the connection of the EVJ LCD models (with RS-485 INTRABUS port) for wall installation. In the example EVJ LCD has an independent power source. N.B. - do not power another device with the same transformer - the INTRABUS/RS-485 EVIF22ISX serial interface should…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Models to be mounted on the wall with rear housing in a built-in box The diagram below shows the layout of the EVJ LCD models for wall installation with rear housing in a built-in box. The tables below describe the EVJ…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Example of electrical connection of EVJ LCD models for wall installation with rear housing in a built-in box The diagram below shows an example of the connection of the EVJ LCD models for wall installation with rear…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Description of EVD094 connectors The diagram below shows the layout of the EVD094 connectors. The tables below describe the EVD094 connectors. Connector 1 Part Description 1 electro-mechanical relay digital output DO1…
-
analogue input IN5 (NTC or dry contact) 13 reference (GND) 14 dry contact digital input IN6 15 unused 16 auxiliary power supply output 12 VDC, max. 40 mA 17 open collector digital output OC1 (12 V, max. 40 mA) 18 reference (GND) Connector 4 Part Description 1 INTRABUS port reference (GND) 2 INTRABUS…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Termination of the RS-485 line To terminate the RS-485 line of the EV3 CHILL/HPRU, place micro-switch 1 in the ON position. Do not touch micro-switch 2. To terminate the RS-485 line of the EVD CHILL/HPRU, place…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 DESCRIPTION OF USER INTERFACE 4.1 Key functions The table below shows the functions of the keys. EV3 key EVD key EVJ key Name On/stand-by Function - Holding the key down will switch the device on or off and return to…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Icons The icons have four flashing modes: - slow flash: 0.5 Hz - normal flash: 1 Hz - rapid flash: 2.5 Hz - flash every 5 sec (1 sec off, 4 sec on). EV3 CHILL/HPRU and EV3K01 display: EVD CHILL/HPRU display: EVJ LCD…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Signals The table below shows the meaning of the signal icons of EVJ LCD, EV3 CHILL/HPRU, EVD CHILL/HPRU and EV3K01. EVJ LCD EV3 Colour Meaning GREEN Function active CHILL/HPRU , EVD CHILL/HPRU and EV3K01 Depends on…
-
AMBER
Defrosting - ON if defrosting is in progress - OFF if defrosting is not in progress or has finished - FLASHING (2 s) if some timings are in progress for the start of the defrost cycle or if (1 s) dripping is in progress not AMBER present Run - ON if the controller is switched on - OFF if the…
-
5.1 EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 MENU Access levels The ability to view a menu depends on the visibility level (which can be modified from the serial port) assigned to each option; the ability to view a parameter depends on the visibility of the…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 List of menus The following menus are available: Set Gives access to the quick setting of the control setpoints IO ALM Par Shows the I/O values Pro Shows the temperature or pressure values of the inputs configured as…
-
rtc
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Enables the time to be set in devices with a clock YEA: set year Mon: set month dAY: inFo set day of the month UdA: set day of the week Hou: set hour Min: set minutes enables the project data to be displayed in this…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 SELECTING THE OPERATING MODES The controller manages heating and cooling, depending on the configuration of the dedicated parameters. There are three possibilities for selecting the operating mode: - By digital input…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 CONFIGURING A DEVICE The following sections list all the possible configurations of the EV3 CHILL/HPRU and EVD CHILL/HPRU devices. The parameter G02 enables a delay in device start-up to be set: until this time…
-
Chiller
-
Chiller
Heat Chiller Heat default pump visibility pump value default default visibility value value default Min Max 0 1 UM Description value G19 0 0 M H Type of ventilation 0: Independent 1: Unique G20 0 0 M M 0 1 Enable expansion 0: Disabled 1: Enabled G21 0 1 H M 0 1 Enable system heating elements for…
-
таблицы и схемы — в просмотре
-
Chiller
-
таблицы и схемы — в просмотре
-
Chiller
-
Chiller
Heat Chiller Heat default pump visibility pump value default default visibility value value default Min Max -22 22 UM Description value I59 0 0 M M TK2 digital output function output function output function configuration I60 0 0 M M -22 22 AO1 digital configuration I61 0 0 M M -22 22 AO2 digital…
-
таблицы и схемы — в просмотре
-
Chiller
-
таблицы и схемы — в просмотре
-
Chiller
-
таблицы и схемы — в просмотре
-
Chiller
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Configuring inputs All the inputs can be configured by entering an appropriate value in the parameters I06-I25. When a value below 100 is set, the input is configured as a digital input, when the value is above 100, it…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 25 Thermostat (step 1) 26 Thermostat (step 2) 27 Thermostat (step 3) 28 Thermostat (step 4) 29 Thermostat (step 5) 30 Thermostat (step 6) 100 Input water probe 101 Output water probe 102 Condensing probe circuit 1 103…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Configuring analogue outputs There are 2 analogue outputs, AO1 and AO2, and two more in the expansion. The parameters I48 and I49 (I50 and I51 for the expansion) determine the type of output: 0-10 V, phase cut, PWM…
-
The conversion table used is as follows
50 Hz 60 Hz Out min Out max num tick Talfa Veff Vperc Out min Out max num tick Talfa Veff Vperc [%] [%] 500 us [V] [%] [%] [%] 500 us [ms] [V] [%] 0 19 Always off 0 19 Always off 8.0 6.5 7.5 6.0 7.0 5.5 6.5 5.0 6.0 4.5 5.5 4.0 5.0 3.5 4.5 3.0 4.0 Always on 3.5 Always on 7.3.1.3 0-10 V [ms] The…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Configuring AO function Parameters I70-73 determine the function of the analogue outputs in accordance with the following table: 7.4 Value of parameters I70-I73 Meaning 0 Disabled 1 System pump 2 Compressor circuit 1 3…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Value of parameters I54-I69 Meaning 10 Solenoid valve circuit 2 11 Defrosting 12 Fans circuit 1 (step 1) 13 Fans circuit 2 (step 2) 14 Fans circuit 1 (step 3) / Fans circuit 2 (step 1) 15 Fans circuit 1 (step 4) / Fans…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 SERIAL PORTS Controllers EV3 CHILL/HPRU and EVD CHILL/HPRU have the following serial ports: - INTRABUS baud rate 19,200, even, 1 stop bit proprietary communications protocol INTRABUS node 1 (MASTER) - RS-485 baud rate…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 CONTROL FUNCTIONS 9.1 Initial information The sun ( ) and snowflake ( - G09 = 0 = heating / = cooling - G09 = 1 = heating / = cooling ) icons can be configured by parameter G05 according to the following coding…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 I01 = 0 : Return water temperature probe (100) • I01 = 1 : Supply water temperature probe (101) • I01 = 2 : Temperature probe / condensing pressure transducer circuit 1 (102) • I01 = 3 : Temperature probe / evaporating…
-
Outputs
Compressor 1 Compressor 2 Compressor 3 Compressor 4 Compressor 5 Compressor 6 1 Compressor 1 Compressor 2 Compressor 3 Compressor 4 Compressor 5 Compressor 6 2 Compressor 1 Cases Single circuit Compressor 1 Compressor 2 Compressor Unloader Compressor 1 Compressor 1 Enable Compressor 2 Compressor 3…
-
Single circuit controls 9.4.2.1 Single circuits with On/Off compressors The following are some of the possible combinations for ON-OFF adjustment. - 1 compressor without unloaders (G16=1 G17=1; C01=0; C02=0). The compressor is connected to the output configured as Compressor 1. Cooling Mode…
-
Cooling Mode
9.4.2.2 Heating Mode Single circuit 1 modulating compressor In this case the only compressor will modulate with a "simple" ramp from the minimum value (C09) to the maximum value (C10) according to the capacity control request. The configuration of the parameters is G16=1, G17=1, C01=0, C02=1. The…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Single circuit 1 modulating compressor + up to 5 ON/OFF compressors In this case the modulating compressor will have a "sawtooth” action, while the ON/OFF compressors will be activated "in steps". Only the case of 5…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Single circuit 3 modulating compressors In this case all the compressors have the same rotation frequency and will be enabled in sequence and made to modulate in order to maintain the same percentage compared to the…
-
Dual-circuit controls 9.4.3.1 Dual-circuit with 1 ON/OFF compressor per circuit (balancing and saturation) As regards control, this case is the same as that of a single circuit with 2 compressors. The compressors of circuit 1 and circuit 2 are controlled as 2 power steps. The configuration of the…
-
Cooling Mode
9.4.3.3 Heating Mode Dual-circuit with 6 ON/OFF compressors (saturation) In this case the compressors (up to 6) are activated in sequence, saturating the first activated circuit before activating the second one. The configuration of the parameters is G16=2, G17=3, C01=0, C02=0, C03=3. The…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Dual-circuit with 1 modulating compressor per circuit (balancing and saturation) In this case the compressor of the first circuit is switched on and brought to maximum capacity before switching on the compressor of the…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Dual-circuit with 1 modulating compressor and 2 ON/OFF compressors per circuit (balancing) The compressors of circuit 1 and 2 are switched on/off alternately (starting with the 2 modulating compressors) to keep the…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Dual-circuit with 1 modulating compressor and 2 ON/OFF compressors per circuit (saturation) All the compressors of circuit 1 are switched on (starting with the 2 modulating compressors) before starting those of circuit…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Dual-circuit 6 modulating compressors (balancing) The compressors of circuits 1 and 2 are activated alternately. When a compressor is activated, all the compressors of the circuit are brought to the start-up speed for…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Dual-circuit 6 modulating compressors (saturation) In this case the compressors of circuit 1 are activated first and only afterwards those of circuit 2. When a compressor is activated, all the compressors of the…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Remote control If the machine does not have its own control function but is controlled externally (for example a condensing unit controlled by one or more internal units), it is possible to establish up to 6 digital…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Dynamic setpoint The controller can change the working setpoint (questo "del regolatore" va eliminato anche dal manuale in italiano) by adding to the setpoint (Coo or HEA) a value (Offset setpoint) which depends on the…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Solenoid valve The Solenoid valve circuit 1/2 digital output should be configured for enabling the function. If parameter G18 = 0 and the Evaporating probe circuit 1/2 is configured and not in error mode, control…
-
r27 is a correction parameter for speeding up the control function when the error is too high. r27 = 100 corresponds to no correction, r27=1 corresponds to maximum correction. A period (in seconds) is defined for PWM HGBP valve management (parameter r32) and the PID algorithm defines its duty cycle.…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Modulating operation If a modulating pump is to be used, it must be connected to an analogue output (AO1 or AO2) configured as the System pump. In this case the pump speed is controlled proportionally to the absolute…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Heating elements in antifreeze mode The heating element starts when the pump is switched on and when the minimum temperature between the input and output water is lower than the parameter H02 with hysteresis H05. page…
-
Ventilation Control 10.1 Initial information The condensing temperature/pressure (in cooling mode) and the evaporating temperature/pressure (in heating mode) are controlled modulating the ventilation that can either be proportional or ON/OFF in steps. The maximum number of fan speed steps is 4…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Modulating control function In cooling mode, ventilation control depends on the maximum value between the Condensing probe circuit 1/2 and the Evaporating probe circuit 1/2. In heating mode, on the other hand, it…
-
Defrost 11.1 Initial information The defrost function is only active if the system is in heating mode and enabled by the parameter d01. d01 = 0 Defrost disabled d01 = 1 Defrost with compressor active d01 = 2 Defrost by compressor stop (as d01 = 1 but without activating the compressors) d01 = 3 Timed…
-
page 90 of 110
-
DOMESTIC HOT WATER (DHW) 12.1 Initial information The domestic hot water function is active if fitted (G15 = 1), if a probe is configured as the Domestic hot water probe and if a relay is configured as the Domestic hot water valve. The domestic hot water function is available if the user has…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Anti-legionella function Anti-legionella mode is set by parameter G25: if it is different to 0, the function is active. Furthermore, if the parameter is set to 2, a cycle is programmed for when the machine is switched…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Solar Panels To ensure the solar panel function works correctly, a probe must be configured as the Solar panel manifold probe, a probe as the Solar panel storage probe and a relay output as the Solar panel pump. The…
-
13 INTERNAL STATUSES
States table specific values for the temperature probes: 3276.4: Disabled -3276.8: Err specific values for the pressure probes: 327.64: Disabled -327.68: Err Specific analogue output values - 1: Disabled Digital input and output values - 1: Disabled 0: OFF 1: ON Label S01 Heat pump Chiller Min Max…
-
S13
-
S39
-
14 ALARMS
All the alarms have automatic reset except for: - Antifreeze alarm: manual reset - High pressure alarm: manual reset if the number of occurrences per hour is higher than parameter A05 - Phase sequence relay alarm: manual reset - Compressor thermal switch alarm: manual reset if the number of…
-
Code
Meaning APMP Pump thermal switch alarm The alarm is activated if the input configured as the pump thermal switch input is active. It is deactivated if the input is inactive. Main results: - UArn all the compressors, fans, system heating elements and the pump are switched off. Generic signal The…
-
Code
Meaning AHP1 Circuit 1/2 high pressure alarm AHP2 The alarm is activated both by the high pressure switch and when the maximum value between that of the condensing probe and that of the evaporating probe exceeds the threshold set by A06. The alarm is manually reset if the number of events in an hour…
-
Code
Meaning EA01 Probe alarms EA02 The alarm is activated in the following situations: EA03 - when a probe short circuits or is interrupted EA04 - if the upper or lower limit set for a probe are exceeded EA05 Non-configured analogue inputs do not cause alarms EA06 Main results: EA07 - the functions in…
-
ACCESSORIES 15.1 INTRABUS/RS-485 interface and EVIF22ISX programming key The interface converts the signal of the INTRABUS communications port of EV3 CHILL/HPRU and EVD CHILL/HPRU into an RS-485 signal with the same communication protocol. This enables cables up to 1000 m long to be used to connect…
-
The characteristics of the MODBUS connection (the baud rate, parity and number of stop bits) are automatically detected by the interface if micro-switch 3 of the 3-way dip switch is in the OFF position (if this micro-switch is in the ON position, the parameters of the MODBUS network remain stable…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Configuration download N.B. - the configuration download is possible if the firmware of the controller it originates from and the firmware of the destination controller are the same - if the configuration download…
-
16 TECHNICAL SPECIFICATIONS
16.1 Technical specifications EV3 CHILL/HPRU Purpose of the control device function controller Construction of the control device built-in electronic device Housing black, self-extinguishing Category of heat and fire resistance D Measurements 75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x 2 5/16 in)…
-
NTC probes
0-10 V transducers 4-20 mA transducers EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 Sensor type ß3435 (10 KOhm @ 25 °C, 77 °F) Measurement field from -50 to 120 °C (from -58 to 248 °F) Resolution 0.1 °C (1 °F) Input heating element > 10 KOhm Resolution 0.1 V…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU | Application manual ver. 3.0b | Code 1443DCHE304 EVD CHILL/HPRU technical specifications Purpose of the control device 16.3 function controller Construction of the control device built-in electronic device Housing grey, self-extinguishing Category of heat and fire…
-
Analogue inputs
5 for NTC probes (can also be configured for dry contact digital input) 2 for NTC probes, 4-20 mA, 0-5 V or 0-10 V transducers (can also be configured for dry contact digital input) NTC probes 0-10 V transducers 4-20 mA transducers Sensor type ß3435 (10 KOhm @ 25 °C, 77 °F) Measurement field from…
-
EV3 CHILL/HPRU & EVD CHILL/HPRU
Controllers for single and dual-circuit chillers and heat pumps Application manual ver. 3.0b PT - 25/20 Code 1443DCHI304 This document and the solutions contained therein are the intellectual property of EVCO and thus protected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an…
-
Via Feltre 81, 32036 Sedico Belluno ITALY
Tel. +39 0437/8422 | Fax +39 0437/83648 info@evco.it | www.evco.it page 110 of 110