Инструкция на Контроллеры Dixell серии IC200CX для чиллеров и тепловых насосов
Контроллеры IC200CX для чиллеров и тепловых насосов: функции, интерфейс пользователя, индикация, параметры, регулирование контуров, аварийные сигналы. Руководство пользователя. Документ на английском языке.
Загружаем документ…
Текст инструкции
-
dixcil
iCHilL IC200CX Series User manual
-
FUNCTION MENU “ M” KEY 25 12.1 12.2 12.3 12.4 12.5 12.6 12.7 12.8 12.9 12.10 12.11 12.12 12.13 12.14 12.15 12.16 12.17 12.18 12.19 12.20 ALARM LIST: SHOW AND RESET COMPRESSOR OVERLOAD ALARM RESET COMPRESSOR OVERLOAD PASSWORD. ALARM LOG LIST ERASE THE ALARM LOG LIST PASSWORD VALUE OF THE ALARM LIST…
-
PUMP DOWN 40 23.1 23.2 23.3 23.4 23.5 23.6 OFF UNIT WITH PUMP DOWN AND WITH LOW PRESSURE SWITCH CONTROL PUMP DOWN WITH DEDICATED PRESSURE SWITCH PUMP DOWN FUNCTION WITH DEDICATED PRESSURE PROBE PUMP DOWN ALARM DURING COMPRESSORS START- UP PUMP DOWN ALARM DURING COMPRESSORS SWITCHING OFF PUMP DOWN BY…
-
33.11 END DEFROST BY LOW WATER OUTLET EVAPORATOR TEMPERATURE DEFROST PARAMETER DESCRIPTION ENERGY SAVING 57 34.1 34.2 34.3 34.4 34.5 ENERGY SAVING: DIGITAL INPUT ACTIVATION ENERGY SAVING TIME TABLE WITH RTC RTC DAILY TIME TABLE PROGRAMMING ENERGY SAVING OR UNIT ON/OFF ACTIVATION WITH RTC PROGRAMMING…
-
KEYABOARD ALARM 77 40 AUTOMATIC TO MANUAL ALARM PROCEDURE 77 41 TABLE OF THE OUTPUT STATUS IN ALARM CONDITION 78 41.1 41.2 41.3 ALARM: “A” TYPE AND STATUS OF THE LOADS IN CASE OF ALARM ALARM: “B” TYPE AND STATUS OF THE LOADS IN CASE OF ALARM ALARM: “C” TYPE AND STATUS OF THE LOADS IN CASE OF ALARM…
-
1 GENERAL ADVICE
• • • PLEASE READ BEFORE USING THIS MANUAL This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. Check the application…
-
Rel. 1.0 22/04/2009 GENERAL FEATURES iCHILL IC200CX is an electronic controller for chiller unit applications having one or two circuits: • Air/air • Air/water • Water/water • Motocondensing Additional features: • Heat pump with gas reversibility • Free cooling function • Recovery function 2.1 MAIN…
-
Three different time bands per day (only for controller with RTC onboard) • From digital input Weekly ON/OFF: • Three different time bands per day (only with RTC onboard) Dynamic setpoint: • Determined by analogue NTC input or 4÷20mA current input. Change over : • Automatic chiller or heat pump…
-
CHARACTERISTICS IC206CX IC208CX n n N° KEYS 6 RELAYS 6 n 8 n DIGITAL INPUTS 11 Config Config Config Config 2 configurables (signal 0÷10V) Config Config 2 configurables (signal 0÷10V, PWM) Config Config n n n n 12 Vac/dc (+15%;-10%) n n 24 Vac/dc (± 10%) Opt Opt n n n n Clock on board Opt Opt Buzzer…
-
4 USER INTERFACE
-
Main display (upper display)
Parameters dP01 (IC200CX), dP05 (remote keyboard n°1), dP07 (remote keyboard n°2) PARAMETER VALUE 0 DESCRIPTION No display read out CORRESPONDING LABEL No label 1 NTC temperature probe of the evaporator water inlet Ein 2 NTC temperature probe of the evaporator water outlet 1 and 2 Out1 circuit 1…
-
PARAMETER
VALUE 0 4.2 Rel. 1.0 22/04/2009 DESCRIPTION No display read out CORRESPONDING LABEL No label 1 NTC temperature probe of the evaporator water inlet Ein 2 NTC temperature probe of the evaporator water outlet 1 and 2 Out1 circuit 1 Out2 circuit 2 3 NTC temperature probe of the common evaporator water…
-
Condenser probe temperature Cdt1 / pressure CdP1 Bottom display of the circuit 1 • Evaporator pressure probe LP1 Top display of the circuit 2: Condenser probe temperature Cdt2 / pressure CdP2 Bottom display of the circuit 2 Evaporator pressure probe LP2 4.3 ICONS MEANING ICON °C -°F BAR-PSI MEANING…
-
Rel. 1.0 22/04/2009 MEANING / FUNCTIONNING OF THE BOTTOM DISPLAY LED Led # 1 – 2 (With RTC) If the bottom display shows the RTC the leds are both blinking. Led # 1 – 2 In function Menu During the time counting to the next defrost for one or both circuits the leds are both blinking. LED during…
-
6 DISPLAY INFORMATION
6.1 READ THE SET POINT VALUE Push and release the SET key, the set value is displayed. In stand-by the bottom display shows SetC (set chiller), by pushing SET again the next label is SetH (set heat pump). If the unit is running the only set displayed is related to the running mode. 6.2 1) 2) 3)…
-
Rel. 1.0 22/04/2009 DISPLAY VISUALIZATION IN STD-BY It is possible to customise the visualization of the display when the unit is in STD-BY: Parameter dP4: 0= the display shows "STD-BY" 1= the display shows what defined by parameters dP1 and dP2 2= the display shows “OFF” dP4=0 dP4=1 The display…
-
Rel. 1.0 22/04/2009 KEY FUNCTION KEY ACTION Push and release Push once again FUNCTION Show chiller set point SetC and heat pump SetH In chiller or heat pump if the Energy saving or the Dynamic setpoint are enabled it shows the real setpoint Setr, the led is blinking. Set point modification To enter…
-
7 REMOTE TERMINAL
The iCHILL can be connected to a remote keyboard (max 2 remote keyboards). The remote keyboard with probe on board can be used for the regulation of the machine. The maximum length of the cable is 150mt (shielded cable is recommended). Use the connection cable CAB/CJ30 (2x0.2 mm2) to interface the…
-
9 ANALOG AND DIGITAL OUTPUT CONFIGURATION
9.1 ANALOG INPUT PB1 - PB2 – PB5 – PB6 Parameters involved: CF08 = Configuration PB1 CF09 = Configuration PB2 CF12 = Configuration PB5 CF13 = Configuration PB6 0. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. Not enabled Temperature probe PTC for compressor #1 discharge Temperature…
-
4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. Rel. 1.0 22/04/2009 Flow switch evaporator pump / supply fan overload Flow switch condenser pump Antifreeze heater circuit 1 Antifreeze heater circuit 2 High pressure…
-
Part Winding 1 of the compressor 2
34. Part Winding 2 of the compressor 2 35. Capacity step valve 1 compressor 2 36. By-pass gas valve compressor 2 start 9.5 ANALOG OUTPUT CONFIGURATION 0 ÷ 10 VOLT (OUT1 E OUT2) Parametri: CF43 = Analog output OUT1 configuration CF44 = Analog output OUT2 configuration 0 = output disabled 1 = 0..10V…
-
10 PROGRAMMING WITH THE “HOT KEY 64”
10.1 DOWNLOAD: HOW TO PROGRAM AN INSTRUMENT WITH A PROGRAMMED “HOT KEY” 1. Turn off the instrument supply 2. Insert the hot key. 3. Turn on the power supply. 4. Immediately the parameters are downloaded. During the download the regulation is locked and the top display shows the “doL” blinking label.…
-
4. Change the value with UP or DOWN keys;
5. Push “SET” to confirm, after some seconds the display shows the next parameter; 6. Exit: Push SET + UP together when a parameter label is displayed or wait 15seconds without pushing a key. NOTE: a new parameter value is confirmed also after the 15 seconds of timeout is expired (without pushing…
-
Push SET key and the top display shows a blinking 0, with UP or DOWN insert the Pr2 password. Push SET and, if the value is correct, top display will show the first family of parameters “ALL”. Otherwise set the password again. 4. Select a parameter family with DOWN or UP keys. 5. Push SET to enter…
-
1. 2. Rel. 1.0 22/04/2009 Push 1 time the DOWN key and the led 3 should be on, the parameter is now available in Pr1. To hide the parameter in Pr1: Keep pushed SET key; Push 1 time the DOWN key and the led 3 should be off, the parameter is now removed from Pr1. 11.9 MOVE A PARAMETER FROM PR3 TO PR2…
-
Rel. 1.0 22/04/2009 CHANGE THE POLARITY OF THE DIGITAL INPUTS-OUTPUTS Enter the programming: 1. Select a parameter with digital input/output value, the top display shows the label o before the configuration number while the bottom display shows the parameter label. 2. Push SET key: the o label and…
-
12.3 COMPRESSOR OVERLOAD PASSWORD
The default value is 0; to change this value enter Pr3 level, search AL60 parameter and modify its value. 12.4 ALARM LOG LIST ALOG FUNCTION TO SEE THE ALARM LOG The function and the alarm codes are visible only if there are alarm events. If many events are active at the same time the list displayed…
-
Rel. 1.0 22/04/2009 READ-OUT OF A COMPRESSOR NOT ENABLED During the normal running condition a disabled compressor is displayed with a blinking label alternated with the measurement value of the display. If the compressor is disabled these the corresponding labels: C1dS = compressor 1 disabled, C2dS…
-
Cond FUNCTION selects the proportional output 1 and 2
Label involved in Cond function. Cnd1 Proportional output status of the condenser fan of the circuit 1. Cnd2 Proportional output status of the condenser fan of the circuit 2. TO SEE THE OUTPUT PERCENTAGE: Enter the function menu 1. Use the UP or DOWN keys to select Cond. 2. Push SET key: the bottom…
-
Select with UP or DOWN the trEM function
Push SET the trE1 or trE2 label is shown on the bottom display, the top display shows the probe value. Use the UP or DOWN arrow to change beteween trE1 or trE2 read-out. To exit to the normal display read-out push MENU or wait the time – out time. ATTENTION: THE trEm function and the labels trE1 or…
-
starts in heat pump. the unit starts in chiller, External air temperature probe < ST12 the unit 14 UNIT START - STOP The unit start sotp can be done from one of the following operations: • From keyboards • RTC Time table • Digital input configured as remote ON/OFF 14.1 START – STOP AND STAND- BY…
-
With active contact if the unit is being switched off by keyboard it can be switched on by keyboard. If the unit is being switched off by keyboard, in order to switch on the unit from digital input it must be deactivated and activated. 14.6 MODE WITH DIGITAL INPUT CONFIGURATED AS HEAT PUMP REQUEST…
-
To have the same regulation both for chiller and heat pump set the parameters ST09 and ST10 with the same value 16 THERMOREGULATION: PROPORTIONAL OR NEUTRAL ZONE Par. ST11 determines the type of regulation 0= Proportional 1= Neutral zone 16.1 GRAPH OF THE COMPRESSOR THERMOREGULATION IN CHILLER 16.2…
-
Compressor regulation in heat pump
17 COMPRESSOR STATUS INTO THE NEUTRAL ZONE A particular functioning is scheduled thruogh the rotation or the forced insertion of compressors or spteps during the loads functioning into the neutral zone Par. CO50 / CO51 in order to prevent an extended functioning without compressors functioning…
-
17.1 MAXIMUM TIME OF NEUTRAL ZONE STAY WITHOUT INSERTION OF
RESOURCES WITH AT LEAS ONE RESOURCE INSERTED Par. CO50 With at least one compressor on, when the functioning is into the neutral zone, is calculated the time set by the par. CO50 after which is forced a compressor or partialization step insertion. The resolution is fixed on dozen minuts if the…
-
When both compressors are activeted the thermoregulation is done with the variation of the capacity percentage. When the thermoregulation switches off the ON/OFF compressor, the controller manages the capacity percentage to follow the real request. UNIT IN HEAT PUMP Compressor activation: when the…
-
When the thermoregulation requests the activation of the second compressor
When both compressors are activated the thermoregulation is done with the variation of the capacity percentage. When the thermoregulation switches off the ON/OFF compressor, the controller manages the capacity percentage to follow the real request. Pg.36/114
-
18 THERMOREGULATION AND COMPRESSORS ROTATION
The CO13 parameter allows to choose the sequence of activation of the compressors. CO13= 0 Sequential. Depending on the thermoregulation: Activation sequence: COMP. 1 COMP.2 Deactivation sequence: COMP.2 COMP.1 CO13= 1 Rotation by hour. Depending on the time running hours the first compressor called…
-
20.4 PART WINDING
This algorithm allows to reduce the start-up current when using hermetic or semi-hermetic compressors or medium – big screw compressors. Each compressor needs two relay outputs: • One is the PW motor coil 1 of the compressor; • One is the PW motor coil 2 of the compressor The time delay between the…
-
1= the steps are turned on in sequential mode, the outputs are anabled or disabled depending on the output polarity. In case of thermoregulation request one of the step is turned on or off while the other steps do not change their status. Eg: 1 capacity compressor with 3 partializations: 4 Power…
-
Having one compressor with 3 partializations, at the compressor start-up, with CO07=0, the partialization valve is enabled only for the time CO12 but it won’t be never used during the thermoregulation. After the compressor stops running the time CO12 will be reloaded. Having one compressor with 3…
-
If the last compressor stops before the low pressure switch because of the CO33 time-out (maximum compressor on time after turning off the P.D. solenoid valve), the ICHILL calculates the AL28 parameter (maximum number of pump down alarm per hour) and if an alarm occurs the display will show the…
-
If the last compressor stops before the pump down pressure switch because of the CO33 time-out (maximum compressor on time after turning off the P.D. solenoid valve), the ICHILL calculates the AL28 parameter (maximum number of pump down alarm per hour) and if an alarm occurs the display will show…
-
It is possible to have the pump down procedure also without pressostat or pressure trasducers ; in this case, by configuring CO52 and CO53, the compressor is switched off after CO52 time starting from pump down valve activation and switched on after CO53 time starting from pump down valve…
-
24.6 REGULATION IN HEAT PUMP MODE
UNLOADING IN HEAT PUMP MODE The compressor unloading in heat pump mode is managed by the analogue input configured as evaporator probe circuit 1 or 2. When the heat pump thermoregulation request begins to start the compressors, if the evaporator pressure/temperature is equal or lower than CO43…
-
When the unit is in stand-by or remote off and the parameter Ar21=1, if the antifreeze thermoregulation requires the water pump is turned on. CO15 = 4: modulating control type 1. The water pump/ supply fan are running only if the unit is running (in chiller or heat pump). After giving the start in…
-
Note: During the defrost and when the compressor is off in dripping time the pump is on
28 WATER PUMP OF THE CONDENSER 28.1 CONDENSER WATER PUMP CONTROL Operative mode of the condenser water pump CO20 = 0 Not enabled, pump not controlled. CO20 = 1: Continuous control type 1. The water pump is running only if the unit is running (in chiller or heat pump). After giving the start in…
-
29.2 CONDENSER WATER PUMP ROTATION THROUGH DIGITAL INPUT CONTROL
With two digital inputs configured as overload alarm of water pump and support pump the rotation is enabled when the digital input of the running pump becomes active. That pump is turned off while the other is forced on. If only one digital input is configured as condenser water pump alarm or only…
-
Modulating control of the condenser pump in Chiller mode
Modulating control of the condenser pump in Heat pump mode: 31 CONDENSER FAN REGULATION With the parameters CF43..CF46 is possible to select the analog output (OUT1..OUT4) and the signal to manage the condenser fan in proportional mode. If the condenser fan is managed by PWM output, the parameter…
-
Independent from the compressor status but off in stand–by. Par. FA01 = 2 + Par. FA02 = 0 Fans on, with ON/OFF regulation and with temperature/pressure transducer control, only when the compressor is on (at least one relay is configured as fan control). When the compressor turns off also the fans…
-
31.4 GRAPH: PROPORTIONAL REGULATION OF CONDENSER FANS
31.5 GRAPH: ON / OFF REGULATION OF THE CONDENSER FAN IN CHILLER MODE 31.6 GRAPH: ON / OFF REGULATION OF THE CONDENSER FAN IN HEAT PUMP MODE Pg.50/114
-
32 THERMOREGULATION OF THE ANTI FREEZE, INTEGRATION HEATING OR
BOILER 32.1 THERMOREGULATION OF THE HEATERS IN CHILLER The Par. Ar06 selects the probe/s control for the anti-freeze relay outputs configured as anti-freeze / support / boiler heaters for the circuits 1 and 2 in chiller mode. Par. Ar06 = 0: the function is disabled Par. Ar06 = 1: the…
-
Par. Ar08 = 2: the heater 1 regulation is executed through the condenser water outlet NTC probe of the circuit 1. The heater 2 regulation is executed through the condenser water outlet NTC probe of the circuit 2. ATTENTION It is not possible to control the heaters of the circuit 1 with the NTC probe…
-
33 DEFROST CYCLE
The defrost cycle starts only if all these steps are determined: Heat pump unit DF01≠0 (defrost enabled) The condenser/evaporator probe is configured (per circuit) (if the evaporator probe/s is/are defined, the defrost cycle is always controlled by it / them). 33.1 FORCED DEFROST The function is…
-
dF22=0
dF22=1 dF22=2 not possible (ACF1) Yes Yes Yes Yes not possible (ACF1) not possible (ACF1) Yes not possible (ACF1) ATTENTION: The configuration error ACF1 is displayed if the parameter value of dF22 and dF23 is not permitted. 33.7 AUTOMATIC DEFROST PROCEDURE Phase 1: when the unit is working in heat…
-
33.8 OTHER INFORMATION ABOUT THE DEFROST
If the unit is configured with one condenser see parameter FA05: 0= common condenser; 1= separated condensers. For FA05=0, common condenser, the defrost of the two circuits starts at the same time. ATTENTION Before starting the 3rd phase, the dF06 counting (time delay between two circuits defrost)…
-
dF06 defrost delay time between the 1st and the 2nd circuit
After the interval dF09 determined by the defrost request of one of the circuits the other 2nd circuits must wait also the time dF06 before defrosting. dF07 Compressor off time before the defrost (the led of the compressor is blinking) After the dF09 delay and before activating the defrost, the…
-
dF26 Stop supply fan during defrost cycle
0= Not enabled 1= Enabled dF26 Probe selection for minimum temperature outlet during defrost This parameter allows to select which probe controls the outlet temperature to force the exit of the defrost dF27 Set point for minimum temperature outlet during defrost 34 ENERGY SAVING 34.1 ENERGY SAVING…
-
Example of a daily programming
Monday Enater parameter programming 1. In the ES parameter family, select the parameter ES07, the top display shows 0 - 0 2. Push SET key: the top display shows 0 - 0 blinking, with UP or DOWN keys select the corresponding function (see next table) : 3. Push SET to confirm. 4. Push SET + UP to exit…
-
35 DYNAMIC SETPOINT
The dynamic setpoint allows to increase or decrease the setpoint with a proportional value determined by Sd01 (chiller) and Sd02 (Heat pump) that depends from the 4..20mA analogue input or from the external air temperature probe. This function allows to save energy or run the unit when the external…
-
36 GEOTHERMAL FUNCTION
The function manages an ON/OFF valve (relay) or modulated valve (signal 0..10V) to use, for example, a ground water as cooling integration. Configuration: • the function has to be activated by parameter US21 • two probes have to be configured by parameters US25 and US26 • one relay has to be…
-
Analog output 0..10V: geothermal function configured on reverse action
Analog output 0..10V: geothermal function configured on direct action 37 AUXILIARY FUNCTION 37.1 AUXILIARY FUNCTION ON RELAY OUTPUT The auxiliary relays can be configured to manage two independent, from heat pump or chiller mode, output controls. Each output can be managed with a dedicated…
-
37.1.2 Auxiliary relay on reverse action
PBr = NTC probe or transducer selected by the parameters uS02 / uS06 37.2 AUXILIARY FUNCTION ON ANALOG OUTPUTS The analog outputs OUT1…OUT4 can be configured as auxiliary output. The function is enabeld if: • AUX1: parameter uS09≠0 and an analog input configured as “Temperature probe NTC for…
-
38 LOAD MAINTENANCE
PARAMETERS CO24..CO29 are the set of the running hour counters of the loads (compressors and water pumps). They establish, for each load, the number of running hours limit to display a maintenance message. If one of these parameters is equal to 0 the maintenance signalling is disabled but the…
-
39 MESSAGES - ALARM CODES
the alarm codes are defined by letters and numbers:. Alarm typology: • A = alarm of the unit • b = alarm of the circuit • C = alarm of the compressor 39.1 AP1 - AP2 - AP3 - AP4 - AP5 - AP6 - AP7 - AP8 PROBE FAILURE Label on the display Reason Reset Restart Icon Action AP1 = PB1 probe alarm…AP6 = PB6…
-
AL17/AL21 Maximum time flow switch alarm active befor to block the water pump
It determines maximum time of flow alarm active before to block the water pump. ATTENTION With air/water or water/water units (CF01=1,2) the minimum number of events per hour is 1. 39.4 ATSF: OVERLOAD ALARM OF THE SUPPLY FAN Label on the display Origin Reset Restart Icon Action AtSF: Overload alarm…
-
39.8 AFR: POWER SUPPLY FREQUENCY ALARM
Label on the display Origin Reset Restart Icon AFr (Line frequency alarm) The power supply frequency is not equal to the Par. CF54 ± tolerance Ferquency control parameter adjusted, frequency within the tolerance Automatic Blinking Alarm relay + buzzer ON Action The alarm is disabled if CF54=0 39.9…
-
ACF1 - ACF2 - ACF3 - ACF4 - ACF5 - ACF6 - ACF7 - ACF8 - ACF9 – ACF10 – ACF11 CONFIGURATION ALARM OF THE UNIT Label on the display ACF1 • Heat pump unit without 4-way valve not configured • Wrong configuration of defrost parameters dF22/23 ACF2 • Condensing control without probe configuration. (one…
-
ACF6
• The number of compressors/steps of the 2 circuits ( CF04 + CF05 ) is: √ > 4 with no direct compressor start-up (CO10 ≠ 0) or the number of steps is ≠ 0 (CF06), √ > 2 and the intermittent valve is configurated with ON (CO08) and OFF (CO09 ) ≠ 0 • Pump-down function but at least in one circuit √ The…
-
ARTF CLOCK FAILURE Label on the display Origin Reset Restart Icon Action Regulation Loads Energy saving Unit ON/OFF 39.14 ArtC (clock alarm) Wrong setting Clock adjusted Manual in function menu Blinking Alarm relay + buzzer ON Not changed Disabled if based on RTC Disabled if based on RTC AEUN…
-
Origin
Rel. 1.0 22/04/2009 Icon Action During normal running condition when the temperature/pressure of evaporator water inlet is lower than AL69 setpoint. The alarm is not signalled for AL68 seconds starting from compressor activation. Evaporator inlet temperature > AL69 + AL70 Unit in STD-BY or remote…
-
Chiller: evaporator inlet NTC probe higher than AL33 + AL34
Heat pump: evaporator inlet NTC probe higher than AL42 + AL43. In stand-by or remote OFF: the evaporator inlet NTC probe higher than AL33+AL34 or AL42+AL43. Automatic Reset Restart Icon Action 39.20 Blinking Alarm Relay + and buzzer on AEP1 - AEP2 EVAPORATOR PUMPS / SUPPLY FAN MAINTENANCE REQUEST…
-
Rel. 1.0 22/04/2009 B1LP - B2LP LOW TEMPERATURE / LOW CONDENSING PRESSURE OF THE CIRCUIT Label on the display Origin Reset Restart Icon Action b1lP (low pressure digital input of the circuit 1) b2lP (low pressure digital input of the circuit 2) When the condensing probe value is lower than AL03…
-
air. After the AL44 delay if the anti-freeze probe is still lower than AL42 setpoint for AL45 seconds the unit is locked again with an antifreeze alarm. 39.26 B1HP - B2HP HIGH CONDENSING PRESSURE / TEMPERATURE OF THE CIRCUIT Label on the display Origin Reset Restart Icon Action Regulation Condensing…
-
Rel. 1.0 22/04/2009 B1EU – B2EU: UNLOADING FROM LOW TEMPERATURE OF THE EVAPORATOR WATER OUTLET Label on the display Origin Reset Restart Icon Blinking Alarm relay + buzzer Action Regulation Compressor Other loads 39.31 OFF Not modified C1HP - C2HP COMPRESSOR HIGH PRESSURE ALARMS Label on the display…
-
Rel. 1.0 22/04/2009 C1TR - C2TR COMPRESSOR OVERLOAD ALARM Label on the display Origin Reset Restart Icon Action Compressor involved Compressor not involved C1tr (Compressor #1 overload alarm) -…C2tr (Compressor #1 overload alarm 2) With active digital input The alarm is not detected for AL24 time…
-
B1PH Rel. 1.0 22/04/2009 - B2PH: PUMP DOWN STOP ALARM FROM PRESSURE SWITCH / LOW PRESSURE SWITCH Label on the display Origin Reset Restart Icon b1PH (Pump down stop alarm of the circuit 1) b2PH (Pump down stop alarm of the circuit 2) Pressure switch: if CO30 = 1,2,3,4 and ID not active, the pump…
-
Rel. 1.0 22/04/2009 ALARM RELAY AND BUZZER Alarm relay / buzzer outputs Origin Alarms still active Alarms not reset Whitout alarms In stand- by or remote ON-OFF if AL59 = 1 By pushing one of the key of the front panel Reset relay alarm Buzzer silencing The alarm relay is enabled only by…
-
41 TABLE OF THE OUTPUT STATUS IN ALARM CONDITION
The alarm codes are made of letters and numbers to define the different typologies:. 41.1 ALARM: “A” TYPE AND STATUS OF THE LOADS IN CASE OF ALARM Alarm Code ALti AEFL ACFL AtSF AEUn AELt Aedt AtE1 AtE2 AtC1 AtC2 AEP1 AEP2 ACP1 ACP2 ArtC Atr1 Atr2 ArtF ALc1 ALc2 ALc2 AEE AFr ACF1 ACF2 ACF3 ACF4 ACF5…
-
AC11
AEht (1) (2) (3) (4) (5) Rel. 1.0 22/04/2009 Configuration alarm High water temperature inlat evaporator Yes Yes Yes Yes Yes Yes = with probe configured as anti-freeze / boiler control and Ar10 = 0 = with probe configured as auxiliary relay control = with manual alarm procedure = Off compressors…
-
C(n)oP
C(n)tr C(n)dt C(n)dS C(n)Mn Rel. 1.0 22/04/2009 Compressor(n) oil pressure switch / Oil level switch Compressor(n) overload Compressor high discharge temperature Compressor (n) disabled from keyboard Compressor(n) maintenance Yes Yes Yes Yes (n) identifies the compressor 1, 2 , 3 , 4 , 5 , 6…
-
42 TABLE OF THE PARAMETERS
Label Description ALL Shows all the parameters ST Shows only the Thermoregulation parameters CF Shows only the Configuration parameters SD Shows only the Dynamic Setpoint parameters ES Shows only the Energy Saving, RTC parameters CO Shows only the compressor parameters US Shows only the Auxiliary…
-
Parameter
dP 1 dP 2 dP 3 dP 4 dP 5 dP 6 dP 7 dP 8 Pr1 Pr2 Pr3 Parameter CF 1 CF 2 CF 3 CF 4 CF 5 CF 6 CF 7 Rel. 1.0 22/04/2009 Description min Default read-out of the top display 0 Default read-out of the bottom display 0 Default display read-out configuration top / bottom 0= Configurable (parameters dP1 and…
-
CF 8
-
CF 44
Rel. 1.0 22/04/2009 CF 49 OUT 4 configuration 0= Not enabled 1= 0..10V signal for compressor 1 inverter controlled 2= 0..10V signal for compressor 2 inverter controlled 3= 0..10V signal for auxiliary output 1 4= 0..10V signal for auxiliary output 1 5= 0..10V signal for geothermal function 6= 0..10V…
-
CF 56
CF 57 Firmware Release (this parameter is only in reading) Eeprom parameter map (this parameter is only in reading) Enabling compressors CF 58 Enabling compressors 0= chiller and heat pump 1= only chiller 2= only heat pump Pr1 Password Pr2 Password Pr3 Password Dynamic Setpoint Parameters…
-
CO 6
CO 7 CO 8 CO 9 CO 10 CO 11 CO 12 CO 13 CO 14 CO 15 CO 16 CO 17 CO 18 CO 19 Rel. 1.0 22/04/2009 Partialization (Capacity Control) Functioning (see Capacity Control) 0= On/off steps 0 1= Continuous insertion of the steps and direct action 2= Continuous insertion of the steps and reverse action 3=…
-
CO 20
Rel. 1.0 22/04/2009 CO 31 Operative mode of the condenser pump 0= Not enabled 1= ON/OFF: continuous operation type 1 When the unit is running in Chiller or Heat Pump the pump is running. In std-by or remote OFF mode, the pump is OFF. 2= ON/OFF: on if called by compressor When a compressor is…
-
CO 47
CO 48 CO 49 CO 50 CO 51 CO 52 CO 53 CO 54 Rel. 1.0 22/04/2009 Minimum ON time of the capacity step after the unloading function start (only for 0 capacity compressor) Compressor liquid injection Setpoint of the solenoid valve (on) of the liquid injection 0 32 Setpoint of the solenoid valve (off) of…
-
CO 82
Rel. 1.0 22/04/2009 CO 83 CO 84 CO 85 Time at maximum speed during the switching off of the pump Modulating condenser water pump Probe selection (Pb1..Pb6) for modulating condenser water pump in chiller Probe selection (Pb1..Pb6) for modulating condenser water pump in heat pump Set point for…
-
US 11
Minimum value of the auxiliary proportional output 1 US 12 Maximum value of the auxiliary proportional output 1 US 13 Auxiliary proportional output 1 setpoint US 14 Auxiliary proportional output 1 differential US 17 Auxiliary proportional output n° 2 Auxiliary proportional output n° 2 operating mode…
-
FA 1
FA 2 FA 3 FA 4 FA 5 FA 6 FA 7 FA 8 FA 9 FA 10 FA 11 FA 12 Rel. 1.0 22/04/2009 Fan configuration output 0 = Not enabled 1 = Always on 2 = ON/OFF regulation with steps 3 = ON/OFF Continuous regulation 4 = Proportional speed control Fan operating mode 0= Dependent from the compressor 1= Independent…
-
FA 21
FA 22 FA 23 Rel. 1.0 22/04/2009 Proportional speed control FA01 = 4 CUT-OFF differential in heat pump. To set a temperature/pressure differential to stop the fan. ON/OFF regulation FA01 = 2/3 Differential step circuit n° 2 Over ride CUT- OFF in Heat pump. To set a temperature/pressure differential…
-
Ar 14
Rel. 1.0 22/04/2009 Time delay before turning the boiler on 0 250 Min 50.0 -58 0.1 0 70.0 158 25.0 45 °C °F °C °F Dec int Dec int 50.0 -58 0.1 0 50.0 -58 0.1 0 70.0 158 25.0 45 70.0 158 25.0 45 °C °F °C °F °C °F °C °F Dec int Dec int Dec int Dec int -50.0 -58 0.1 70.0 158 25.0 °C °F °C °F Dec int…
-
dF 18
Pressure / temperature setpoint to force the ventilation ON during the defrost. dF 19 dF 20 Forced defrost Minimum time delay before a forced defrost Pressure / temperature setpoint for a forced defrost dF 21 Forced defrost differential -50.0 -58 0.0 0 70.0 158 50.0 725 °C °F bar psi Dec int Dec Int…
-
AL 8
Rel. 1.0 22/04/2009 AL 9 Low temperature/pressure alarm with unit in OFF or stand – by: 0 = Not enabled 1= Alarm enabled High Alarm High temperature/pressure alarm from analogue input AL 10 High temperature/pressure alarm differential from analogue input AL 31 Oil Alarm Low oil pressure / level…
-
AL 33
Rel. 1.0 22/04/2009 AL 40 “Antifreeze / low ambient temperature (air / air unit) / low temperature air outlet (air/air)” alarm setpoint temperature “Antifreeze / low ambient temperature (air / air unit) / low temperature air outlet (air/air)” alarm differential temperature Alarm delay for…
-
AL 52
AL 53 AL 54 AL 55 AL 56 AL 57 AL 58 AL 59 AL 60 AL 61 AL 62 AL 63 AL 64 AL 65 AL 66 AL 67 AL 68 AL 69 AL 70 AL 71 AL 72 AL 73 AL 74 AL 75 AL 76 AL 77 AL 78 Rel. 1.0 22/04/2009 Maximum number of generic alarm events (each event stop the regulation) before turning the alarm from automatic to manual…
-
AL 79
AL 80 Pr1 Pr2 Pr3 Rel. 1.0 22/04/2009 Probe 1 selection for Inlet / outlet water tempearture differential alarm Allows to select which probe value NTC/PTC Pb1..Pb6 Probe 2 selection for Inlet / outlet water tempearture differential alarm Allows to select which probe value NTC/PTC Pb1..Pb6 Password…
-
43 BLACK-OUT
After the black-out is restored: 1. The instrument restores the same operating mode lost after the supply failure. 2. If active, the defrost is aborted. 3. All the timers and time parameters are reloaded. 4. The manual alarm is not reset. 44 WIRING CONNECTIONS 44.1 HARDWARE RESOURCES FOR IC206CX…
-
44.2 HARDWARE RESOURCES FOR 208CX MODELS
8 digital outputs (relays) MAX current on the relay contacts relè 5(2)A 250V - MAX common current 10A 250V 11 digital inputs (free of voltage) 6 analogue inputs: • 4 NTC / PTC probes • 2 NTC / PTC / pressure transducer 4÷20 mA / pressure transducer ratio-metric 0÷ 5.0 Volt 4 modulating outputs: • 2…
-
44.4 DIGITAL INPUTS
GND = common terminal ID1…ID11 = digital inputs 44.5 ANALOG INPUT FOR PRESSURE TRANSDUCER PP30 (4 ÷ 20MA SIGNAL) 12V = power supply for pressure transducers Pb3 and Pb4 = pressure transducer inputs
-
44.6 ANALOG INPUT FOR PRESSURE RATIOMETRIC TRANSDUCER PPR30 (0 ÷ 5V SIGNAL)
+5V = power supply for pressure transducers GND = ground for pressure transducers Pb3 and Pb4 = pressure transducer inputs Pg.102/114
-
45 PWM OUTPUT FOR CONDENSING FAN SPEED CONTROL
OUT3 and OUT4 = cut of phase signals for the modulation of the condenser fan GND = ground for pressure transducers The compatible modules are the following: XV05PK mono-phase , cut phase control 500 Watt (2A) XV10PK mono-phase , cut phase control 1000 Watt (4A) XV22PK mono-phase , cut phase control…
-
45.2 PROPORTIONAL OUTPUTS CONFIGURED FOR AUX RELAY CONTROL
OUT3 and OUT4 = signals for relays GND = ground 45.3 HOT KEY 64 CONNECTION Pg.104/114
-
45.4 XJ485CX CONNECTION
The XJ485CX interface is a signal converter (from TTL to RS485). The RS485 uses two terminals (+) and (-) that must be connected respecting the polarity. Use the CAB/RS02 to connect the XJ485 interface to the TTL connector.
-
Can be used max. 2VI620CX remote keyboards. Use shielded cable for the connection up to 150mt maximum. In case of communication failure the upper display shows “noL” (no link). Use the CAB/CJ30 to interface the ichill connector to the shielded cable. 46 INSTALLING AND MOUNTING 46.1 PANEL CUT- OUT…
-
46.2 VERTICAL BOARDS VI620CX PANEL CUT-OUT
The remote terminals are for panel mounting, panel cut-out 72x56 mm, and screwed with two screws. The IP65 can be reached with the gasket RGW-V (optional). WALL MOUNTING: use the vertical V-KIT (black, white and grey) as described in the following scheme:
-
47 ELECTRICAL CONNECTIONS
The instrument is provided with: • 2 removable terminal blocks MOLEX MICROFIT 14 and 18 ways for power supplay / digital and analogue inputs and modulating outputs • 1 removable terminal blocks AMP 12 ways for the relay outputs • 5 ways connector for TTL RS485 interface outputs. Wire size: • signal…
-
48.2 WIRING KIT
CWCXA15-KIT e CWCXA30-KIT: wiring kit for IC206CX (lenght of 1,5mt or 3mt) CWCXB15-KIT e CWCXB30-KIT: wiring kit for IC208CX (lenght of 1,5mt o 3mt) 48.3 TRANSFORMER The TF10 trasnformer models: 230/12 Vac , 230 /24 Vac, 110 / 12 Vac, 24 / 12 Vac 48.4 XJ485CX TTL/RS485 converter to connect the…
-
49 TECHNICAL DATA
Housing: self extinguishing ABS. Case: frontal 32x74 mm; depth 60mm Mounting: panel mounting in a 29x71mm panel cut-out Frontal protection: IP65 Display: Top Display 4 digits with d.p. Bottom Display 4 digits with d.p. Power supply: 12Vac -10%÷+15% or 24 Vac/dc ±10% 50/60 Hz Power absorption: 10VA…
-
NOTE
Dixell S.p.A. Z.I. Via dell’Industria, 27 32010 Pieve d’Alpago (BL) ITALY tel. +39 - 0437 - 98 33 - fax +39 - 0437 - E-mail:dixell@dixell.com - http://www.dixell.com