WSAR-MT 21-25-31-41-51-61-81 AIR-WATER HEAT PUMP FOR OUTDOOR INSTALLATION Installation and Use Manual M0G440G8-00 02/09/2008
-
UNIT IDENTIFICATION
SERIAL NUMBER LABEL The units are identified by the serial number label shown here. The label lists the type of unit (series and size), serial number, year of manufacture, number of electrical diagram, main technical data, logo and address of the manufacturer. The label is placed on the unit…
-
INSTRUCTIONS FOR THE USER
• This is a partial shyntesis of the information provided in the manual; carefully read this manual • Carefully read this manual. Keep it with the electrical diagram. Make it available to technicians for servicing. • Ask the installer for training on start-up, shutdown, changing set points, placing…
-
GENERAL WARNINGS
MANUAL PURPOSE This manual has been designed to enable the unit to be installed, started up and maintained correctly. MANUAL INSTRUCTIONS It is essential to observe these instructions. The manufacturer declines all liability for any damage that may be caused whether directly or indirectly to persons…
-
RESIDUAL RISKS
GENERAL This section lists some of the more common situations which, being beyond the control of the manufacturer, could be a source of risk to persons or property. DANGER AREA The figure below highlights the area in which only authorised personnel may operate. • External danger zone, identified by…
-
Contact with parts that could become live when the unit is
started up can result in electric shock, burns or death by electrocution. When there is no need for circuits to be powered up, set the isolating switch on the power line to the OFF position, padlock it and post a warning sign. MOVING PARTS Contact with the fan rotors can cause injury. Before…
-
Chemical -physical properties. Relative density, gas (air=1) Heavier than air. Solubility in water (mg/l). Not known, but probably very low. Aspect. Colorless liquefied gas. Smell. Simile to ether. Point of ignition. Don’t ignite. 10 Stability and reactivity. Stability and reactivity. No…
-
RECEPTION
INSPECTION UPON RECEPTION Check on arrival that the unit has not suffered damage during transit and that it is complete in every part as specified in the order. In the event of visible damage/deficiencies being discovered, make a note immediately on the delivery document with the comment…
-
POSITIONING
GENERAL For installing air-conditioning systems, it is necessary to consider the following: • the technical spaces necessary for the machine and system • the place where the machine will be installed • the transport of thermal carrier fluids and relevant connections to the unit: o water o air o…
-
ACCESS TO THE UNIT INTERIOR
To access to the unit interior remove in sequence : 1. lower lateral panels 2. upper lateral panels 3. the casing Removable panels and casing M0G440G8-00 Electrical panel that can be opened 03/09/08 Coupling points for panels and casing page 12
-
WATER CONNECTIONS
GENERAL Piping must be designed with the least possible number of bends and head variations. If the pressure chute of the installation is above the useful prevalence of the pump, the water delivery capacity is reduced as well as, as a consequence, the thermal exchange and the yield. INTERCEPTING…
-
INPUTS
To perform water / electrical connections remove first the plate cover ( 1 ) In case of unit lower input , use the pre-cutting hole on the base plate ( B ) Kit idronico: C B D A Unit water and electrical connections Optional hydronic kit A Lateral output input for water circuit B Electric line input…
-
ELECTRICAL CONNECTION
GENERAL The characteristics of the electrical lines and relevant components must be determined by SPECIALIZED PERSONNEL ABLE TO DESIGN ELECTRICAL INSTALLATIONS; moreover, the lines must be in conformity with professional procedures and the regulations in force. All electrical operations should be…
-
ACCESSORY ELECTRICAL DATA
Sizes Circulating pump data F.L.A. – Circulating pump A F.L.I. - Circulating pump kW Integration resistance data F.L.A. - Integration resistance (1) A F.L.A. - Integration resistance (2) A F.L.I. - Integration resistance (3) kW 0,95 0,20 0,95 0,20 1.24 0,26 1.24 0.26 1.24 0.26 3.20 0.66 3.20 0.66…
-
Costumer connection terminal block XC2 19 20 XC 2 Remote second set : S A 3 Remote Summer – Winter: S A 2 XC2 XC2 The second setpoint is used to reduce the energy The Summer-Winter operating mode can be chosen consumptions (ex. by night or during the absence by remote selector . periods). To enable…
-
Domestic hot water request : S A 4
EXT. 3-WAY VALVE 230/1/50 XC2 N XC 1 For the production of domestic hot water the 3-way valve must be present. For details see on the side . For the production of domestic hot water the 3-way valve When the production of domestic hot water is active, it is must be present . not possible to change…
-
SET POINT CORRECTION
ON OUTSIDE TEMPERATURE and HUMIDITY WATER RESET 7 XC 2 + 6 5 + 8 - XC2 XC 2 + 4-20 mA WINTER SUMMER With low outside With mild outside SUMMER WINTER temperatures the refrigerant temperatures the thermal If the refrigerant needs is If the thermal needs is low, needs is reduced . needs is reduced.…
-
CLIVET BUS connection
MODBUS connection max 50 mt - standard max 1000 mt - optional 230/1/50 J1 J2 + GND XC3 DIP 4 DIP 4 DIP 2 -+ DIP 2 XC3 GND RS 485 RS485 SYSTEM MANAGER DIP 2 DIP 3 DIP 4 Necessary configuration if are present the domestic hot water module or the mixing module for radiant panels max 1000 mt - optional…
-
START-UP
ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF THE SYSTEM. ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. PRELIMINARY CHECKS Before checking, please verify the…
-
thermal protection. In this event, cut the power and reverse
the 2 phases on the machine power. Prevent the compressor from working with in reverse rotation: more than 2-3 anomalous starts up can damage it. Make sure the direction of rotation is correct, measure the condensation and suction pressure. Pressure must clearly differ: at the start, the suction…
-
CONTROL
HEAT / COOL – EXIT (previous menu) ALARMS / AHEAD fast menu STATA / BACK fast menu ON / OFF – MAIN MENU ENTER : access to menu AHEAD BACK slow switch on / switch off : the unit comfort / economic : choose between max. comfort or min. consumptions automatic : daily/weekly scheduling Press the button…
-
It appears the new chosen status ( ECO ) COOL / HEAT / produce DOMESTIC HOT WATER 1 Press the button Rotate the button 2 to scroll the menu Press the button 3 to confirm the choice Cooling 4 Heating It appears the symbol of the new choice Domestic hot water production TO MODIFY THE SET ( COOLING…
-
UNIT KEYPAD mode
Access to menu main menu UP – DOWN stata main menu previous menu base FW version keypad FW version unit stata stata I/O digital inputs analogical inputs digital outputs analogical outputs alarms active alarms alarm log alarm reset log reset configuration keypad setup setpoint language unit all…
-
CHRONOTHERMOSTAT – SYSTEM MANAGER mode
accesso menu main menu stata UP – DOWN main menu previous menu keypad FW version unit stata heat pump ACS module terminals alarms heat pump ACS module terminals configuration keypad setup setpoint language zones sanitary setup antilegionella system unit list autoconfiguration scheduling zones weekly…
-
The ALARMS indicates a potentially dangerous situation for the unit integrity. Before resetting the alarm, identify and remove the lockout cause. Resetting more than once can cause irreversible damages . In case of doubt please contact an authorized service centre. 1 Press to see the alarm Active…
-
LIST OF ALARMS
-
CHECK THE STATA
( water and air temperatures, etc ) Press to access to the STATA menu 1 than rotate to scroll . The complete stata list is at the following page 2 STATA ⇒ S1 xxxx S2 XXXX S3 S4 S5 Press to go back to the main panel Or : MAIN MENU Press to access to the MAIN menu 1 than rotate to choose the STATA…
-
UNIT STATA
Num. status M0G440G8-00 DESCRIPTION UM 1 Current Set point °C 2 Current step difference (with compensations) °C 3 Resource insertion timer Seconds 4 Dynamic TimeScan of the resource insertion Seconds 5 Outside T compensation °C 6 Ambient T compensation °C 7 WR compensation °C 8 Charge compensation…
-
ROUTINE MAINTENANCE
BEFORE UNDERTAKING ANY SORT OF MAINTENANCE OR CLEANING, DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE UNIT, AND ENSURE THAT OTHER PEOPLE CANNOT RE-CONNECT IT . All equipment is subjected to wear out. The maintenance makes : 1. keeps the unit efficiency 2. the components last longer 3. keeps their…
-
MAINTENANCE INSPECTIONS
Foresee inspection assistance carried out by authorized centers or by qualified personnel. The inspections should be carried out at least: • - Every year for only the cooling units • - Every six months for the cooling and warming units The frequency, however, depends on the use: in the event of…
-
REFRIGERANT TABLES
THIS SECTION IS DEVOTED ONLY TO QUALIFIED TECHNICIANS THAT KNOW THE FOLLOWING: • THE OPERATIONAL PRINCIPLES OF THE REFRIGERATING CIRCUIT OPERATION • THE MODES OF DETECTING TEMPERATURE AND PRESSURE • THE RISKS RELEVANT TO THESE OPERATIONS The data of the tables allow the testing of the refrigerating…
-
TROUBLESHOOTING
THE OPERATIONS MUST BE CARRIED OUT BY TECHNICAL QUALIFIED PERSONNEL HAVING THE REQUISITES UNDER LAW REQUISITES AND IN CONFORMITY WITH THE SAFETY REGULATIONS IN FORCE. THE INTERVENTIONS WITHIN THE WARRANTY PERIOD WILL BE CARRIED OUT BY AUTHORIZED SERVICE CENTERS. BEFORE RESETTING AN ALARM, IDENTIFY…
-
COMPRESSOR PROTECTION
1. Identify the part on the wiring diagram 2. Loose electric contacts/terminals, leads broken 3. electrical windings interrupted 4. Vacuum power voltage below the limits 5. power contactors / contacts defective 6. start-up power voltage lower than the limits 7. electrical absorption high /…
-
DECOMMISSIONING OF THE UNIT
DISCONNECTING THE UNIT The units must be disconnected by authorised personnel, who before proceeding must first read the Residual Risks section in this manual. Awaiting dismantling and disposal, the unit can also be stored outdoors, as bad weather and rapid changes in temperature will not cause…
-
TECHNICAL DATA
-
TECHNICAL DATA
BASE CONFIGURATION Sizes 400/3/50+N Heating A7(6)W30/35 Heat capacity 1 KW Total absorbed capacity 1 kW COP EUROVENT 4 COP EN14511 Heating A2(1)W30/35 Heat capacity 2 KW Total absorbed capacity 2 kW COP EN14511 Cooling A35W23/18 Cooling capacity 3 KW Total absorbed capacity 3 kW EER EUROVENT 4 ESEER…
-
OPERATING LIMITS
Sizes COOLING EXTERNAL EXCHANGER Input air max. temperature INTERNAL EXCHANGER Output water max. temperature Output water min. temperature HEATING EXTERNAL EXCHANGER Input air max. temperature Input air min. temperature INTERNAL EXCHANGER Output water min. temperature Output water max. temperature…
-
SOUND LEVELS
Sound Power Level (dB) Size Octave band (Hz) Sound pressure level 1000 2000 4000 8000 Sound power level dB(A) Measures according to EN 3744 regulations, with respect to the EUROVENT 8/1 certification. dB(A) The sound pressure is measured at 1 m from the external surface of the unit in open field…
-
DIMENSIONS
(1) condensate discharge (2) installation input (3) installation output (4) domestic hot water input (5) domestic hot water output (6) installation charge (7) power input (8) E.P. and maintenance (9) outlet air direction (10) inlet air direction (11) compressor (12) finned exchanger (13) fan SIZE…
-
CLIVET SPA
Feltre (BL) ITALY Tel. + 39 0439 3131 Fax + 39 0439 313300 info@clivet.it CLIVET ESPAÑA S.A. (Madrid) SPAIN Tel. + 34 91 6658280 Fax + 34 91 6657806 info@clivet.es CLIVET UK LTD Fareham (Hampshire) U.K. Tel. + 44 (0) 1489 572238 Fax + 44 (0) 1489 573033 info@clivet-uk.co.uk CLIVET NEDERLAND B.V.…