Инструкция на Чиллеры Clivet серии WBAN... для наружной установки
Чиллеры Clivet серии WBAN 41-61-81 для наружной установки. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
WBAN 41-61-81
AIR TO WATER HEAT PUMP FOR OUTDOOR INSTALLATION OPERATION IN HEATING-ONLY MODE Installation and Use Manual M2E240P5-03 12/09/07
-
UNIT IDENTIFICATION
SERIAL NUMBER LABEL The units are identified by the serial number label shown here. The label lists the type of unit (series and size), serial number, year of manufacture, number of electrical diagram, main technical data, logo and address of the manufacturer. The label is placed on the unit…
-
INSTRUCTIONS FOR THE USER
• This is a partial sintex of the information provided in the manual; carefully read this manual • Carefully read this manual. Keep it with the electrical diagram. Make it available to technicians for servicing. • Ask the installer for training on start-up, shutdown, changing set points, placing in…
-
TO DO FOR
Some functions are active only if they are enabled during installation (remote ON-OFF, remote SUMMER WINTER change, remote ECO, sanitary hot water, set point compensation). Check with the installer about the configuration used. Start the unit LONG pressing of the ON/OFF button Choose the WINTER mode…
-
To reset the current alarm
ONLY AFTER THE CAUSE ELIMINATION ! TEST + ON/OFF contemporary for some seconds Control parameter 117 Modify the water temp. in HEATING Control parameter 33 Modify the water temp. in ECO HEATING Control parameter 30 Modify the water temp. in MAINTENANCE heating Control parameter 43 Only by SERVICE…
-
GENERAL WARNINGS
MANUAL PURPOSE This manual has been designed to enable the unit to be installed, started up and maintained correctly. MANUAL INSTRUCTIONS It is essential to observe these instructions. The manufacturer declines all liability for any damage that may be caused whether directly or indirectly to persons…
-
RESIDUAL RISKS
GENERAL This section lists some of the more common situations which, being beyond the control of the manufacturer, could be a source of risk to persons or property. DANGER AREA The figure below highlights the area in which only authorised personnel may operate. • External danger zone, identified by…
-
Contact with parts that could become live when the unit is
started up can result in electric shock, burns or death by electrocution. When there is no need for circuits to be powered up, set the isolating switch on the power line to the OFF position, padlock it and post a warning sign. MOVING PARTS Contact with the fan rotors can cause injury. Before…
-
Physical and
chemical properties Physical state (20°C): liquid gas Colour: colourless Smell: Slightly similar to ether; pH: not applicable. Boiling point/interval: -42,4 °C Melting point/interval: Not inflammable in test conditions Vapour pressure: (25°C): 1.13 Mpa (11,3 bar) a (50°C): 2.11 Mpa (21,1 bar) a…
-
RECEPTION
INSPECTION UPON RECEPTION Check on arrival that the unit has not suffered damage during transit and that it is complete in every part as specified in the order. In the event of visible damage/deficiencies being discovered, make a note immediately on the delivery document with the comment…
-
POSITIONING
GENERAL For installing air-conditioning systems, it is necessary to consider the following: • the technical spaces necessary for the machine and system • the place where the machine will be installed • the transport of thermal carrier fluids and relevant connections to the unit: o water o air o…
-
Install the unit raised off the ground and on a sturdy base
Consider the maximum depth that snowfall might reach. ! ! 2A ! 1. elastic joint 2. floating floor 3. soundproofing Tree ! A Consider clearances and direction of expelled air. Keep the coil clean. Avoid zones with leaves / dirt / corrosives. Prevent the transmission of vibrations. ! Provide…
-
WATER CONNECTIONS
GENERAL Piping must be designed with the least possible number of bends and head variations. If the pressure chute of the installation is above the useful prevalence of the pump, the water delivery capacity is reduced as well as, as a consequence, the thermal exchange and the yield. INTERCEPTING…
-
DIAGRAM OF RECOMMENDED USE SIDE CONNECTION
Depending on the type of machine and the selected setup, some components may be integrated into the unit. P F 10 8 P 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Charged system pressure switch vent circulating pump / pump expansion tank safety valve flow switch pressure switch / thermometer filter…
-
ELECTRICAL CONNECTION
refer to standard units. In the event of differences between the data of the registration plate and the data shown in this manual, as well as in the technical chart, please refer to the DATA SHOWN IN THE REGISTRATION PLATE. GENERAL The characteristics of the electrical lines and relevant components…
-
SYSTEM COMPOSITION
The system is composed of the following modules; some are optional that could be not installed. Some are supplied in packages separate from the unit: check the shipping document descriptions USER AMBIENT TERMINAL Permits setting the unit function modes (cooling – heating, ECO) and to display the…
-
FUNCTIONAL CONNECTIONS
FOR ALL THE CONNECTIONS MAKE REFERENCE TO THE ELECTRICAL PANEL SUPPLIED WITH UNIT Use voltage-free remote control devices that are suitable to commutate very low loads (12V, 10mA) Few inputs must be activated by configuration parameters whose access is reserved to authorized assistance centres (in…
-
ADDITIONAL HEATING ELEMENT T ext It is possible to control an external element for additional heating, typically electric resistances. The control can be: • ON-OFF ( max 1 A ) • modulating WITH SIGNAL 0-10 V T out1 (in this case a plug-in expansion module is necessary, an optional that must be…
-
COUPLING WITH BOILER This function allows the unit to be coupled to a boiler with "high temperature" thermostat setting (70 °C for example), i.e., with a working point above the operating limits of the unit. Text T out1 The coupling to the boiler is managed using: • the fresh air temperature probe…
-
SANITARY HOT WATER: COMPENSATION OF THE SET POINT FOR OUTSIDE TEMPERATURE*
The set point can be compensated according to the outside temperature in 2 modes: 1. hot season thermal efficiency curve when the outside temperature is high, the sanitary hot water set point is decreased; in this manner the thermal efficiency is increased curve A in the graph the compensation is…
-
The water set point at the radiant panels can be managed in three ways
1. the valve is managed to maintain the supply temperature at par 192 value. 2. calculated automatically in function of the fresh air temperature; two set are calculated. This configuration is obtained setting par 190=1 HEATING SET POINT P 199 P 198 P 201 P 200 3. T EXT the installation maintains…
-
UNIT INTERFACING VIA RS 485 Below the indications for the serial connection ; refer anyway to the CLIVET “RS 485 NETWORKS – GUIDELINES” document and ask for the COMMUNICATION PROTOCOL about the COMPACT electronics - The total length of each single serial line, don’t have to be over 1000 metres The…
-
START-UP
ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF THE SYSTEM. ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. PRELIMINARY CHECKS ELECTRICAL SYSTEM Before checking…
-
EVAPORATOR WATER FLOW RATE
VERIFY TENSIONS – ABSORPTIONS Check that the temperatures of the fluids are included in the WORKING LIMITS. If the controls of the previous paragraphs are positive, it is possible to restart the unit. For information on the control panel, refer to the paragraph CONTROL. While the unit is working…
-
CONTROL
USER KEYPAD The keyboard allows visualizing and changing the functioning conditions of the unit. The service keyboard is needed to visualize or modify the functioning parameters. BUTTON FUNCTION COMFORT mode 1° set - point HEATING ECONOMIC mode 2° set-point COOLING ON / OFF LONG press LED operating…
-
ALARMS
FLASHING LED: there is an anomaly at the AUTOMATIC reset FIXED LIGHT LED: there is an anomaly at the MANUAL reset ALARM RESET: TEST + ON/OFF keys pressed simultaneously for more than 2 seconds. Alarm type: ELECTRICAL CIRCUIT ALARM REFRIGERANT CIRCUIT ALARM Return probe Supply probe Radiant panel…
-
S
-
VISIBLE STATUS FROM REMOTE KEYBOARD OR SERVICE KEYBOARD
UNIT STATA MENU INDICE DESCRIPTION VALUE °C Current Set Point Temperature drop in degrees centigrade given by the compressor including compensations, if any Resource activation timer When this value reaches the value fixed at the next status (TimeScan), the thermal regulator will compare the input…
-
ALARMS
BEFORE RESETTING THE ALARM, IDENTIFY AND ELIMINATE THE CAUSE OF ITS ACTIVATION. REPEATED RESETS CAN CAUSE IRREVERSIBLE DAMAGES. The ALARMS show a potentially dangerous situation for machine safety. Before resetting the alarm, discover and remove the cause: repeated resetting could cause irreversible…
-
ROUTINE MAINTENANCE
BEFORE UNDERTAKING ANY SORT OF MAINTENANCE OR CLEANING, DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE UNIT, AND ENSURE THAT OTHER PEOPLE CANNOT RE-CONNECT IT . All equipment is subjected to wear out. cleaning activities; otherwise, controls have to be performed by specialized technicians…
-
MAINTENANCE INSPECTIONS
Foresee inspection assistance carried out by authorized centers or by qualified personnel. The inspections should be carried out at least: • - Every year for only the cooling units • - Every six months for the cooling and warming units The frequency, however, depends on the use: in the event of…
-
REFRIGERANT TABLES
THIS SECTION IS DEVOTED ONLY TO QUALIFIED TECHNICIANS THAT KNOW THE FOLLOWING: • THE OPERATIONAL PRINCIPLES OF THE REFRIGERATING CIRCUIT OPERATION • THE MODES OF DETECTING TEMPERATURE AND PRESSURE • THE RISKS RELEVANT TO THESE OPERATIONS The data of the tables allow the testing of the refrigerating…
-
Pg
-
TROUBLESHOOTING
THE OPERATIONS MUST BE CARRIED OUT BY TECHNICAL QUALIFIED PERSONNEL HAVING THE REQUISITES UNDER LAW REQUISITES AND IN CONFORMITY WITH THE SAFETY REGULATIONS IN FORCE. THE INTERVENTIONS WITHIN THE WARRANTY PERIOD WILL BE CARRIED OUT BY AUTHORIZED SERVICE CENTERS. BEFORE RESETTING AN ALARM, IDENTIFY…
-
DECOMMISSIONING OF THE UNIT
DISCONNECTING THE UNIT DISMANTLING AND DISPOSAL The units must be disconnected by authorised personnel, who before proceeding must first read the Residual Risks section in this manual. THE UNIT MUST ALWAYS BE SENT TO AUTHORISED CENTRES FOR DISMANTLING AND DISPOSAL. Before disconnecting the unit, the…
-
TECHNICAL DATA
Sizes Heating Heat output Compressor power input Total power input COP Compressor Type of compressors No. of Compressors Std Capacity control steps Oil charge (C1) Refrigerant charge (C1) Refrigerant circuits External exhcanger Type of internal exchanger No. of internal exchangers Water flow-rate…
-
OPERATINE LIMITS (HEATING)
Sizes EXTERNAL EXCHANGER Max air temperature return Min air return temperature (W.B.) INTERNAL EXCHANGER Max. water supply temperature Min. water supply temperature Water thermal head (min / max) 1 2 °C °C 3 4 °C °C °C -18 40 -17 -17 60 20 3/8 Water thermal head = 5°C ATTENTION: IN CASE OF…
-
INTERNAL EXCHANGER PRESSURE DROP
DP (kPa) 60 50 Q = WATER FLOW DP = AVAILABLE PRESSURE 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q (l/s) 1.1 1.2 1.3 1.4 1.5 1.6 PUMP PERFORMANCE DP (kPa) Q = WATER FLOW DP = AVAILABLE PRESSURE 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 41 0,9 Q (l/s) 1,0 1,1 1,2 1,3 1,4 1,5 1,6 1,7 81 61 SOUND LEVELS Sound pressur…
-
DIMENSIONS
-
Size 81
-
CLIVET SPA
Feltre (BL) ITALY Tel. + 39 0439 3131 Fax + 39 0439 313300 info@clivet.it CLIVET ESPAÑA S.A. (Madrid) SPAIN Tel. + 34 91 6658280 Fax + 34 91 6657806 info@clivet.es CLIVET UK LTD Fareham (Hampshire) U.K. Tel. + 44 (0) 1489 572238 Fax + 44 (0) 1489 573033 info@clivet-uk.co.uk CLIVET NEDERLAND B.V.…