AquaEdge®
19XR Two-Stage High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with PIC 5 Controls Version 3.3 Controls Operation and Troubleshooting CONTENTS Page SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . .1,2 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .…
-
system controls cooling load within the set point plus or
minus the dead band by sensing the water or brine temperature and regulating the inlet guide vane via a mechanically linked actuator motor, and regulating VFD (variable frequency drive) speed if the compressor is powered by a variable speed drive. The guide vane is a variable flow pre-whirl assembly…
-
Carrier Service Call: 1-800-379-6484
- POWER SUPPLY CONNECTOR 2 - LEN CONNECTOR 3 - CCN CONNECTOR 4 - ETHERNET CONNECTOR 5 - USB CONNECTOR 2 1 PIC 5 BOTTOM VIEW a19-2139 PIC 5 CONTROL INTERFACE Fig. 1 — PIC 5 Control Interface and Connectors Table 1 — ISM Input/Output Descriptions DESCRIPTION Communication Compressor Run Contact…
-
Table 3 — 19XR6/7 IOB1 Connections
DESCRIPTION CHANNEL TERMINAL TYPE OPTIONAL Entering Chilled Water Temperature AI1 J16-1,5 5 k — Leaving Chilled Water Temperature AI2 J16-2,6 5 k — Entering Condenser Water Temperature AI3 J16-3,7 5 k — Leaving Condenser Water Temperature AI4 J16-4,8 5 k — Evaporator Refrigerant Liquid…
-
Table 5 — 19XR6/7 IOB3 Connections
DESCRIPTION Low Speed ME Bearing Temperature Low Speed CE Bearing Temperature High Speed ME Bearing Temperature High Speed CE Bearing Temperature Remote Reset Temperature Guide Vane 1 Actual Position Common Chilled Water Supply (CHWS) Temperature Auto Water Temperature Reset Common Chilled Water…
-
NOTE: A suitable 24 VAC relay is Carrier part number
19XV05005503. Carrier recommends using a relay with a contact rating of 10 amp sealed RMS or greater. LEGEND FOR FIG. 2-6 A19-2265 19XV05005503 BASE DIMENSIONS (REFERENCE) DIMENSIONS IN INCHES [MM] PART NO. 19X4003501 19X4003502 19X4003503 19X4003504 19X4003505 19X4003506 NO. OF PIN 2 PIN 4 PIN 6…
-
ATATAIATATAIATAIATATATA
-
NOTE
-
Fig. 6 — 19XR6/7 Control Wiring
-
Fig. 8 — 19XR6/7 Control Panel, IOB Layer
1TB 2TB 1TB — CUSTOMER 3-PHASE POWER CONNECTION FOR CONTROL PANEL 2TB — FIELD WIRING CONNECTION FROM STARTER Fig. 9 — 19XR6/7 Control Panel, Bottom Layer 11
-
Sensors
Controls Outputs PRESSURE TRANSDUCERS — Pressure transducers measure and control the pressures in the unit. These electronic sensors deliver 0 to 5 VDC. The transducers can be calibrated through the controller. The pressure transducers are connected to the IOBs. See Table 7. EVAPORATOR/CONDENSER…
-
• Data/configuration screens, which list the parameters by
type • Operating mode selection screen • Password entry and language selection screen • Parameter modification screen • Time schedule screen If the interface is not used for a long period, it goes into screensaver mode and displays a black screen. However, the control is always active and the unit…
-
When a start-up mode is selected, a status screen displays
the progress of the start-up sequence (Fig. 14). Messages — The Set Point screen, On/Off screen, User Login screen, and Main Menu screens described in the next sections may display status messages at the bottom of the screen. See Table 10. Table 10 — Status Messages MESSAGE COMMUNICATION FAILURE!…
-
Configuration Screen — To access the Configuration menu,
press the Configuration icon on page 2 of the Main Menu (User, Service, or Factory access level). The Configuration menu opens. Then press the General Configuration icon on the Configuration menu. Press the arrows at the bottom right corner to navigate through pages. See Fig. 18. (Certain…
-
Schedule Menu Screen — To access the Schedule menu
screen, press on the Configuration menu screen. Select Local Schedule, Ice Build Schedule, or Network Schedule as applicable. Press the arrows at the bottom right corner to navigate through the time periods. See Fig. 20. Evaporator Status *MENUOCC1 - Local Schedule Entering Chilled Water Leaving…
-
Economizer Status
Damper Control Type Target Damper Position Actual Damper Position Economizer Pressure Evaporator Pressure Pressure Difference a19-2310 NOTE: The pressure difference shown in this screen is the difference between economizer pressure and evaporator pressure. Fig. 29 — Envelop Control /HGBP (Hot Gas…
-
Table 12 — Pre-Start Alerts and Alarms
Table 11 — Compressor Run Status STATUS STATUS DESCRIPTION NO. NAME 0 OFF STATSTOP is STOP, no alarm. 1 CTLTEST Controls Test is active. 2 PUMPDOWN Pumpdown is active. 3 LOCKOUT Lockout is active. Recycle shutdown completed on low 4 RECYCLE load in effect until the need for cooling resumes…
-
The set point is determined by the heat/cool mode, EWT
(entering water temperature) option, and ice build option. See Table 13. Chiller Shutdown Sequence — Chiller shutdown begins if any of the following occurs: • Local OFF button is pressed • A recycle condition is present (see the previous section) • The time schedule has gone into unoccupied mode…
-
Ramp Loading will be used regardless of user configuration
and the minimum loading rate (1^F/min) will be used. Two methods of ramp loading are available: temperature ramp loading and motor load ramp loading. If VFD OPTION is set to VFD and increased capacity is needed, the control will first try to increase IGV TARGET POSITION if it has not reached the…
-
PIC 5 supports 3 different types of EC/HGBP control
valve types: 1. Continuous; modulating valve controlled by two contactors, one to open and another to close. If both contactors are open the valve will hold its position. Valve has a feedback signal for fully open/closed position. 2. On/off; valve controlled by one contact. It has no position…
-
RECYCLE CONTROL — The chiller may cycle off and
wait until the load increases to restart when the compressor is running in a lightly loaded condition. This normal cycling is known as “recycle.” In cooling mode, a recycle shutdown is initiated when either of the following conditions is true: • Leaving chilled water temperature (or entering chilled…
-
Table 15 — Override Parameters
OVERRIDE CONDITION High condenser pressure override (Unit Type Heat/Cool=1 in Configuration Menu Factory Parameters. Before configuring Unit Type = 1 the condenser shell side must be verified to be 300 psig design or higher.) High condenser pressure override (Unit Type Cool Only = 0 in…
-
COOLING TOWER CONTROL — If WATER PRESSURE
OPTION in the CONF_OPT table is set to 1 or 2, there will be another optional hydraulic control I/O board in the PIC 5 control system to allow PIC 5 control for the water pumps and cooling tower fans (high speed and low speed). The cooling tower fans are controlled by the pressure difference between…
-
PRESSURE - Pressures
Pressure Sensor Calib Fig. 32 — Pressures Screen, Page 1a19-2233 a19-2236 Fig. 35 — Pressure Sensor Calib Screen, Page 2 PRESSURE - Pressures 2. Each transducer is supplied with 5 vdc from the IOB. Calibration is done by selecting the appropriate Pressure Sensor option on the Pressure Sensor Calib…
-
TEMP_CAL - Temp Sensor Calib
a19-2316 Fig. 37 — Maintenance Menu Calibration Fig. 39 — Temp Sensor Calib Screen, Page 2 2. Place the temperature sensor in a 32 F (0° C) water solution. 3. Read the sensor raw temperature on the Maintenance screen. 4. Calculate the offset to be applied as follows: 32 – sensor raw temp (°F)…
-
3. Go to Main Menu Maintenance Menu ISM
Calibration. 4. Select J6 0-10V Input. The ISM_CAL2 screen is displayed. See Fig. 42. ISM_CAL1 - J8B 4-20mA Output ISM_CAL2 - J6 0-10V Input a19-2318 Fig. 41 — ISM_CAL1 Screen 3. Set Calibration Enable to Enable. 4. Input a test output mA value. The controller will make the ISM output this mA value…
-
PROGNOSTICS — This advanced diagnostic and prognostic function is designed for service and to help resolve problems before they affect operating efficiency and the chiller life. The CONF_PRG (Prognostics Config) screen is available from the Alarm Menu. See Fig. 47 and 48. EMAILCFG - E-Mail…
-
threshold set in the Trans Calib Threshold option generates
an alert 161 that a calibration is required. The comparison is done for all of the transducers. A value more than the configurable threshold displays the red light in for Refrigerant Transducer Calibration in the Prognostics status screen. A value more than 0.9 times the configurable threshold…
-
Pumpdown/Lockout — The Pumpdown/Lockout fea-
ture prevents compressor start-up when there is no refrigerant in the chiller. To access this function one must be logged in as Advanced User/Service or higher. The feature can accessed from the Maintenance Menu. See Fig. 54. Pumpdown/Lockout Chilled Water Pump Chilled Water Flow Evaporator Pressure…
-
Oil Stir — If Factory Parameters Marine Option is enabled, when chiller is not running, the oil pump will be switched on for 30 seconds every 3 hours whether oil heater is on or off. When oil stir is in progress, oil heater will be switched off. Trending Power Request — If Factory Parameters …
-
Resetting Alarms — When the cause of the alarm has
been identified and corrected, the alarm can be reset either automatically or manually (depending on the type of alarm). See Table 17 for alarms that are eligible for automatic reset. In the event of a power supply interrupt, if Auto Restart Option is set to ENABLE in the Option Configuration menu…
-
Table 17 — PIC 5 Alarm Codes
ALARM CODE (ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE TEMPERATURE SENSOR FAULTS Alm-200 ALM-200 Sensor Fault — Leaving Chilled Water Automatic if the temperature measured by the sensor returns to normal Unit shuts down Alm-201 ALM-201 Sensor Fault — Entering…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE TEMPERATURE SENSOR FAULTS (CONT) Alm-211 ALM-211 Sensor Fault — High Speed Comp End Bearing Temp Automatic if the temperature measured by the sensor returns to normal Unit shuts down Alm-212 ALM-212 Sensor Fault…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE PRESSURE TRANSDUCER FAULTS (CONT) Alm-218 ALM-218 Sensor Fault — Diffuser Pressure Automatic if the voltage measured by the sensor returns to normal Unit shuts down Alm-219 ALM-219 Sensor Fault — Oil Sump Pressure…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE PRESTART FAILURES (CONT) Alm-234 ALM-234 Prestart Failure — Low Line Voltage Manual Unit shuts down. Compressor is not allowed to start. Alm-235 ALM-235 Prestart Failure — High Line Voltage Manual Unit shuts down.…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE PROTECTIVE LIMITS (CONT) Alm-253 ALM-253 Protective Limit — High Discharge Temperature Manual Unit shuts down. Alm-254 ALM-254 Protective Limit — Low Evaporator Refrigerant Temperature Manual Unit shuts down. Alm-255…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE PROTECTIVE LIMITS (CONT) Alm-257 ALM-257 Protective Limit — High Condenser Temperature Manual Check CONDENSER PRESSURE. Check for high condenser water temperatures, low water flow, fouled tubes. Check for division…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE PROTECTIVE LIMITS (CONT) Confirm that Diffuser Option in SRD Configuration screen has not been Enabled if compressor does not have a split ring diffuser. May indicate rotating stall condition. Check rotating stall…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION ACTION TAKEN BY CONTROL RESET TYPE POSSIBLE CAUSE COMMUNICATION FAILURE Alm-282 Alm-283 Alm-284 ALM-282 Protective Limit — Displacement Switch ALM-283 Protective Limit — High Pressure Switch ALM-284 Protective Limit — Power Feedback Loss Manual Unit shuts down.…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE INTEGRATED STARTER MODULE ALARMS (CONT) Alm-402 ALM-402 ISM Fault — High Line Voltage Alm-403 ALM-403 ISM Fault — Low Manual (Swift Restart eligible) Line Voltage Alm-404 ALM-404 ISM Fault — Line Manual (Swift…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE INTEGRATED STARTER MODULE ALARMS (CONT) Alm-407 ALM-407 ISM Fault — Motor Locked Rotor Trip Manual Unit shuts down. Alm-408 ALM-408 ISM Fault — Starter Lock Rotor Trip Manual Unit shuts down. Alm-409 ALM-409 ISM…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE INTEGRATED STARTER MODULE ALARMS (CONT) Alm-413 Alm-414 Alm-415 ALM-413 ISM Fault — Start Contact Fault ALM-414 ISM Fault — Transition Contact Fault ALM-415 ISM Fault — Oil Pump/High Pressure Switch Failure Manual…
-
CODE
(ALARMRST) Alm-423 Alm-424 Alm-425 Alm-426 Alm-427 Alm-428 Alm-429 Alm-430 Alm-431 Alm-432 Alm-433 Alm-434 Alm-435 Alm-436 Alm-437 Alm-438 Alm-439 Alm-440 Alm-441 ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE INTEGRATED STARTER MODULE ALARMS (CONT) ALM-423 ISM Fault — Cal…
-
CODE
(ALARMRST) ALARM TEXT DESCRIPTION RESET TYPE ACTION TAKEN BY CONTROL POSSIBLE CAUSE INTEGRATED STARTER MODULE ALARMS (CONT) Alm-442 ALM-442 VFD Fault — Stop Fault Manual Alm-443 ALM-443 VFD Fault — Rectifier Overtemp Manual Alm-444 ALM-444 VFD Fault — Inverter Overtemp Manual Alm-445 ALM-445 VFD…
-
Table 18 — PIC 5 Alert Codes
ALERT CODE (ALARMRST) ALERT TEXT DESCRIPTION ACTION TAKEN BY CONTROL PRESTART ALERTS RESET TYPE Alt-100 ALT-100 Prestart Alert — Starts Limit Exceeded Automatic when the situation returns to normal Turn on Alert relay. Alt-101 ALT-101 Prestart Alert — Low Oil Temperature Automatic when the situation…
-
Table 18 — PIC 5 Alert Codes (cont)
ALERT CODE (ALARMRST) ALERT TEXT DESCRIPTION ACTION TAKEN BY CONTROL SENSOR ALERTS (CONT) RESET TYPE Alt-132 ALT-132 Sensor Alert — Automatic when the situation Entering Chilled Water Press returns to normal Alert relay is ON. Alt-133 ALT-133 Sensor Alert — Leaving Cond Water Press Automatic when…
-
Table 18 — PIC 5 Alert Codes (cont)
ALERT CODE (ALARMRST) Alt-157 Alt-158 Alt-159 Alt-160 Alt-161 Alt-162 Alt-164 Alt-165 Alt-166 Alt-167 Alt-169 ACTION TAKEN BY CONTROL PROCESS ALERTS (CONT) ALERT TEXT DESCRIPTION ALT-157 Process Alert — High Condenser Pressure Chiller Off ALT-158 Process Alert — Prognostic Alert ALT-159 Process…
-
Event States — An event state is a specific set of condi-
TOUCH SCREEN SETTINGS FOR THE CONTROLLER tions that the controller may encounter when controlling the chiller. Event states are repeatable, predictable, and represent known states of the control. When the control is in a particular state, a unique message is associated with that state. The event…
-
If needed, press “Edit Connection.” See Fig. 62. Default parameters are shown; to modify, press a specific parameter. To change IP address manually, press TCP/IP Address to display the TCP/IP Address screen. See Fig. 59. TCP/IP Address Network . . Help . i 103 <= clr 1 2 hmi.html 3 127.0.0.1 => 4…
-
General Display Settings — To set contrast, screen-
saver, screen image rotation, and touch screen calibration, press Display on the Setup screen (see the section Touch Screen Settings for the Controller on page 49). The Display screen opens. See Fig. 67. LEGEND — Firmware version that is loaded in panel — Boot loader version that is loaded in panel…
-
The intranet site of the unit is the IP address (see Unit IP
Address on page 49). NOTE: The unit cannot automatically obtain the network parameters via a DHCP server. COMMUNICATION PROBLEMS Hardware Problems — See Table 20 for potential communication issues caused by hardware problems. Web Interface Problems — See Table 21 for potential communication issues…
-
In the example shown in Fig. 71, the PC receives four negative responses (request timed out)
Use the following methods to troubleshoot: UNIT IS POINT-TO-POINT CONNECTED TO A PC — Ensure controller is powered on prior to configuration and check Ethernet connection and PC Network Interface Card (NIC). NOTE: In addition to the following procedure, it may be necessary to check the Ethernet…
-
If a proxy server is used, add the unit IP address to the exceptions list of the proxy server (advanced proxy configuration). See Fig. 73. a19-2176 Fig. 74 — Java Control Panel a19-2175 • Network settings: In the Java Control Panel, click Network Settings. Select a direct connection to bypass the…
-
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE
VFD General VFD General Parameters Parameters Fig. A — Screen Structure, Basic Level (All) Access (No Password Required) 55
-
Main Menu Description
ICON DISPLAYED TEXT* ACCESS ASSOCIATED TABLE PAGE NO. General Parameters All GENUNIT 57 Temperatures All TEMP 58 Pressures All PRESSURE 58 Inputs Status All INPUTS 59 Outputs Status All OUTPUTS 60 Hydraulic Status All HYDRLIC 61 Run Times All RUNTIME 62 Modes All MODES 62 Setpoint User SETPOINT 62…
-
General Parameters
CCN TABLE NAME: GENUNIT PIC 5 PATH: Main Menu General Parameters LINE PIC 5 DESCRIPTION Control Mode 0 = Local, 1 = Network 2 = Remote, 3 = Local Sched Compressor1 Run Status Deter Start Stop Command Network: Cmd Start/Stop Network:Cmd Occupied Cooling / Heating Select Control Point Control Point…
-
Temperatures
CCN TABLE NAME: TEMP PIC 5 PATH: Main Menu Temperatures LINE PIC 5 DESCRIPTION Entering Chilled Water Leaving Chilled Water Entering Condenser Water Leaving Condenser Water Evap Sat Refrig Temp Evap Refrig Liquid Temp Evaporator Approach Condenser Approach Cond Sat Refrig Temp Comp Discharge Temp…
-
Inputs Status
CCN TABLE NAME: INPUTS PIC 5 PATH: Main Menu Inputs Status LINE PIC 5 DESCRIPTION Compressor Start Contact Compressor Run Contact Damper Valve Fully Closed Damper Valve Fully Opened Damper Valve Status 0=Closed, 1=Interim, 2=Opened 3=Failure EC Valve Fully Closed EC Valve Fully Opened EC Valve…
-
Outputs Status
CCN TABLE NAME: OUTPUTS PIC 5 PATH: Main Menu Outputs Status LINE PIC 5 DESCRIPTION Diffuser Output Head Pres Output Chiller Status Output VFD Speed Output Oil EXV Output Oil EXV Target Oil Pump VFD Output mA Oil Pump VFD Target Head Pres Valve Tgt Pos Guide Vane 1 Output EC Valve Output mA Alarm…
-
Hydraulic Status
CCN TABLE NAME: HYDRLIC PIC 5 PATH: Main Menu Hydraulic Status LINE PIC 5 DESCRIPTION Chilled Water Pump Condenser Water Flow Cond Water Flow Value Entering Cond Water Pres Leaving Cond Water Pres Condenser Water Delta P Condenser Delta P Offset Cond Water Pulldown/Min Condenser Water Pump Chilled…
-
Run Times
CCN TABLE NAME: RUNTIME PIC 5 PATH: Main Menu Run Times LINE PIC 5 DESCRIPTION Starts in 12 Hours Compressor Starts Num Compressor Running Hrs After Service Hrs Stop to Start Timer Start to Start Timer Oil Lubrication Duration Oil Storage Duration Recy Startup in 4 Hours Swift Restarts in 1 Hour…
-
Navigation: MAIN MENU CONFIGURATION MENU
ICON Configuration Menu DISPLAYED TEXT ACCESS ASSOCIATED TABLE PAGE NO. Service Parameters Service SERVICE1 64 Surge Correction Config Service CFGSURGE 64 Protective Limit Config Service CFGLIMIT 65 Lab Test Forced Service LABONLY Factory only Option Configuration Service CONF_OPT 66 ISM…
-
Service Parameters
CCN TABLE NAME: SERVICE1 PIC 5 PATH: Main Menu Configuration Menu Service Parameters LINE PIC 5 DESCRIPTION Service Password Atmospheric Pressure GV1 Travel Limit GV1 Closure at Startup Controlled Fluid DB Derivative EWT Gain Proportional Dec Band Proportional Inc Band Maximum GV Movement…
-
Protective Limit Config
CCN TABLE NAME: CFGLIMIT PIC 5 PATH: Main Menu Configuration Menu Protective Limit Config LINE PIC 5 DESCRIPTION Evap Approach Alert Cond Approach Alert Cond Press Override Low Cond Press Override High Cond Press Cutout Low Cond Press Cutout High Evap Override Delta T Evap Refrig Trippoint High…
-
Option Configuration
CCN TABLE NAME: CONF_OPT PIC 5 PATH: Main Menu Configuration Menu Option Configuration LINE PIC 5 DESCRIPTION Auto Restart Option Common Sensor Option Water Pressure Option EC Valve Option 0 = No, 1= Cont 2 = On/Off, 3 = 4-20 mA EC Selection 0 = Disable, 1 = Surge 2 = Low Load, 3 = Comb ECV Open…
-
ISM Configuration
CCN TABLE NAME: CONF_ISM PIC 5 PATH: Main Menu Configuration Menu ISM Configuration LINE PIC 5 DESCRIPTION Communication Timeout Starter Type 0 = Full Volt, 1 = Reduced Volt 2 = Solid State, 3 = FS VFD Single Cycle Dropout Motor Rated Load Amps Motor Rated Kilowatts Motor Locked Rotor Trip…
-
Factory Parameters
CCN TABLE NAME: FACTORY PIC 5 PATH: Main Menu Configuration Menu Factory Parameters LINE PIC 5 DESCRIPTION 1 2 Factory Password Chiller Type 0=19XR6/7, 1=19XR2-5/E/D/V Unit Type 0 = Cool Only, 1 = Heat Machine Refrigerant Type 0 = R134a, 1 = Low Pressure Comp 0 = Single, 1 = Dual Cond Shell…
-
Unit Mount VFD
CCN TABLE NAME: CFGUMVFD PIC 5 PATH: Main Menu Configuration Menu General VFD Config LINE PIC 5 DESCRIPTION Compressor Speed 100% Rated Line Voltage Motor Nameplate Current Motor Nameplate Voltage Motor Nameplate RPM Motor Nameplate KW Skip Frequency 1 Skip Frequency 2 Skip Frequency 3 Skip…
-
IOB Configuration
-
Master Slave Configuration
CCN TABLE NAME: CONF_MS PIC 5 PATH: Main Menu Configuration Menu Master Slave Config LINE PIC 5 DESCRIPTION Slave Address Master/Slave Select 0=Disable, 1=Master, 2=Slave Chiller Connection Type 0=Parallel, 1=Series Middle Sensor Option Master Lead/Lag Select 0=Lead change to Lag Once Failed…
-
Schedule Menu
Navigation: MAIN MENU CONFIGURATION MENU SCHEDULE MENU ICON DISPLAYED TEXT ACCESS Local Schedule User Ice Build Schedule User Network Schedule User Fig. B — Schedule Menu and Submenus 72 ASSOCIATED TABLE
-
Holiday Menu
Navigation: MAIN MENU CONFIGURATION MENU HOLIDAY MENU The Holiday Menu has 16 submenus (HOLDY-01 to HOLDY_16), so it is possible to set 16 different holiday periods. For more information about holiday periods, see the Time Schedule section on page 24. Figure C below shows the Holiday Menu and a…
-
Date/Time Configuration
Navigation: MAIN MENU CONFIGURATION MENU DATE/TIME CONFIGURATION DATETIME - Date/Time Configuration a19-2351 Fig. E — Date/Time Configuration Menu Network Configuration CCN TABLE NAME: CONNECT PIC 5 PATH: Main Menu Configuration Menu CONNECT LINE RANGE DEFAULT VALUE* mb_opt ser_type…
-
Quick Test Menu
Navigation: MAIN MENU QUICK TEST Quick Test CCN TABLE NAME: QCK_TEST PIC 5 PATH: Main Menu Quick Test LINE PIC 5 DESCRIPTION Quick Test Enable GV 1 Calibration Enable GV1 Calibration Status 0=No Calibration or Failure 1=In Progress, 2=Completed Guide Vane 1 Actual Ohms Guide Vane 1 Actual mA…
-
Navigation: MAIN MENU MAINTENANCE MENU
ICON Maintenance Menu DISPLAYED TEXT* ACCESS ASSOCIATED TABLE PAGE NO. Capacity Control Service CAPACTRL 77 Override Control Service OVERRIDE 77 Surge Correction Service MAISURGE 78 Maintenance ISM Config Service ISM_MCFG 78 Maintenance VFD Config Service VFD_MCFG 79 Swift Restart Service MAISWRST…
-
Capacity Control
CCN TABLE NAME: CAPACTRL PIC 5 PATH: Main Menu Maintenance Menu Capacity Control LINE PIC 5 DESCRIPTION Total Error + Resets Control Point Error Controlled Water Temp Control Point Actual Set Point Entering Water Change DT Enter Water Temp Reset Leaving Water Temp Reset Discharge Gas Temp Reset…
-
Surge Correction
CCN TABLE NAME: MAISURGE PIC 5 PATH: Main Menu Maintenance Menu Surge Correction LINE PIC 5 DESCRIPTION Surge Region 0 = No, 1 = Low, 2 = High, 3 = Deadband, 4 = Noise Active Delta Tsat Calc Ref Delta Tsat High Eff Delta Tsat Amps Change Surge Prot Max Amps Change Value Surge Counts Surge…
-
Maintenance VFD Config
CCN TABLE NAME: VFD_MCFG PIC 5 PATH: Main Menu Maintenance Menu Maintenance VFD Config LINE PIC 5 DESCRIPTION VFD Config Conflict Delete VFD Config Yes = Delete, No = Keep Motor Rated Load Current Motor Nameplate Current Motor Nameplate Voltage Motor Nameplate RPM Motor Nameplate kW Compressor…
-
Master Slave
CCN TABLE NAME: MAIN_MS PIC 5 PATH: Main Menu Maintenance Menu Master Slave LINE PIC 5 DESCRIPTION Unit is Lead or Lag 0 = Disable 1 = Lead 2 = Lag Master Control Type 0 = Local 1 = Network 2 = Remote 3 = Local Sched Slave Control Type 0 = Local 1 = Network 2 = Remote 3 = Local Sched Lead Lag…
-
ISM Status
CCN TABLE NAME: MAIISMC PIC 5 PATH: Main Menu Maintenance Menu ISM Status LINE PIC 5 DESCRIPTION Single Cycle Dropout Phase Loss Over Voltage Under Voltage Current Imbalance Voltage Imbalance Overload Trip Locked Rotor Trip Starter LRA Trip Ground Fault Phase Reversal Frequency Out of Range ISM…
-
Power Load Parameters
CCN TABLE NAME: POWER_O PIC 5 PATH: Main Menu Maintenance Menu Power Load Parameters LINE PIC 5 DESCRIPTION VLF Load Current Percent VFD Load Current Ground Fault Current Motor Current Imbalance% Motor Actual Frequency Motor Target Frequency DC Bus Voltage DC Bus Voltage Reference Load Current…
-
UM VFD Status
CCN TABLE NAME: VFD_STAT PIC 5 PATH: Main Menu Maintenance Menu UM VFD Status LINE PIC 5 DESCRIPTION Single Cycle Dropout Line Current Imbalance High Line Voltage Low Line Voltage Low DC Bus Voltage High DC Bus Voltage VFD Power On Reset Ground Fault Line Phase Reversal Motor Overload Trip Start…
-
Maintenance Others
CCN TABLE NAME: MAIOTHER PIC 5 PATH: Main Menu Maintenance Menu Maintenance Others LINE PIC 5 DESCRIPTION 5V Sensor Power Monitor Evap Pres Trans Volts Cond Pres Trans Volts Econ Pres Trans Volts Diffuser Pres Tran Volts Oil Sump Pres Tran Volts Oil Sup Pres Trans Volts Evap Enter Water Volts…
-
Maintenance IOB
CCN TABLE NAME: MAIIOB PIC 5 PATH: Main Menu Maintenance Menu Maintenance IOB LINE PIC 5 DESCRIPTION IOB1 Power Supply Volt IOB1 Num Peak Prev Sec IOB1 Low Voltage Flag IOB1 24VAC Fuse Status IOB2 Power Supply Volt IOB2 Num Peak Prev Sec IOB2 Low Voltage Flag IOB2 24VAC Fuse Status IOB3 Power…
-
Pressure Sensor Calib (PRES_CAL) Menu Description
Navigation: MAIN MENU MAINTENANCE MENU PRESSURE SENSOR CALIB ICON DISPLAYED TEXT ACCESS ASSOCIATED TABLE PAGE NO. Evap Pressure Sensor Service PRSCAL01 87 Cond Pressure Sensor Service PRSCAL02 87 Eco Pressure Sensor Service PRSCAL03 87 Diff Pressure Sensor Service PRSCAL04 87 Oil Sump Pressure…
-
Evap Pressure Sensor
CCN TABLE NAME: PRSCAL01 PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Evap Pressure Sensor DEFAULT LINE PIC 5 DESCRIPTION CCN NAME RANGE VALUE* 1 Evap Pressure Sensor 2 Calibration Enable cal_en DSABLE/ENABLE DSABLE 3 Current Pressure cur_pres 4 Calib Press1 (0 PSI) cal_p1 9…
-
Oil Sump Pressure
CCN TABLE NAME: PRSCAL05 PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Oil Sump Pressure LINE PIC 5 DESCRIPTION Oil Sump Pressure Calibration Enable Current Pressure Calib Press1 (0 PSI) Calib Press2 (100-250PSI) Calibrated Slope Calibrated Intercept Calibration Completed CCN…
-
Cond Entering Water P
CCN TABLE NAME: PRSCAL09 PIC 5 PATH: Main Menu Maintenance Menu Pressure Sensor Calib Cond Entering Water P DEFAULT LINE PIC 5 DESCRIPTION CCN NAME RANGE VALUE* 1 Cond Entering Water P 2 Calibration Enable cal_en DSABLE/ENABLE DSABLE 3 Current Pressure cur_pres 4 Calib Press1(0 PSI) cal_p1 9…
-
CCN TABLE NAME: ISM_CAL1 PIC 5 PATH: Main Menu Maintenance Menu ISM Calibration J8B 4-20mA Output LINE PIC 5 DESCRIPTION Calibration Enable ISM Output mA ISM Output Percent VFD Reading mA VFD Reading Percent Calibration Factor Calibration Completed CCN NAME cal_en ism_ma ismo_per vfd_ma…
-
System Status
CCN TABLE NAME: SYS_STAT PIC 5 PATH: Main Menu Maintenance Menu System Status LINE PIC 5 DESCRIPTION System Control Mode System Status Master Run Status Slave Run Status System Percent Load System KW System Control Point System Demand Limit Supply Liquid Temp Return Liquid Temp CCN NAME RANGE…
-
APPENDIX B — INPUT/OUTPUT BOARD (IOB) AND HUMAN MACHINE INTERFACE (HMI)
DIP SWITCH SETTINGS IOB Dip Switch Settings (Fig. F) IOB IOB-1 IOB-2 IOB-3 IOB-4 IOB ADDRESS SW1 SW1 SETTING (1 TO 4) 0000 1000 0100 1100 SW2 SETTING (1 TO 10) 0000000000 0000000110 0000010110 1100000110 IOB ADDRESS SW1 20 mA SHUNT SW2 20 mA SHUNT SW2 a19- a19-2135 IOB-1 Dip Switch Settings IOB…
-
APPENDIX B — INPUT/OUTPUT BOARD (IOB) AND HUMAN MACHINE INTERFACE (HMI)
DIP SWITCH SETTINGS (cont) HMI Dip Switch Settings — To access switches, remove the access cover on the back of the HMI panel. See Fig. G. a19-2130 Fig. G — HMI Access Cover Set the HMI dip switches as shown in Fig. H. a19-2131 Fig. H — HMI Dip Switch Settings 93
-
APPENDIX C — INPUT/OUTPUT BOARD (IOB) STATUS INDICATORS
• Microprocessor in boot mode: LED flashes at 0.2 seconds on, 0.2 seconds off Each independent communication port has a green status LED. The green LED is on when data is being transmitted by the board. All RS485 ports have a green LED. All control boards have LED indicators that show control board…
-
APPENDIX D — NETWORK CONFIGURATION
General: Net Protocol Extended Modbus Connector — Ethernet connector and CCN connector on PIC 5 controller can be configured to be a Modbus connector: Step 1: Configuration Menu Network Configuration, Modbus Option set to Enable Step 2: When the Modbus Server Type is set to 0(IP), Ethernet…
-
3. Insert the BACnet dongle into the connector. See Fig. O
CAUTION The components that make up the chiller controller include electronic components. These may generate or be damaged by electromagnetic interference such as electrostatic discharge (ESD). Technicians who do not have access to an ESD wrist strap on site should follow these recommendations in…
-
Compressor status is ASCII-coded. In order to obtain the
status from BACnet, statuses are assigned a BACnet code as shown in Table A. Modifying the Unit IP Address — Note that chang- ing IP address from the PIC 5 SETUP menu will require a manual reboot or power cycle of the PIC 5 controller in order to re-build the BACnet stack. For detailed instructions…
-
Table C — BACnet Object Table
OBJECT NAME OBJECT ID OPTION READ/WRITE DESCRIPTION ALARMRST_alarm_1 AV:68 RO Jbus Current Alarm 1 ALARMRST_alarm_2 AV:69 RO Jbus Current Alarm 2 ALARMRST_alarm_3 AV:70 RO Jbus Current Alarm 3 ALARMRST_alarm_4 AV:71 RO Jbus Current Alarm 4 RO Jbus Current Alarm 5 RO Comp1 Run State Val…
-
OBJECT NAME
OBJECT ID OPTION READ/WRITE DESCRIPTION GENUNIT_loc_occ BV:5 COV RO Local Schedule Occupied GENUNIT_statstop BV:1 COV RO Deter Start Stop Command HYDRLIC_CDW_FV AV:45 RO Cond Water Flow Value HYDRLIC_cdw_pd AV:46 RO Condenser Water Delta P HYDRLIC_CDWP BV:27 RO Condenser Water Pump HYDRLIC_CHW_FV…
-
OBJECT NAME
OBJECT ID OPTION READ/WRITE DESCRIPTION MAISURGE_surg_act AV:82 RO Surge Prevention Active MAISURGE_surg_pro AV:83 RO Surge Protection Active OUTPUTS_ALE BV:19 RO Alert Relay OUTPUTS_ALM BV:18 RO Alarm Relay OUTPUTS_CHST_OUT AV:41 RO Chiller Stat Output mA OUTPUTS_COMP_SR BV:20 RO Compressor Start…
-
OBJECT NAME
OBJECT ID OPTION READ/WRITE DESCRIPTION SETPOINT_EWT_OPT BV:39 RW EWT Control Option SETPOINT_ice_sp AV:112 RW Ice Build Setpoint SETPOINT_lcdw_sp AV:111 RW Heating LCDW Setpoint SETPOINT_lcw_sp AV:109 RW Cooling LCW Setpoint TEMP_cond_app AV:15 IR RO Condenser Approach TEMP_COND_SAT AV:16 COV, IR…
-
a19-2297
102 NOTE: This diagram is for reference only. See actual wiring diagram for details. 1TB T2 T6 T5 T4 T1 Fig. Q — Medium Voltage Across-the-Line ISM (Typical) COMPRESSOR MOTOR WYE START T3 - APPENDIX E — ISM WIRING DIAGRAMS
-
A19-2298
103 T2 T6 T5 T4 T1 Fig. R — Medium Voltage Autotransformer ISM (Typical) COMPRESSOR MOTOR WYE START T3 NOTE: This diagram is for reference only. See actual wiring diagram for details. 1TB - APPENDIX E — ISM WIRING DIAGRAMS (cont)
-
1TB
104 a19-2299 NOTE: This diagram is for reference only. See actual wiring diagram for details. T2 T6 T5 T4 T1 Fig. S — Medium Voltage Primary Reactor ISM (Typical) COMPRESSOR MOTOR WYE START T3 - APPENDIX E — ISM WIRING DIAGRAMS (cont)
-
a19-2372
Fig. T — One Line Diagram of Medium Voltage VFD Power (Typical) 105
-
CT INPUTS
ACTUAL VFD SPEED 120 VAC USE IOB CONNECTIONS A19-2373 PER JOB REQUIREMENTS SPEED REF OUT RS-485 SIO COM Fig. U — Medium Voltage VFD ISM I/O (Typical) 106
-
USE 8TB-9, 10 (IOB3)
Fig. V — Starter Field Wiring Schematic 107
-
© Carrier Corporation 2016
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53190041-01 Printed in U.S.A. Form 19XR-CLT-3T Pg 108 11-16 Replaces: 19XR-CLT-2T