Инструкция на Программа Carel FLSTDmSCHE для чиллеров с винтовыми компрессорами
Программное обеспечение FLSTDmSCHE для управления чиллерами с винтовыми компрессорами на контроллерах Carel. Руководство пользователя. Документ на английском языке.
Загружаем документ…
Текст инструкции
-
FLSTDmSCHE
-
IMPORTANT
CAREL bases the development of its products on decades of experience in HVAC/R, on the continuous investments in technological innovations to products, procedures and strict quality processes with in-circuit and functional testing on 100% of its products, and on the most innovative production…
-
1. NOTES
1.1 FLSTDmSCHE release notes SW version 1.0.57 03-02-2013 1.1.13 14-04-2014 1.1.22 30-05-2014 1.3.0 01-08-2014 1.3.2 08-10-2014 1.3.3 12-11-2014 Manual version 1.0 24-01-2013 1.1 15-04-2014 1.2 30-05-2014 1.3 01-08-2014 1.4 08-10-2014 1.5 12-11-2014 Description First official release (2 circuits)…
-
2. INTRODUCTION
2.1 Main features FLSTDmSCHE is the CAREL solution for managing chillers and heat pumps with screw compressors. Usability and display - Easy access to the machine configuration and management parameters with the menu system organised by device (available in the pGD1 terminal). There are three…
-
2.2 Field connections
Addr: 32 Addr: 31 pLAN protocol on port pLAN Addr: 1 Port BMS2 Remote terminal Carel master protocol on port FB2 Addr: 198 Addr: 199 MASTER EVD circ.1 EVD circ.2 Carel master protocol on port FB2 Addr: 2 Addr: 198 Addr: 199 SLAVE EVD circ.3 +030221536 FLSTDmSCHE – rel 1.5 – 12/11/2014 8 EVD circ.4
-
2.3 Components and accessories
FLSTDmSCHE is optimized for pCO5+. The SW can manage up to two screw compressors per board (up to 4 compressors on two boards). Depending on the configuration and type of compressors a different model pCO5+ is necessary. 2.3.5 Pressure sensors 2.3.1 Table of pCO5+ codes Unit type screw compressor…
-
3. HARDWARE INSTALLATION
3.1 I/O configuration Analogue inputs U1 U2 U3 Master Slave Water inlet temperature Water outlet temperature External temperature (for Air/Water unit) Condenser water temperature (for Water/Water unit) NTC NTC NTC U5 Compressor 1 current Compressor 1 current U6 Compressor 2 current Compressor 2…
-
Digital inputs
EVD 1 – DI1 EVD 1 – DI2 EVD 2 – DI1 EVD 2 – DI2 (1) (2) Master Compressor 1 high pressure switch Compressor 1 overload/ Inverter 1 alarm (1,2) Compressor 2 high pressure switch Compressor 2 overload/ Inverter 2 alarm (1,2) Digital inputs EVD 3 – DI1 EVD 3 – DI2 EVD 4 – DI1 EVD 4 – DI2 Slave…
-
3.1.3 Digital outputs: single circuit version - inverter compressor (0-10V) (pCO5+ Medium - see table 2.3.1 page 9, type 1) Digital Description outputs Bitzer NO1 Compressor 1 inverter – Start Start NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 Compressor 1 inverter – Emergency shutdown…
-
3.1.5 Digital outputs: dual circuit version - stepless compressor (pCO5+ XL - see table 2.3.1 page 9, type 6) Digital outputs Min. NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 (1) Description Bitzer Hanbell…
-
3.1.7 Digital outputs: 3 circuit version - step compressor
Master board (pCO5+ XL - see table 2.3.1 page 9, types 4-5) Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Description Bitzer Hanbell RefComp Frascold Compressor 1 - Delta relay(2)/ Part Winding…
-
3.1.8 Digital outputs: 3 circuit version - stepless compressor
Master board (pCO5+ XL - see table 2.3.1 page 9, type 6) Digital outputs Min. NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Description Bitzer Hanbell RefComp Frascold - - - Compressor 1 - Delta relay(2)/ Part…
-
3.1.9 Digital outputs: 3-4 circuit version - step compressor
Master board (pCO5+ XL - see table 2.3.1 page 9, types 4-5) Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Description Bitzer Hanbell RefComp Frascold Compressor 1 - Delta relay(2)/ Part Winding…
-
3.1.10 Digital outputs: 3-4 circuit version - stepless compressor
Master board (pCO5+ XL - see table 2.3.1 page 9, type 6) Digital outputs Min. NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 NO11 NO12 NO13 NO14 NO15 NO16 NO17 NO18 NO19 NO20 NO21 NO22 NO23 NO24 NO25 NO26 NO27 NO28 NO29 Description Bitzer Hanbell RefComp Frascold - - - CR4 CR3 CR4 CR3 V1 V2 V1 V2…
-
Note: Consult the pCO5+ manual (code +0300020EN) for details on installing the pCO5+ controller hardware. +030221536 FLSTDmSCHE – rel 1.5 – 12/11/2014 18
-
3.2 Unit diagrams
Below are some details on the installation position for the probes referred to the first circuit. We recommend installing them in the position described. CMP EVAP ExV COND SOL M U1 U2 U3 S1 S2 S3 S4 Analogue inputs Water inlet temperature Water outlet temperature Outdoor temperature Suction pressure…
-
3.3 Probes installation
Some of the details regarding probe installation are described below. Positioning of discarge gas temperature probes They should be installed in the upper part of the piping at 30-40 cm from the attachment of the compressor flange so they are not influenced by the thermal mass of the compressor…
-
4. START UP
The following methods can be used to update the firmware and acquire the log files on pCO controllers: Smart Key programming key; pCO Manager, a program to install on the PC; an USB pendrive. The controller can be connected directly to the PC via the RS485 serial port used for the “pLAN”…
-
4.5 Setting the address using a terminal
4.4 Setting the controller’s address After setting the controller address (see previous paragraph), in order to establish the controller-terminal connection, the terminal address must be set. The controller’s pLAN address is factory-set as 1. There are two ways to set a controller’s address: using…
-
5. USER INTERFACE
5.1 Terminal pGD1 When the unit is off, zones 4 and 5 are hidden and the reason why the unit is off will be displayed. An example follows. The FLSTDmSCHE user interface is the pGD1 terminal in the wall versions, built-in or mounted directly in the pCO5+, thus "built-in". 5.3 User Menu The terminal…
-
Z5:HiSuctP: High suction pressure Z6:LoDP: Low differential pressure Z7:LoPRat: Low compression ratio Z8:LoDscgP: Low condensing pressure Z9:LoSuctP: Low evaporating pressure Compressor status: Off and countdown minimum off time On and countdown minimum on time Alarm Manual Forced…
-
5.4 MENU DESCRIPTION
5.4.2 Parameters code FLSTDmSCHE has a code for each individual parameter to clearly identify them. Only the parameters are coded and thus the values that can be accessed in read/write mode that characterise how the unit operates. The read only values are not coded. Each parameter has a 4 digit code…
-
6. FUNCTIONS
The PID controllers integrate the "anti-windup" function that limits the integral action when the request has reached the maximum and minimum limits. 6.1 Temperature control FLSTDmSCHE allows the control of the water input or output temperature for the unit. Regardless of the machine reversability…
-
Temperature
[°C] ON unit NOT OK ON pump Filter with low delay Thermoregulation enabling delay OK Flow alarm delay from pump startup Filter with high delay NOT OK Time [s] When the control temperature goes below the set (A028), a counter is activated and the time-out for that counter is changed depending on the…
-
Also the antifreeze prevention is performed using the evaporating
pressure probe. 6.3.3 Evaporator antifreeze management When the unit is off, FLSTDmSCHE manages the evaporator antifreeze (and the condenser one for Water/Water units) with a configuration parameter (A041) that prevents the icing of the water by means of a pump and/or antifreeze heaters. When the…
-
6.4 Compressor rotation
33% If only one compressor is present, the request generated by the thermoregulation will be exactly the percentage request that the compressor must meet. If, on the other hand, the machine is configured with two compressors, FLSTDmSCHE must manage the rotation logic of the compressors in order to…
-
In the pump-down, there are 6 control phases
6.4.3 Rotation for alarm In the event of an alarm for one compressor , the next available compressor will be turned on as a replacement if the request is high enough. For units with two circuits and prevention active in one circuit, the rotation will compensate for the limited compressor by…
-
CXW
CXHIT CXWIT In the pump-down, there are 6 control phases: Comp. Stand-by (open 25%) Stand-by (open 25%) Solenoid valve OFF OFF SH Control SH Control 0% ON ON ON Stand-by (open 25%) OFF ExV 1 OFF 2 Start-up + Pump-Down 3 Modulation 4 Shut-down 5 Minimum + Pump-Down 6 OFF 6.6 Compressor management…
-
Startup procedure duration
This parameter (Db50) specifies the duration of the compressor startup phase in which the valves have a preset behaviour to allow the compressor to reach the operating conditions. 6.6.4 Stepless modulation FLSTDmSCHE manages the stepless modulation of the screw compressors. The percentage request…
-
the maximum power must be distinguished as some compressors
use less time for the discharge phase. Since the valve is impulse controlled, the algorithm calculates the percentage of variation of the screw compressor capacity at each activation of the pulsating valve for decrease. The valve will then continue to pulse until the percentage requested by the…
-
Nota: Parameters Dc06 and Dc07 are needed for the correct
operation of FLSTDmSCHE with 0-10V inverter control and without Modbus connection. It should be noted that in no case these parameters are able to modify the settings of the inverter. Note: The pCO5+ can manage startup relay activations for the compressor with a precision of 20 ms. Therefore set…
-
The activation sequence is as follows
Request Compressor Relay R1 Compressor Relay R2 Star time Da41 Delay Star-delta Da40 Line Star Delta A A A The indirect control technique for the line contactor allows double breaking of the arc during the first phase of the star-delta switch and thus shorter switching times. In fact, the activation…
-
6.7 Eco control and liquid injection
3 Condensing temperature The controller manages two distinct digital outputs for controlling the Eco valve and the injection of liquid in the compressor. Both outputs are active only with the compressor on. 2 9 The Eco valve allows the cooling power to be increased and the compressor performance to…
-
6.9 Compressor alarm prevention
Discharge temperature The suction and discharge pressures determine a working point and depending upon the zone, the control perform corrective actions to maintain or bring the compressor within the operating limits. These actions can be disabled through the prevention enabling parameter (Da80). Max…
-
It will behave as follows: the antifreeze limit according to the mode (A028 in cold and C037 in hot with water/water unit). Device Compressor ExV Fan Description 1. Decrease of power increase speed 2. Power limitation - Compressor Condition Alarm Alarm 6.10 Compressor alarms management Controlled…
-
6.12 Condenser pump
Fan inverter FLSTDmSCHE manages up to two condenser side pumps (only for water/water units). The condenser side pump group is unique and can be made up of one or two pumps. As in the evaporator pump management, the condenser pumps are activated with the unit on and a delay can be set (C012) for…
-
Control in chiller mode Switching to the nominal setpoint is done gradually in the time (C017), according to the diagram below: Fan control can be modulating or ON-OFF and controls the saturated temperature value equivalent to the condensing pressure. Condensing setpoint Startup reg. setpoint C016…
-
The result is a perfect balancing between the capacity of FC coils
and evaporator, so that to maintain the same proportionality in each “capacity working point”, that is same reaction to same temperature variation with regardless to the load percentage. 6.14 Free-Cooling The Free-Cooling (FC) function can be enabled (parameter A044) on air-water unit, Chiller only…
-
Check defrost entry (1)
fans off, the heat that was just developed is not immediately dissipated. If the compressors are left on, the defrost phase is prolonged unnecessarily. Once defrost start condition is verified according to the criteria previously described, there is a parameter (C030) to delay the entry of the…
-
6.16 4-way valve control
A special management to assure the correct control of the 4way valve has been implemented. When a request of valve reverse is present, the application check if the pressure delta is higher than a threshold (Da2A) to command the valve: if the pressure delta is lower, the application waits until the…
-
7. PARAMETERS TABLE
The following table shows the parameters and values displayed by the terminal. 7.1 Info The info menu shows all the states of the various devices. No value is accessible in read / write. Default UOM Range Type R/W BMS index Rotation request compressor 1 circuit 1 0 % I R 223 Compressor 1 circuit 1…
-
Range
Type R/W BMS index Valve opening percent circuit 1 Discharge Superheat circuit 1 0.0 0.0 --°C/°F A A R R 21 14 Manual positioning enable - Circ1 0 D R 554 EVD status circuit 1 0 I R EEV position circuit 1 Superheat circuit 1 Rotation request compressor 1 circuit 2 0 0.0 0 --°C/°F % I A I R R R…
-
Range
Type R/W BMS index Condenser fan temperature probe value circuit 2 13.0 °C/°F A R 229 Number of defrost phase actually running circuit 2 0 I R 288 Condenser fan setpoint circuit 2 Condenser fan output request circuit 2 13.0 13.0 °C/°F % A A R R 5 10 Condenser fan circuit 2 in manual mode 0 D R Valve…
-
PWD
Description Default UOM Inverter frequency compressor 1 circuit 3 Compressor 1 phase countdown circuit 3 Suction temperature circuit 3 Suction pressure circuit 3 Evaporation temperature circuit 3 External temperature Condenser fan pressure probe value circuit 3 Condenser fan temperature probe value…
-
PWD
Description Default UOM Compressor 1 running phase circuit 4 (STEPLESS configuration) 0 Compressor 1 running phase circuit 4 (INVERTER configuration) 0 Inverter frequency compressor 1 circuit 4 Compressor 1 phase countdown circuit 4 Suction temperature circuit 4 Suction pressure circuit 4…
-
Range
Type R/W BMS index Compressor 1 circuit 1 working hours Compressor 1 circuit 1 working hours Compressor 1 hour threshold x1000h h x1000h I I I R R R Ignition type 1 0...999 0...999 0...999 0 1: wind.B 2: star I R 339 Position Compressor 1 circuit 1 start or PartWinding B 0 0...99 I R 224 D R 6 I R…
-
PWD
C005 Description UOM Range Type R/W BMS index 0 0 x1000h h 98: 097% 99: 098% 100: 099% 101: 100% 0...999 0...999 I I R R 57 62 Default 99 x1000h 0...999 I R 65 Condenser fan 1 circuit 1 working hours Condenser fan 1 circuit 1 working hours Circuit 1 condenser fan 1 maintenance hour threshold…
-
PWD
--Da03 Default UOM Range Type R/W BMS index Compressor 1 circuit 2 working hours Compressor 2 hour threshold Inverter request to compressor 1 circuit 2 Reset Inverter alarms compressor 1 circuit 0.0 0 h x1000h I I A I R R R R Reset Inverter alarms compressor 1 circuit 2 0 0...999 0...999 0.0...100.0…
-
PWD
Description Default UOM Range Position Condenser fan 1 circuit 2 0 Condenser 2 status 0 Digital output status of condenser fan circuit 2 0 C058 Condenser Fan 1 manual command circuit x1000h h C007 99 x1000h Condenser fan1 circuit 2 working hours Condenser fan 1 circuit 2 working hours Circuit 2…
-
PWD
Description Default UOM Range 0: Dsbl 1: Open 2: Clos 3: Int 4: Puls 0: Off 1: On 0...99 0: Dsbl 1: Open 2: Clos 3: Int 4: Puls 0: Off 1: On 0...99 0: Dsbl 1: Open 2: Clos 3: Int 4: Puls 0: Off 1: On 0...99 0: Off 1: On 0...1 0...99 0: Off 1: On 0...1 0...99 0: Off 1: On 0...1 0...99 0: Off 1: On…
-
PWD
Description Default UOM Range Position Condenser fan 3 circuit 3 0 Condenser fan 3 status circuit 3 0 Digital output status of condenser fan 3 circuit 3 0 C067 Condenser Fan 3 manual command circuit x1000h h C066 Condenser fan 3 circuit 3 working hours Condenser fan 3 circuit 3 working hours Circuit…
-
PWD
Description Default UOM Range Position Solenoid valve circuit 4 0 Solenoid valve circuit 4 status 0 Digital output value of solenoid valve circuit 4 Position 4way valve circuit Status of 4way valve circuit 4 0 Digital output value of 4way valve circuit 4 Position Eco compressor 1 circuit Eco…
-
таблицы и схемы — в просмотре
-
PWD
Description Default UOM Oil level circuit 1 0 Digital input 7 status 0 High pressure switch status circuit 1 0 EVD digital input 1 circuit 1 0 Overload of compressor 1 circuit 1 0 EVD digital input 2 circuit 1 0 Inverter RUN feedback compressor 1 circuit 1 0 Digital input 13 status 0 Inverter alarm…
-
PWD
Description Default UOM Remote alarm 0 Digital input 1 status 0 Summer/Winter selection by digital input 0 Digital input 2 status 0 Remote ON/OFF 0 0 0.0 0 0 0.0 0 Digital input 3 status EVDEVO Firmware version The fw in the EVDEVO connected is not compatible with the module The fw in the EVDEVO…
-
таблицы и схемы — в просмотре
-
PWD
-
Range
-
PWD
B018 S B019 B020 Description Default UOM Integral time LOP regulation in chiller mode 15.0 s S EEV Low evaporating temp. threshold in HeatPump mode -50.0 °C/°F S Integral time LOP regulation in heating mode 15.0 s B021 S EEV High evaporating temp. threshold in Chiller mode 20.0 °C/°F B022 S Integral…
-
таблицы и схемы — в просмотре
-
PWD
-
Range
-
таблицы и схемы — в просмотре
-
PWD
-
таблицы и схемы — в просмотре
-
PWD
-
таблицы и схемы — в просмотре
-
PWD
-
таблицы и схемы — в просмотре
-
Type
-
8. SUPERVISOR TABLE
FLSTDmSCHE can be connected to various systems of supervision, in particular can be used the following communication protocols BMS: Carel and Modbus. The connection is done by means of a BMS serial port. The various connection protocols are managed by the following option cards: Carel RS485: code…
-
Par
code Description Def. UOM Range R/W Variable name 40.0 2.0 4.0 30.0 -1.5 30.0 -0.8 0 50.0 0 °C/°F °C/°F A A A A °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F % % % -999.9...999.9 -999.9...999.9 -999.9...999.9 -999.9...999.9 -999.9...999.9 -999.9...999.9 0...999.9 -99.9...99.9 0...999.9 -999.9...999.9…
-
таблицы и схемы — в просмотре
-
Par. code Description Def. UOM Range R/W Variable name A048 B029 High water temperature alarm offset over setpoint High condensing temperature: integral time 6.0 -777.7 °C/°F 0..99.9 0...800.0 R/W R/W HighWaterTempOfs_Msk A57_HITCOND_Ti_msk 8.2 Integer variables MB Carel Index index Par. code Def.…
-
Par
code 5072 5073 5074 5075 5076 5077 5078 5079 5080 5081 5082 5083 5084 5085 5086 5087 5088 5089 5090 5091 5092 5093 5094 5095 5096 5097 5098 5099 5100 5101 5102 5103 5104 5105 5106 5107 5108 5109 5110 5111 5112 5113 5114 5115 5116 5117 5118 5119 C063 C068 C055 C060 C065 C070 ----------------C054 C059…
-
Par
code 5150 5151 5152 5153 5154 5155 5156 5157 5158 5159 5160 5161 5162 5163 5164 5165 5166 5167 5168 5169 5170 5171 5172 5173 5174 5175 5176 5177 5178 5179 5180 5181 5182 5183 5184 5185 5186 5187 5188 5189 5190 5191 5192 5193 5194 5195 5209 5210 5211 5212…
-
Par
code Description Def. UOM Range R/W 5241 240 Position Compressor 1 circuit 3 direct start 0 0...99 R 5242 241 Reset Inverter alarms compressor 1 circuit 3 0 0...32767 R 5243 242 Emergency shutdown Inverter compressor 1 circuit 3 0 0...32767 R 5244 5245 5246 5247 5248 5249 5250 5251 Start signal…
-
Par
code Description Def. UOM Range R/W Variable name 5320 5321 5322 5323 5324 5325 5326 5327 5328 5329 5330 5331 5332 5333 Da16 A012 Db57 Db58 Db59 ------------A043 --A025 Oil level alarm startup delay Startup PID --> Run PID delay Step 1 - Step 2 delay Step 2 - Step 3 delay Step 3 - Step 4 delay…
-
Par
code 5401 5402 5403 5404 5405 5406 5407 5408 5409 5410 5411 5412 5413 5414 5415 5416 5417 A019 Db17 Db27 Db37 Db47 Db18 Db28 Db38 Db48 Db63 Db51 --------Da40 Da41 5418 417 B033 5419 418 B034 5420 5421 5422 5423 5424 5425 5426 5427 5428 5429 5430 5431 5432 5433 5434 5435 5436 5437 5438 5439 5440 5441…
-
8.3 Digital variables
MB Carel Index index Par. code Description Def. UOM Range R/W Variable name 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1 0...1…
-
------------------------Q004 E001 E002 Evaporator pump 1 overload Evaporator pump 2 overload Condenser Flow switch status Condenser 1 overload Condenser 2 overload Condenser 3 overload Condenser 4 overload Remote alarm Summer/Winter selection by digital input Remote ON/OFF BMS ON/OFF Enable Setpoint…
-
Evaporator pump 2 flow alarm Evaporator pump 2 maintenance alarm Evaporator pump 2 overload alarm P-Memory expansion alarm or is absent P-Memory expansion alarm or is absent in Slave board Antifreeze alarm evaporator 1 Antifreeze alarm evaporator 2 Antifreeze alarm evaporator 3 Antifreeze alarm…
-
--------------------------------------------------------------------------------------------------A009 394 394 Low pressure alarm by pressure switch circuit 4 MOP alarm EVD circuit 1 MOP alarm EVD circuit 2 MOP alarm EVD circuit 3 MOP alarm EVD circuit 4 Driver offline alarm EVD circuit 1 Driver…
-
--------------------------C046 C043 C044 C042 ------------------------------------------------------------------E014 --------Da48 Da79 Da81 Da80 A044 E012 Da82 B038 A036 A037 ----A038 Digital output status of condenser fan circuit 4 Condenser fan 1 status circuit 1 Condenser fan 1 status circuit 2…
-
Da49 Da43 Da44 --------A013 A011 A033 A034 A035 E010 E011 ------------------------------------------------Da47 ----------B042 C004 A004 C047 circuit 2 Digital output status of Liquid Injection compressor 1 circuit 3 Digital output status of Liquid Injection compressor 1 circuit 4 Digital output…
-
Free cooling anomaly Inverter 1 offline (MBM 3.0) Inverter 2 offline (MBM 3.0) Inverter 1 alarm active (read by MBM3.0) Inverter 2 alarm active (read by MBM3.0) +030221536 FLSTDmSCHE – rel 1.5 – 12/11/2014 0...1 0...1 0...1 0...1 0...1 R R R R R Al_FC_Anomaly MBM_Comp1_InvOffline…
-
9. ALARMS
9.1 Alarms interface The red LED under the ALARM button can be: Off: no active alarm; Flashing: there is at least one active alarm and the display shows a screen that is not part of the alarms loop. On: there is at least one active alarms and a screen that is part of the alarms loop is…
-
AL028
AL029 AL030 AL031 AL032 AL033 AL034 AL035 AL036 AL037 AL038 AL039 AL040 AL041 AL042 AL043 AL044 AL045 AL046 AL047 AL048 AL049 AL050 AL051 AL052 AL053 AL054 AL055 AL056 AL057 AL058 AL059 AL060 AL061 AL062 AL063 AL064 AL065 AL066 AL067 AL068 AL069 AL070 AL071 AL072 AL073 AL074 AL075 AL076 AL077 AL078…
-
AL111
AL112 AL113 AL114 AL115 AL116 AL117 AL118 AL119 AL120 AL121 AL122 AL123 AL124 AL125 AL126 AL127 AL128 AL129 AL130 AL131 A132 A133 A134 A135 A136 A137 A138 A139 A140 A141 A142 A143 A144 A145 A146 A147 A148 A149 A150 A151 A152 A153 A154 A155 A156 A157 A158 A159 A160 A161 A162 A163 A164 A165 A166 A167…
-
A198
A199 A200 A201 A202 A203 A204 A205 Inverter comp.3 alarm Inverter comp.4 alarm Inverter comp.1 alarm by MBM Inverter comp.2 alarm by MBM Inverter comp.1 offline Inverter comp.2 offline Free cooling ineffective, outlet water temperature increasing. Outlet water high temperature alarm Reset Action…
-
CAREL
+030221536 FLSTDMSCHE - rel 1.5 — 12/11/2014 94
-
FLSTDmSCHE – rel 1.5 – 12/11/2014
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 Fax (+39) 049.9716600 http://www.carel.com - e-mail: carel@carel.com +030221536 FLSTDmSCHE – rel 1.5 – 12/11/2014 95