Инструкция на Программа Carel Standard Chiller Modular HP 1/4 для pCO1, pCO2, pCO3
Прикладная программа Standard Chiller Modular HP 1/4 Generic (код FLSTDmMSBE) для контроллеров pCO1, pCO2, pCO3 для чиллеров с винтовыми компрессорами Bitzer и вентилями Carel. Руководство пользователя. Документ на английском языке.
Загружаем документ…
Текст инструкции
-
Standard Chiller Modular HP 1/4 Generic
/Bitzer screw compressor and CAREL valve Application program for pCO1, pCO2, pCO3 User manual Manual Version: 1.4 dated 11/09/08 Program code: FLSTDmMSBE LEGGI E CONSERVA QUESTE ISTRUZIONI READ AND SAVE THESE INSTRUCTIONS
-
We wish to save you time and money!
We can assure you that the thorough reading of this manual will guarantee correct installation and safe use of the product described. IMPORTANT WARNINGS BEFORE INSTALLING OR HANDLING THE DEVICE PLEASE CAREFULLY READ AND FOLLOW THE INSTRUCTIONS DESCRIBED IN THIS MANUAL. The device this software…
-
1. Applications and functions performed by the software
Type of control unit AIR / WATER CHILLER • Chiller only • Chiller + Heat pump • Chiller + Freecooling WATER / WATER CHILLER • Chiller only • Chiller + Heat pump with gas reversing • Chiller + Heat pump with water reversing Type of control Proportional or proportional + integral control on the…
-
2. The user terminal
2.1 Type and operation Three different types of user terminal can be connected: 1. PGD0/semigraphic/6 buttons/4 rows - 20 columns/connection via telephone cable 2. LCD/15 buttons/4 rows - 20 columns/connection via telephone cable 3. Built-in display/6 buttons/4 rows - 20 columns (only on pCO² - pCO3…
-
Use of the buttons 2.3.1 PGD0 terminal with 6 buttons Button ALARM UP DOWN ENTER PRG PRG + ENTER ESC + ENTER 2.3.2 ALARM UP PRG ENTER ESC DOWN Description displays the alarms, mutes the buzzer and deletes the active alarms if the cursor is in the home position (top left corner), scrolls up the…
-
Button
SET POINT + Description Goes to the first screen of Set point parameters (S0). The Set point parameters are used to display/modify the unit working set point within the limits defined in the configuration PROGRAM Goes to the screen for entering the user password (P0) The user parameters are used to…
-
3. pLAN management between boards
The pLAN network identifies a physical connection between the cards (pCO1 pCO2, pCO3) and the external terminals. pLAN=p.CO L.ocal A.rea N.etwork.. The purpose of the pLAN network connection between the cards is to exchange variables among the cards with a logic decided by the program, in order to…
-
4. Installation of default values
When you have checked the connections between the cards and terminals, power up the pCO card/s*. When the machine is powered up, the software automatically installs the default values selected by CAREL for all the chiller and driver configuration parameters. This section tells you how to reset…
-
7. List of inputs/outputs
Inputs and outputs are listed below based on unit type. A number has been associated with each type of machine. This number is the program's main parameter because it identifies the inputs and outputs configuration. Using this list of inputs and outputs, select the number you require from the…
-
CHILLER UNIT + HEAT PUMP – MACHINE TYPE “1” DIGITAL INPUTS N° pCO2 / pCO3 MEDIUM Master (Address 1) Slave (addresses 2/3/4) ID 1 Serious Alarm Serious Alarm ID 2 Evaporator Flow-switch Evaporator Flow-switch ID 3 Remote ON/OFF Remote ON/OFF ID 4 Pump Thermal cutout ID 5 Low Pressure 2…
-
CHILLER UNIT WITH FREECOOLING – MACHINE TYPE “2” DIGITAL INPUTS N° pCO2 / pCO3 MEDIUM Master (Address 1) Slave (addresses 2/3/4) ID 1 Serious Alarm Serious Alarm ID 2 Evaporator Flow-switch Evaporator Flow-switch ID 3 Remote ON/OFF Remote ON/OFF ID 4 Pump Thermal cutout ID 5 Low Pressure 2…
-
WATER/WATER UNIT WITH MAX. 4 SCREW COMPRESSORS (UP TO 4 CAPACITY STAGES PER COMPRESSOR)
7.4 CHILLER-ONLY UNIT – MACHINE TYPE “3” DIGITAL INPUTS N° pCO2 / pCO3 MEDIUM Master (Address 1) Slave (addresses 2/3/4) ID 1 Serious Alarm Serious Alarm ID 2 Evaporator Flow-switch Evaporator Flow-switch ID 3 Remote ON/OFF Remote ON/OFF ID 4 Evaporator Pump thermal Cutout ID 5 Low Pressure 2…
-
CHILLER UNIT + HEAT PUMP WITH GAS REVERSING – MACHINE TYPE “4” DIGITAL INPUTS N° pCO2 / pCO3 MEDIUM Master (Address 1) Slave (addresses 2/3/4) ID 1 Serious Alarm Serious Alarm ID 2 Evaporator Flow-switch Evaporator Flow-switch ID 3 remote ON/OFF ID 4 Evaporator Pump thermal Cutout ID 5 Low Pressure…
-
CHILLER UNIT + HEAT PUMP WITH WATER REVERSING – MACHINE TYPE “5” DIGITAL INPUTS N° pCO² MEDIUM Master (Address 1) Slave (addresses 2/3/4) ID 1 Serious Alarm Serious Alarm ID 2 Evaporator Flow-switch Evaporator Flow-switch ID 3 Remote ON/OFF Remote ON/OFF ID 4 Evaporator Pump thermal Cutout ID 5 Low…
-
8. List of parameters
The table below describes program parameters along with the following additional information: screen code (screens have a code in the top right corner) to make identifying the parameter easier (screen), factory setting, upper and lower limits of the range within which values can be effected, unit of…
-
SCREEN
-
таблицы и схемы — в просмотре
-
SCREEN
MASTER SLAVE FACTORY VALUE Pump status in the event of evaporator or condenser flow switch alarm Solenoid-valve management set-point Solenoid-valve management differential Antifreeze heater setpoint Antifreeze heater differential Cycle reversing valve logic Type of freecooling control Antifreeze…
-
SCREEN
MASTER SLAVE FACTORY VALUE Dynamic proportional enabling factor Protection threshold for high temperature condensation Integral time for high temperature condensation TIMES → Delayed start due to evaporator flow-switch alarm Delayed steady state operation due to evaporator flow-switch alarm Delayed…
-
9. Screens
-
10. EVD 200 electronic expansion valve
The EV Driver module for piloting the electronic expansion valves (EEV) for the pLAN network, makes it possible to control intake superheating to enable the refrigerating unit to operate more efficiently and with greater versatility. Condensor We say efficiently, because by improving and stabilising…
-
CUSTOM VALVE CONFIGURATION If a CUSTOM valve is selected, the configuration levels shown below appear. Minimum Steps Minimum opening steps used only in repositioning to capacity change. Maximum Steps Maximum opening steps Closure Steps Steps to obtain a complete closure of the valve Extra Opening…
-
Kind of load step In this field, one must insert the kind of capacity control used in the circuit. The following choices are available: None or steps: compressor without load steps or with step load steps. Slow continuation: compressor with continuous modulation that is not particularly fast or with…
-
• Superheat neutral area Neutral area for PID control. In this setpoint context, the driver will stop the control and the valve not make any movements. The control starts again when the superheat exits the neutral area. Derivative time Derivative time of PID control. Avoid levels greater than 4…
-
WARNING! deleting the alarms means ignoring them, and consequently it is recommended to carefully check that the system is not damaged or malfunctioning or becomes unreliable (e.g.: if “recharge battery” is signalled, it probably means that the battery is not charged or is not connected, etc.…
-
Inlet temperature control
Employed Inputs: • Water temperature at evaporator inlet Employed Parameters: • Type of unit • Total number of compressors • Type of compressor capacity control • Number of Capacity Control Steps • Control set-point • Proportional band for control at inlet. • Type of control (proportional or…
-
Control of water /water chiller only units
Employed Inputs: • Water temperature at evaporator inlet • Water temperature at evaporator outlet • Water temperature at condenser inlet • Water temperature at condenser outlet Employed Parameters: • Type of unit • Total number of compressors • Type of compressor capacity control • Number of…
-
Control of water/water chiller unit with water reversing heat pump
Employed Inputs: • Water temperature at evaporator inlet • Water temperature at evaporator outlet • Water temperature at condenser inlet • Water temperature at condenser outlet Employed Parameters: • Type of unit • Total number of compressors • Type of compressor capacity control • Number of…
-
Types of controlled compressors Stepped capacity control A maximum number of four compressors are managed, with a maximum of four capacity control steps each. Capacity control is achieved by three relay outputs which, when suitably commanded, short-circuit the refrigerant thrust by the compressor…
-
Stepped capacity control with control at inlet
A description of stepped capacity control of 4 compressors with four capacity control steps each: C1P1 C2P1 P2 P3 P4 C3P1 P2 P3 C4P1 P4 P2 P3 P4 P2 P3 P4 Temperatura ingresso evaporatore Banda di regolazione Setpoint di regolazione All compressors and the relevant capacity control steps will be…
-
Configuration of continuous capacity control relays The control method of the capacity control relays differs for each compressor. Therefore, the software has a facility for configuring the enabling sequence according to the needs of different compressor manufacturers. For multi-card systems: as…
-
Power-up of compressors (temperature above point E) The compressors are powered up in sequence at a rate calculated by the set time required to reach maximum power. As there is no absolute measurement of the effective capacity, when the compressor is started it performs a forced unload cycle for a…
-
14. Compressor rotation
Compressor calls are rotated in order to equal the number of duty hours and power-ups among the devices. Rotation follows the FIFO logic: the first compressor to be powered up is the first to be powered down. At the initial stage, there may be considerable differences in the on-duty hours of the…
-
Forced capacity control Inputs used • Water temperature at evaporator outlet • Compressor delivery temperature • Condensation pressure • Current Parameters used • High delivery temperature prevention threshold • High delivery temperature prevention differential • High pressure prevention threshold •…
-
Solenoid-valve management. Inputs used: • Compressor delivery temperature Parameters used: • Solenoid-valve activation threshold • Solenoid-valve differential Outputs used: • Economizer solenoid-valve, oil-cooler, liquid-injection 17.1.1 Description of operation A digital output is provided for…
-
Condensation control Condensation can be performed in the following modes: • ON/OFF linked to compressor operation (without pressure transducers) • ON/OFF or modulating linked to reading by the pressure transducer (if the high pressure transducers were enabled) • ON/OFF or modulating linked to…
-
Defrosting control for water/air machines Employed Inputs: • battery B3 temperature (can be used as a pressure switch) • high pressure B7 • Input for defrosting pressure switch 1 Employed Parameters: • Inputs used for defrosting • Type of defrosting (simultaneous / separate/independent) • Type of…
-
Free Cooling Control Inputs used • Water temperature at evaporator outlet • Water temperature at inlet of Free Cooling battery • External air temperature Parameters used • Type of unit • Number of units • Type of condensation • Number of fans • Free Cooling valve type • Free Cooling type control •…
-
Free Cooling Thermostat Free Cooling control exploits the calculated control set point values (taking into account any compensation) and the set Free Cooling control differential. The control is based on the water temperature measured by the probe located at the evaporator outlet, considering the…
-
Free Cooling disabling conditions There are two main causes of the closure of the Free Cooling valve: the first depends on the external temperature conditions, and the second on thermostatic demand. The freecooling valve will be closed if the freecooling conditions are no longer present External T.…
-
Free Cooling ON/OFF valve with stepped condensation 21.6.1 Proportional control Here is an example of Free Cooling control with ON/OFF valve and three condensation steps. Differenziale Free Cooling Valvola ON/OFF Free Cooling V1 V2 5.0 % V3 Setpoint Free Cooling Temperatura Uscita Evaporatore The…
-
Differenziale Free Cooling
Differenziale Free Cooling 2 5.0 % Valvola ON/OFF Free Cooling 10 Volt Rampa 0÷10V Inverter 0 Volt Setpoint Free Cooling Temperatura Uscita Evaporatore The devices, whether they are valve or fans, will be activated in the second half of the control differential through the effect of the integrating…
-
21.10 0-10 Volt Free Cooling valve with inverter controlled condensation
21.10.1 Proportional control Differenziale Free Cooling Valvola 0÷10V Free Cooling Rampa 0÷10V Inverter 10 Volt 0 Volt Soglia % massima Soglia % minima apertura valvola velocità inverter Setpoint Free Cooling Temperatura Uscita Evaporatore The control proportional ramp of the Free Cooling valve will…
-
Control algorithm for Bitzer screw compressors Carel developed a second Algorithm according to the Bitzer specifications to manage and protect their compressors. By setting the “Compressor Type” parameter to “Bitzer Steps” or “Bitzer Stepless”, the compressor’s control algorithm is automatically set…
-
For each refrigerant, the polygon changes shape according to the following levels in the table
Absolute pressures Polygon points R22 With or without ECO to po tc pc R134a ECO With or without ECO to po Tc pc R407C With or without ECO to po tc pc 1 12,5 7,3 60,0 24,3 12,5 4,5 60,0 16,8 12,5 7,0 60,0 25,3 2 -10,0 3,5 60,0 24,3 -13,0 1,8 60,0 16,8 -8,0 3,5 60,0 25,3 3 -15,0 3,0 55,0 21,7 -15,0…
-
Zone G • above max. o If the limit is reached when already operational, the compressor is stopped immediately. On the contrary, only at the start, above this limit, the maximum capacity of the compressor is limited to 50% and this condition is allowed for a maximum of 5 minutes. If after 5 minutes…
-
Alarms Alarms are divided into three categories: - signal-only alarms (signal on the display, buzzer, alarm relay) - circuit alarms (deactivate only the corresponding circuit, signal on the display, buzzer, alarm relay) - serious alarms (deactivate the entire system, signal on the display, buzzer…
-
Description of operation
Every pCO unit is able to manage antifreeze control providing the water temperature probe at evaporator/condenser outlet is connected and enabled according to the type of unit being controlled. Antifreeze alarm Heater activation activation Antifreeze Setpoint Heater setpoint Antifreeze differential…
-
Code Driver card alarms Alarm description Probe driver 1 fault Diver 1 EEPROM error Diver 1 stepped motor error Diver 1 battery error High pressure on driver 1 Low pressure on driver 1 Low super-heat driver 1 Valve not shut while driver 1 being disabled High super-heat driver 1 Standby due to EEPROM…
-
Alarm log The alarm log can store the standard chiller’s operating state when alarms are generated or at particular times. Each record represents an event that can be displayed from the list of all the events available in the memory. The log is used to resolve problems and faults as it represents a…
-
AL:019
AL:020 AL:021 AL:022 AL:031 AL:032 AL:033 AL:034 AL:035 AL:036 AL:037 AL:041 AL:051 AL:052 AL:053 AL:060 AL:061 AL:062 AL:063 AL:064 AL:065 AL:066 AL:067 AL:090 AL:101 AL:102 AL:103 AL:104 AL:105 AL:106 AL:107 AL:108 AL:109 AL:114 AL:115 AL:116 AL 201 AL:202 AL:203 AL:204 AL:205 AL:206 AL:207 AL:208…
-
25.1.1.1 Key
A Analogue variable D Digital variable I Integer variable IN OUT IN/OUT Input variable Output variable Input/output variable pCO Å Supervisor pCO Æ Supervisor pCO ÅÆ Supervisor Type A A A A A A A A A A A A A A A A A Direction OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT…
-
Type
D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D Direction OUT OUT OUT OUT IN/OUT IN/OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT…
-
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 Fax (+39) 049.9716600 http: // www . carel . com - e-mail: carel @ carel . com Cod. CAREL +030221296 – rel. 1.4 – 11/09/08 Agency