SEQUENCE CONTROLLER
Date: SEPT, 2003 Replaces: 506B-01/04B User manual Programme code: Ref: SEQ3.04
-
OPERATING LIMITS
The McQuay sequencer is capable of controlling a system of Chillers or Heat Pumps, installed in a single system, in order to control the common leaving water temperature of the evaporators, for improved and complete system management. The McQuay sequencer can control up to a maximum of 10 units…
-
FEATURES OF THE PROGRAMME The programme allows full management of a refrigerator plant consisting of several refrigerators. The features of the system are as follows: display and control of the measured sizes; possible configuration of the number of refrigerators to be controlled; LED display of…
-
Front view with front door open Figure 3 references COMPRESSORS Bar Bar °C °C °F °F FANS 1. 2. 3. 4. SET 2 SET EXT NETWORK Polycarbonate - coated mechanical buttons Function indicator LEDs Adhesive polycarbonate Silicone rubber buttons. Figure 3 2.4 Use of the buttons permits display of values…
-
Display COMPRESSORS Bar Bar °C °C °F °F FANS SET 2 SET EXT NETWORK Figure 4 Features • number of digits: 6 • colour: green • height: 13mm • number of side indicator LEDs: 5 • number of LEDs indicating the displayed function: 3+3 2.6 Function indicator LEDs The 5 LEDs placed beside the display have…
-
LIST OF PARAMETERS All parameters in boldface are described from page 12 In the following tables there are two Default columns: in the right column there are the values determined by McQuay. Default values are stored in the memory of every system (see page 21). In the left column the user may write…
-
Printer button
Description Code Pr1 Pr2 Default immediate printing request (only if P42=1) cyclic printing time setting (only if P42=1) 0 60 Defined Limits Units of measurement 0→disable 1→enable 0÷999 min I/O button Code Description Default Ai1 Ai2 Ai3 Ai4 i1 i2 i3 i4 i5 i6 i7 i8 i9 i10 i11 i12 Ao1 Ao2 o1 o2 o3…
-
C10
C11 C12 C13 C14 C15 C16 C17 C18 C19 C20 C21 C22 year setting band start hour with secondary set band end hour with secondary set Sunday with secondary set Monday with secondary set Tuesday with secondary set Wednesday with secondary set Thursday with secondary set Friday with secondary set Saturday…
-
Programming button
Code Description Default Defined Limits Unit of measurement PSn P1 password for access to programming section probe ELWT type (refrigerated water control) 0 2 P4 P5 P6 P10 P11 P12 P13 P14 number of devices controlled by probe ELWT number of devices operating in the event of probe ELWT failure number…
-
P39
P40 P41 P42 P43 P44 P45 P46 P47 °C or °F display remote on/off enable clock enable printer enable identification number automatic or manual reset alarms alarm relay operation delay ON/OFF button disable with machine ON serial communication baud-rate P61 P62 machine stop mode cold/hot 0 0 0→°C;→°F…
-
ALARM DESCRIPTION For description of how to control Alarms, see parameter P44 on page 18 Alarm button Code AL 1 AL 2 AL 3 AL 4 AL 5 AL 6 AL 7 AL 8 AL 9 AL 10 AL 11 AL 12 AL 13 AL 14 AL 15 AL 17 AL 18 AL 19 AL 20 AL 21 AL 22 AL 23 AL 24 AL 25 AL 26 AL 27 AL 28 AL 29 AL 30 AL 31 AL 32 AL 33 AL 34 AL…
-
DESCRIPTION OF PARAMETERS t1÷t12 - refrigerator hour display These parameters indicate the number of operating hours of the individual refrigerators. When displaying these parameters, the identification number code alternates, every two seconds, with the number of operating hours of the refrigerator…
-
C22 - time band exclusion end
The end of time band exclusion with secondary set is required (see parameter C20). Caution: do no enable at the same time the time bands with reduced setpoint and regulation of setpoint from analogue input because both options have priority over the setpoint set. St3, St5 - minimum setpoint They…
-
SL1, SL2 - low temperature alarm threshold
It represents the threshold of low of probe ELWT and CTWR respectively. When the value detected by the probe falls below the set value, the alarm is activated. SC, dC, dt - setpoint, differential and compensation delta See parameter P23. P1, P24 - probe type The parameters make it possible to…
-
P11 - minimum refrigerator stop time
This sets the minimum refrigerator stop time. The refrigerators are not started again unless the minimum time set from the last stop time has elapsed. ON OFF ON OFF connecti on device P11 Figure 8 P12 - minimum time between startups of different refrigerators This represents the minimum time that…
-
These parameters indicate the integration time of circuits ELWT and CTWR, if a Proportional + Integral regulation has been selected (P15=1 and/or P30=1). P17, P32 - minimum refrigerator startup request time These parameters allow the setting of the time between successive requests for startup of the…
-
P21 - function not enabled
P22 - external air temperature probe enable (see figure 30) This parameter enables the presence of an external air temperature probe with the possibility of effecting compensation of the setpoint relating to probe ELWT. P23 - probe 1 compensation enable If parameter P22 is activated (P22=1), then it…
-
P43 - identification number
The parameter allows the setting of the unit identification number (useful only in case of connection to a system of supervision and/or remote assistance). P44 - alarms with automatic or manual reset P44=0 ⇒ automatic. In the event that one or more alarm conditions are detected, these are indicated…
-
P61 - not enabled
P62 - cold/hot With this parameter it will be possible to decide whether the devices belonging to circuit ELWT are used to produce cold (P62=0; e.g. refrigerators) or hot (P62=1; e.g. heat pumps). • • proportional band cold 1 2 differential set • • • • n pressure or temperature • • 1 pressure or set…
-
The relevant probe is broken or not connected. Check the wiring and functional capacity of the probe. If AL14 is present, the devices programmed with the P5 parameter are forced to start up, and the inverter of device no.1/valve, if enabled, is forced to 10 volts. The remaining devices can be…
-
CONNECTIONS For an exhaustive description of the hardware and of the installation procedure please refer to the Microtech II “Installation and Usage manual", available on request. 6.1 Hardware architecture Terminal with LED or LCD display programme eprom Connector for RS422 serial board Connection…
-
Figure 18 references, page 22
10W (see note on page 28) 1. Power supply connector 24V~50-60 Hz 15VA or 24V 2. Telephone-type connector for connection to the user terminal (MMI-Man Machine Interface) 3. Real-time clock board (optional) 4. RS422/RS485 optoinsulated board (optional) for connection to a monitoring remote assistance…
-
MEANING OF INPUTS AND OUTPUTS Power supply CONNECTOR J17 – 1 G SIGNALS J17 – 2 J1 – 2 G0 +24 DESCRIPTION Power supply + 24 V 10 W or 24V~50/60 Hz 15 VA (see note on page 28) Power supply reference (max. power that can Power supply for external active probes 24 V be supplied: 80mA Connection with…
-
J24 – 6
-
Installation of EPROMs
Before connecting / disconnecting the EPROM, shut down power to Microtech II board. For correct operation of the system, the EPROM must be connected to the appropriate socket on the main board, ensuring that the “notch” on the surface of the EPROM matches one marked on the socket. Connect the EPROM…
-
APPENDIX A: TROUBLESHOOTING Unit does not start (mains ON LED on main board is off, LCD is off, other LEDs are off). Check: a) that there is mains voltage; that downstream of the 230V~ - 240V~ power voltage transformer there are 24V~; b) that 24V~ power connector has been correctly plugged in; c)…
-
CARE