Инструкция на Контроллер-диспетчер MicroBMS.
Контроллер-диспетчер MicroBMS для управления сетью фанкойлов. Инструкция по эксплуатации.
Смотрите также: Руководство по эксплуатации →
Загружаем документ…
Текст инструкции
-
User manual
Manuel d’utilisation Benutzerhandbuch Manuale operativo Manual de utilización µBMS English Français Deutsch Italiano Communicating electronic regulation control unit Centrale de supervision pour régulation électronique communicante Überwachungszentrale für elektronische Kommunikationsregelung…
-
We have designed our new µBMS mini control unit to
manage system operation and temperature control of both individual and medium size heating, ventilation and air conditioning installations. ✔ Control and programming of ON / OFF, standby, time Being easy to use, it provides effective management of from 1 to 15 different temperature zones. This…
-
3 - Basic functions
3.1 - Switching on the µBMS Press the key to switch on the µBMS mini control unit. The set temperature point should appear on the display. 3.2 - Ventilation (fan) speed selection Press the key to select the fan speed. Each press on the key will make the following symbols appear for selection : Low…
-
3.5 - Setting the desired temperature in AU mode (automatic Heating/Cooling mode
changeover with 2 set temperature points) 1 For this procedure, the AU mode must have been enabled when the µBMS mini control unit was initialised during commissioning. 2 Press the key several times until the symbol appears on the display. By so doing, AU appears in the upper left hand temperature…
-
4 - Quick procedure for setting the time and day
Follow the procedure below if your control panel is already installed and wired on site and you just want to set the time, day and basic parameters : 4.1 - To access time and day settings Press the flashing. key until the time and day values start You now have access to the time and day setting…
-
Access to the various µBMS parameters
The operations for setting parameters and values as detailed below are only possible when the µBMS mini control unit is switched OFF by pressing the ON/OFF key (no temperature shown on the LCD display). 5.1 - How to access the µBMS parameter setting mode ? 1 Press both the and keys simultaneously…
-
5 - Commissioning (setting the µBMS mini control unit parameters) – (cont'd)
5.4 - Activate /deactivate the timer programming function You can activate or deactivate the timer programming function by pressing the key. Mon timer symbol appear, and press Press once to make the again to make it disappear. 1 UNIT timer symbol is displayed, the user has access to When the the…
-
5 - Commissioning (setting the µBMS mini control unit parameters) – (cont'd)
5.8 - Setting the regulation zone number This function is directly dependent on the installation and its architecture. In fact, you must determine the number of different zones in your system, i.e. locations with different occupied and unoccupied patterns (e.g. office blocks and storage areas) as…
-
6 - Using the Copy / Paste function for setting zone parameters
When you wish to use the same programming profile for several different regulation zones, it is possible to use the Copy and Paste function, indicated by the symbol on the screen and by the key. Once one zone has been programmed from Monday to Sunday, you can copy and then paste these settings into…
-
7 - Programming examples
The temperature is not displayed if the remote control is switched OFF. 7.1 - Global control programming (Zone 0) °C Mon °C 19 °C 14 °C 1 Mon 14 °C 2 AUTO AUTO UNIT UNIT Stage 1 Stage 2 In this programming example, all the fan coil units will operate in HEAT and AUTO ventilation modes, with a set…
-
7 - Programming examples (continued)
7.2 - Personalised programming (Zone 1) °C 22 °C Mon 1 STOP 14 °C AUTO 22 °C °C STOP Mon 14 °C 2 AUTO UNIT UNIT Stage 1 Stage 2 In this programming example, all the fan coil units in Zone 1 will operate in HEAT and AUTO ventilation modes, with a set temperature point of 22 °C from 7h00 to 12h00…
-
7 - Programming examples (continued)
7.3 - Personalised programming (Zone 2…up to Zone 15) °C 21 °C STOP Mon 1 STOP 14 °C AUTO 21 °C °C Mon 14 °C 2 AUTO UNIT UNIT Stage 1 Stage 2 In this programming example, all the fan coil units in Zone 2 will operate in HEAT and AUTO ventilation modes, with a set temperature point of 21 °C from 8h00…
-
8 - Programming to achieve energy savings
Example : In business premises with the following opening hours : Select ZONE 0 by pressing the UNIT keys. Morning : 9h to 12h - Afternoon : 15h to 20h. STAGE 5 : ON : -:-- OFF : 21h00 In summer, you wish to maintain the following set temperatures : STAGE 6 : ON : -:-- OFF : 22h00 Press the HOUR is…
-
Backlighting
Just repeat this operation to unlock the keypad. Then, a different series of audible warning sounds is emitted and The liquid crystal display back lighting illuminates when the control unit passes into Configuration / Initialisation mode and when any key is pressed. the IR triangle returns to its…
-
10 - µBMS min control unit installation and wiring
It is necessary to choose the right location for µBMS min control unit in the room in which it is to be installed. It should be installed at a height of 1.5 metres from the floor and it should be easily accessible. It is important to choose a location away from any direct or indirect heat source…
-
Connect the µBMS mini control unit GND terminal to the NIU interface board GND terminal. Carry out the same operation for the 12 V terminal. Finally, connect the µBMS mini control unit RS 485 terminals to the NIU interface board µBMS terminals (the RCW terminal is intended for a different purpose).…
-
12 - Wiring the 1st NIU interface board to the 2nd NIU interface board
Connect the µBMS terminals of the first NIU interface board to the µBMS terminals of the second NIU interface board and connect the µBMS terminals of the second NIU interface board to the µBMS terminals of the third NIU interface board and so on until the last NIU interface board is connected. The…
-
Addressing performed in accordance with the following table implies that all the fan coil units situated in the same zone will receive the same settings. ZONE 1 - 2 fan coil units ZONE 2 - 1 fan coil unit Addressing 0001 ZONE 3 - 2 fan coil units Addressing 0011 Addressing 0010 Addressing 0001…
-
15 - Connecting an Aqu@logic unit to the Aqu@Net system bus
������� ����� Master terminal block ✔ Maximum length : 1000 m of wire in RS 484 bus up to the µBMS mini control unit. 12 V GND 1 2 Slave terminal block ✔ 0.4 to 0.65 mm diameter twisted pair cable with 120 Ω impedance shield : AWG 22 to 26. ✔ Maximum of 15 zones for 80 units and one Aqu@logic.…
-
42 cours Jean-Jaurès 17800 PONS - FRANCE Tél. : +33-5 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Dans un souci d’amélioration constante, nos produits peuvent être modifiés sans préavis. Photos non…