Каталог продукции DELTA Battery 2019 - Свинцово-кислотные аккумуляторы
Загружаем документ…
Текст каталога
-
ID
-
DELTA lead-acid
rechargeable batteries DELTA is a brand of reliable leadacid VRLA batteries (Valve Regulated Lead Acid), presented on the Russian market since 2001. DELTA is widely used in telecommunications, security systems, access control, power supply systems for mobile operators’ base stations, solar and wind…
-
UNIVERSAL
BATTERIES UPS SERIES 5 years DT pages 2-5 6 years DTM pages 6-9 years 10-12 DTM L pages 10-13 years 10-12 DTM I pages 14-17 years 8 HR pages 18-21 8 years HR-W pages 22-25 12 HRL-X pages 26-29 10-12 GEL pages 30-33 years 15 GX pages 34-37 10 FT-M pages 38-41 years SOLAR SERIES SPECIAL PURPOSE years…
-
DELTA lead-acid batteries of DT series
are specially designed for use in low current systems and optimized for buffer operation. They are manufactured using AGM technology (Absorbent Glass Mat an electrolyte absorbed in a fiberglass separator). DELTA DT series batteries have low internal resistance and high energy density. They meet…
-
In buffer mode over 65Ah – 7-10 years Service life up to 40Ah – 1000 cycles at 30% discharge depth, In cyclic mode over 65Ah – 1100 cycles at 30% discharge depth. Self-discharge Less than 3% per month Charging method DC voltage charging 25°С Cyclic mode 2,4-2,5 V/cell Temperature compensation - 5…
-
Capacitance (%)
TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE (5 YEARS) 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE (5 YEARS) Charging voltage 2.27 - 2.3 V/cell Service life (years) Voltage (V)…
-
100% discharge 50% discharge
-
DELTA lead-acid batteries of the DTM
series are sealed, maintenance-free with a gas recombination system (VRLA). They are manufactured using AGM technology (Absorbent Glass Mat - an electrolyte absorbed in a fiberglass separator). The DTM series is universal and is recommended for use in both buffer and cyclic operation - in various…
-
6 years
In buffer mode 1200 cycles at 30% discharge depth Service life Self-discharge Less than 3% per month Charging method DC voltage charging 25°С Cyclic mode 2,35-2,4 V/cell Temperature compensation - 5 mV/cell°C Buffer mode 2,25-2,3 V/cell Temperature compensation - 3.3 mV/cell°C Terminal diagrams 4,8…
-
UNIVERSAL
BATTERIES Capacitance (%) TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE Charging voltage 2.25 - 2.30 V/cell Service life (years) 8
-
Type
Voltage, V Capacitance, Ah* Length (±2), mm Width (±2), mm Height (±2) max, mm DTM 6012 6 1.2 0.31 B Knife F1 DTM 6032 6 3.2 0.69 B Knife F1 DTM 6045 6 4.5 0.78 A Knife F1 DTM 1.2 B Knife F1 DTM 1.85 B Knife F1 DTM 12008 12 0.8 0.4 G AMP DTM 12012 12 1.2 0.61 F Knife F1 DTM 12022 12 2.2 B Knife F1…
-
UNIVERSAL BATTERIES DELTA lead-acid batteries of the DTM L series are sealed, maintenance-free with a gas recombination system (VRLA). They are manufactured using AGM technology (Absorbent Glass Mat - an electrolyte absorbed in a fiberglass separator). submersible pumps and boilers of heating…
-
10-12 years
In buffer mode 1250 cycles at 30% discharge depth Service life Self-discharge Less than 3% per month Charging method DC voltage charging 25°С Cyclic mode 2,35-2,4 V/cell Temperature compensation - 5 mV/cell°C Buffer mode 2,25-2,3 V/cell Temperature compensation - 3.3 mV/cell°C Terminal diagrams For…
-
UNIVERSAL
BATTERIES Capacitance (%) TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE Charging voltage 2.25 - 2.3 V/cell Service life (years) 12
-
Type
-
DELTA sealed lead-acid batteries of the
DTM I series are manufactured according to AGM technology (electrolyte absorbed in a fiberglass separator), equipped with an LCD display showing the battery operation status. The DTM I series belongs to the Long Life range with a lifetime of up to 12 years, with the possibility of increasing it by…
-
10-12 years
In buffer mode 1250 cycles at 30% discharge depth Service life Self-discharge Less than 3% per month Charging method DC voltage charging 25°С Cyclic mode 2,35-2,4 V/cell Temperature compensation - 5 mV/cell°C Buffer mode 2,25-2,3 V/cell Temperature compensation - 3.3 mV/cell°C Terminal diagrams For…
-
Capacitance (%)
TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE Charging voltage 2.25 - 2.3 V/cell Service life (years) 16
-
Type
-
DELTA lead-acid batteries of the HR
series are sealed, maintenance-free with a gas recombination system (VRLA). They are manufactured using AGM technology (Absorbent Glass Mat - an electrolyte absorbed in a fiberglass separator). Thanks to this technology, the batteries have excellent discharge characteristics. The HR series belongs to…
-
In buffer mode Delta HR 12-40, HR 12-65, HR 12-100 – 10-12 years old Service life Up to 26Ah inclusive – 1200 cycles at 30% discharge depth. Delta HR 12-40, HR 12-65, HR 12-100 – 1300 cycles at 30% discharge depth In cyclic mode Self-discharge Less than 3% per month Charging method DC voltage…
-
Capacitance (%)
TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE (5 YEARS) 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE (8 YEARS) Charging voltage 2.25 - 2.3 V/cell Service life (years) 20
-
100% discharge
-
DELTA lead-acid batteries of the HR-W
series are sealed, maintenance-free with a gas recombination system (VRLA). They are manufactured using AGM technology (Absorbent Glass Mat - an electrolyte absorbed in a fiberglass separator). The HRL-W series is part of DELTA UPS series designed specifically for use in uninterruptible power supplies…
-
8 years
In buffer mode 1200 cycles at 30% discharge depth Service life Self-discharge Less than 3% per month Charging method DC voltage charging 25°С Cyclic mode 2,35-2,4 V/cell Temperature compensation - 5 mV/cell°C Buffer mode 2,25-2,3 V/cell Temperature compensation - 3.3 mV/cell°C Terminal diagrams…
-
Capacitance (%)
TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE Charging voltage 2.25 - 2.3 V/cell Service life (years) 24
-
Type
-
DELTA lead-acid batteries of the HRL-X
series are sealed, maintenance-free with a gas recombination system (VRLA). They are manufactured using AGM technology (Absorbent Glass Mat - an electrolyte absorbed in a fiberglass separator). Thanks to optimized technology, the batteries have excellent discharge characteristics over the entire time…
-
12 years
In buffer mode 1300 cycles at 30% discharge depth Service life Self-discharge Less than 3% per month Charging method DC voltage charging 25°С Cyclic mode 2,35-2,4 V/cell Temperature compensation - 5 mV/cell°C Buffer mode 2,25-2,3 V/cell Temperature compensation - 3.3 mV/cell°C Terminal diagrams…
-
Capacitance (%)
TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE Charging voltage 2.25 - 2.3 V/cell Service life (years) 28
-
Type
-
SPECIAL
PURPOSE SERIES, GEL TECHNOLOGY DELTA sealed lead-acid batteries of GEL series are manufactured according to AGM+GEL technology: combined AGM and GEL technology. DELTA batteries of GEL series (from 33 Ah) are equipped with an integrated controller and an LCD display showing the battery operation…
-
10-12 years
In buffer mode 1400 cycles at 30% discharge depth Service life Self-discharge Less than 3% per month Charging method DC voltage charging 25°С Cyclic mode 2,35-2,4 V/cell Temperature compensation - 5 mV/cell°C Buffer mode 2,25-2,3 V/cell Temperature compensation - 3.3 mV/cell°C Terminal diagrams…
-
GEL TECHNOLOGY
Capacitance (%) TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE Charging voltage 2.25 - 2.3 V/cell Service life (years) 32
-
Type
Voltage, V Capacitance, Ah* Length (±2), mm Width (±2), mm Height max (±2), mm Weight, kg Body Terminal type GEL12-15 3.7 D Knife F2 GEL12-20 5.3 E Bolt + nut Ø 5.5 mm GEL12-26 8.1 E For M5 bolt GEL12-33 10.6 B Bolt + nut Ø 6.4 mm GEL12-45 14.1 E For M6 bolt GEL12-55 12 55** 16.7 B For M6 bolt…
-
SPECIAL
PURPOSE SERIES, GEL TECHNOLOGY DELTA GX series lead-acid monoblocks are manufactured using GEL technology. A composite gel is used as an electrolyte, which ensures deep discharge resistance and high temperature stability of Delta GX batteries. Designed for operation in both buffer and cyclic modes.…
-
15 years
In buffer mode 1400 cycles at 30% discharge depth Service life Self-discharge Less than 3% per month Charging method DC voltage charging 25°С Cyclic mode 2,25-2,3 V/cell Temperature compensation - 5 mV/cell°C Buffer mode 2,35 - 2,4 V/cell Temperature compensation - 3.3 mV/cell°C Terminal diagrams…
-
GEL TECHNOLOGY
Capacitance (%) TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE Charging voltage 2.25 - 2.3 V/cell Service life (years) 36
-
Voltage, V
-
DELTA maintenance-free front-end
lead-acid batteries of series FT-M are manufactured according to AGM technology with an absorbed electrolyte. Thanks to this technology, the batteries do not need to be refilled with distillate throughout their lifetime. Housing is optimized for installation in 19» and 23» telecommunication cabinets…
-
10-12 years
In buffer mode 1300 cycles at 30% discharge depth Service life Self-discharge Charging method Less than 3% per month DC voltage charging 20°С Cyclic mode 2,35-2,4 V/cell Temperature compensation - 30 mV/cell°C Buffer mode 2,27 - 2,3 V/cell Temperature compensation - 20 mV/cell°C Terminal diagrams…
-
FT-M TECHNOLOGY
Capacitance (%) TEMPERATURE INFLUENCE ON THE CAPACITANCE Temperature (°C) Capacitance (%) SERVICE LIFE IN CYCLIC MODE 100% discharge 50% discharge 30% discharge Number of cycles Capacitance (%) SERVICE LIFE IN BUFFER MODE Charging voltage 2.27 - 2.3 V/cell Service life (years) 40
-
Type
-
CT
STARTER BATTERIES DELTA CT Series lead-acid batteries are specially designed for systems that use multiple powerful discharges. Scopes of application: • Motorcycles • Scooters They meet international safety standards and are recommended for use in motorcycles, scooters, water motorcycles, quad…
-
таблицы и схемы — в просмотре
-
EPS
STARTER BATTERIES DELTA starter batteries of EPS (Extreme Power Series) series are sealed, maintenance-free lead-acid batteries manufactured according to NANO-GEL technology especially for motor vehicles with high energy consumption. EPS series is designed for starting engines in extreme temperature…
-
Voltage, Capacitance,
V Ah Type Length, mm Width, mm Height Weight, max, kg mm Starting current, CCA (-18°C), A Polarity Body Terminal type (*) В Bolt + nut 6 mm EPS 1214 4.6 220 direct (+ -) EPS 1216 5.86 230 reverse (- +) Е Bolt + nut 6 mm EPS 1218 6.5 270 direct (+ -) В Bolt + nut 6 mm EPS 1218.1 5.96 250 direct (+ -)…
-
www.delta-batt.com
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.